7 | Fire-Resistive Construction (1 st part) Exercises

Session 13 | Codes | Gary Parker. 7 | Fire-Resistive Construction (1 st part) Exercises . Given: the 1-hr exterior wall shown is located 12 feet from an interior property line. It has protected openings as shown.

Download Presentation

7 | Fire-Resistive Construction (1 st part) Exercises

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Session 13 | Codes | Gary Parker 7 | Fire-Resistive Construction (1st part) Exercises

  2. Given: the 1-hr exterior wall shown is located 12 feet from an interior property line. It has protected openings as shown. Determine: the maximum area permitted for unprotected openings

  3. Given: the 1-hr exterior wall shown is located 12 feet from an interior property line. It has protected openings as shown. Determine: the maximum area permitted for unprotected openings

  4. All of the following building components may be used to create a fire area except . • fire walls • fire barriers • exterior walls • fire partitions • Reference d Sec. 702.1 • A projection is considered a building element that extends beyond the of a building. • exterior wall • fire area • building area • floor area • Reference d Sec. 704.2

  5. 3 For wall and opening protection and roof covering requirements, an imaginary property line shall be placed between . • court walls • fire areas • buildings on the same lot • different occupancies • Reference c Sec. 704.3 • 4 In a nonsprinklered building, what is the maximum area of unprotected exterior wall openings for a fire separation distance of 8 feet? • 10% • 25% • unlimited • unprotected openings are prohibited • Reference a Table 704.8

  6. 5 In a fully-sprinklered office building, what is the maximum area of unprotected exterior wall openings for a fire separation distance of 5 feet? • 10% • 15% • 25% • unprotected openings are prohibited • Reference b Sec. 704.8.1, Table 704.8 • 6 A parapet is not required for those buildings having a maximum floor area of square feet on any floor. • 400 • 1000 • 1500 • 3000 • Reference b Sec. 704.11, Exception 2

  7. 7 A parapet is not required on the exterior wall of a fully sprinklered building located a minimum of feet from an interior property line. • >5 • >10 • >15 • >20 • Reference a Sec. 704.11, #6; 704.8.1 • 8 The measurement between the face of an exterior wall and the closest interior lot line is described as the . • fire separation distance • fire exposure setback • clearance to construction • exterior fire exposure • Reference a Sec. 702.1

  8. 9 In a building of Type I or II construction, nonbearing exterior walls having a maximum fire-resistance rating of are permitted to be constructed of fire-retardant-treated wood. • 0 hours (no rating is required) • ½ hour • 1 hour • 2 hours • Reference a Sec. 603.1, #1.2 • 10 Show windows may be of combustible construction in Types I and II construction where located a maximum of above grade. • 15 feet • 35 feet • one story • three stories • Reference a Sec. 603.1, #6