Partial discharge patterns for silicone rubber insulators under salt-fog

Partial discharge patterns for silicone rubber insulators under salt-fog. Lopes, I.J.S.; Jayaram, S.H.; Cherney, E.A. Electrical Insulation and Dielectric Phenomena, 2001 Annual Report. Conference on , 14-17 Oct. 2001. Abstract.

Download Presentation

Partial discharge patterns for silicone rubber insulators under salt-fog

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Partial discharge patterns for silicone rubber insulators under salt-fog Lopes, I.J.S.; Jayaram, S.H.; Cherney, E.A.Electrical Insulation and Dielectric Phenomena, 2001 Annual Report. Conference on , 14-17 Oct. 2001

  2. Abstract • Silicone rubber insulators in a salt-fog chamber 에서의 누설전류(LC)의 진전을 학습하기 위하여 pd를 사용하였다. • Low-level LC와PD 측정 : dead-end type silicone rubber insulators • PD 신호처리 : maximum , mean charge • PD 경향 : moving average technique • Silicone rubber insulators 의 초기열화단계 연구.

  3. Introduction • 외부절연체는 low free surface energy, resist wetting and inherently hydrophobic 을 가지는 polymeric material 을 사용. • 누설전류와 소수성의 상실로 인하여 물질의 성질을 잃을 수 있다. • LC 신호는 초기에 검출되고 초기열화단계를 더 잘 정의하지만 ,LC와 insulators surface condition과의 관계는 완전하게 알려져 있지 않다. • 초기 열화 단계동안 insulators 에서의 Pd 존재의 검출은 중요하다. • Signal processing techniques - PD data 의 저장 - PD 의 형상 추출 - moving average technique 를 사용하여 PD 경향 취득.

  4. Experimental setup and procedure • Fig 1 참조. -acrylic box. two IEC type nozzles(a flow rate of 0.5 liters/min). -voltage : 5kVA,60Hz,220V/100kV testing transformer (regulating transformer 3.1kVA,0-140V magnetic circuit breaker • LC 측정 : 챔버 접지에 100 ohm 의 shunt resister 를 삽입하여 오실로스코프로 측정한다. • Pd 측정 : simultaneous sampling data acquisition board 사용 • PD와 LC측정회로 모두 surge protection system 적용 • Silicone rubber insulators는 챔버안에 수평하게 장착한다. • 모든 측정에서 New and clean 한 insulators 사용

  5. Experimental setup and procedure • 염무하에 있는 insulators에 일정한 전압을 가하여 PD와 LC 를 동시에 측정하였다. • LC level : 시험하는 동안 매 5분마다 측정, average values and waveform을 연속적으로 관측. • PD 측정 : 시험하는 동안 계속 측정. • 각각 90cycle 2 min = a total 2700cycle 60 min • 매 사이클마다 적용된 전압에 따라 평균과 최대값을 저장 분석함. • PD 경향 : 5-minute window frame 을 사용하여 moving average technique 를 적용하여 취득.

  6. Experimental setup and procedure • Two insulator design - 3 sheds (creepage = 305mm) - 4 sheds (creepage = 356mm) • 안개생성을 위한 물의 전도성 : 1800uS/츠 • Two voltage : 8kV , 10kV • The average stress on the surface

  7. Result and discussion • lc 를 8,10kV 적용시 시간의 함수로 보임(Fig 2). • 3-sheds 가 4-sheds 에 비해 누설전류가 많다.(이유: creepage 거리) • 3-sheds being almost zero : 8kV(20분) 10kV(10분) • 10kV 3-sheds 인 경우 8kV에 비해 높은 값을 보이고 있다. (이유 : higher average stress) Fig 2. Development of Leakage Current

  8. Result and discussion • 3-sheds 는 shorter creepage 때문에 higher average stress보임. • PD level : 3-sheds > 4-sheds • LC 보다 PD 가 더 가변적이고 격렬한 반응을 보인다. • Fig 3,4 는 simple moving average technique 를 적용. Fig 3. Partial discharge recorded at 8kV Fig 4. Partial discharge recorded at 10kV

  9. Result and discussion • Calculating a moving average - two or more data 획득 , 평균을 냄 , 다음 data 와 더해서 평균냄 계속 반복하면서 남아있는 데이터 끝까지 계산함.

  10. Result and discussion • Fig 5,6 은 5-minute window frame 사용하여 획득. • 3-sheds 가 4-sheds 에 비해 higher value 를 가짐. • Fig 5에서 8kV일때 최대와 평균그림에서 two plateaus 를 보임. (40 and 60 min , 60 and 75 min) • Around 60 min = sudden change (이유 : the transition between corona from water droplets and dry-band arcing) Fig 5.PD trends at 8kV obtained with the moving average technique Fig 5.PD trends at 10kV obtained with the moving average technique

  11. Summary • 염무하에 있는 두 종류의 silicone rubber insulators의 LC와 PD를 동시에 측정하였으며, 누설전류의 징후를 PD 로 보여주었다. • Moving average technique 으로 PD level 의 경향을 보였으며, sharp 하게 변하는 부분은 dry-band discharge 와 관계한다. • 최대, 평균 PD 값은 PD 변화의 패턴을 분명하게 나타내는데 사용되었다.