220 likes | 384 Views
ezPAC SA320/330. April 2011. SATEC 25 years of Innovation in measurement & management of Energy and Power Quality. The Full Range of Electricity Management Solutions for Every Application. PAS. eXpertpower™ Server ( SaaS ). eXpertpower™ Server (Pro Edition). Internet. eXpertpower™. LAN.
E N D
ezPACSA320/330 April 2011
SATEC25 years of Innovation in measurement & management of Energy and Power Quality
The Full Range of Electricity Management Solutions for Every Application PAS eXpertpower™ Server (SaaS) eXpertpower™ Server (Pro Edition) Internet eXpertpower™ LAN ETC2002 RS232/422/485, Profibus, TCP/IP, Dialup modem, GPRS, RF Modbus RTU, ASCII, DNP3.0, Modbus/TCP, DNP3/TCP, IEC 61850 PM130 PLUS BFM136 C192PF PM172 PM296 PM174/5 EM720 EM920 ezPAC Substation Automation Asset Management Power Measurement Fault Recording Energy Efficiency & Cost Allocation Revenue Metering Energy Management & Billing Smart Grid & Demand Response Power Quality Analysis Multi-Tenant Submetering UTILITIES & RENEWABLE COMMERCIAL & INDUSTRIAL ALL
Universities Gas Pharmaceutical Transportation Transmission Data Centers Supermarkets /Wholesale Banks Process Industry Generation OEM COMMERCIAL INDUSTRIAL UTILITIES Mining Telecom Hi-Tech Automotive Distribution Sports Semiconductors Residential
ezPAC SA320/330 6-in-1 solution: • Revenue Metering • Power Quality • Distributed Fault Recorder • Sequence of Events (SoE) • Backup Protection Equipment • Devices Control
Substation Automation • Relay Target Information • Get all of the information available from a digital relay without replacing the electromechanical one • Add-On Protective Relaying Backup • Under / over frequency relay • Automatic load shed & restore (0.01 Hz with adjustable time delay) • Reclosing relay • Multi-shot automatic reclosing • Synchro-check and LLDB/LBDL supervision • Permit / block reclose • Phase angle, slip frequency, LLDB/LBDL control • Time over-current relay backup • Back up prime TOC relay curve with up to 32 current magnitude and duration set-points • Various Communication protocols • Modbus • DNP3.0 • IEC 61850
Sequence of Events (SoE) • Four types of events: • digital input • relay output • Fault • Set-point • Each input point is programmableto be NO or NC • Programmable status words • Programmable De-bounce times 1-256 msec • Up to 160 discrete inputs – wet or dry contacts
Fault Recorder • 4 measured currents • IRIG-B time synchronization • Up to 20 minutes of continuous recordingwith 256 MB memory • Programmable fault thresholds and hysteresis • Up to 150 amps fault currents (30 x In) • Zero-sequence currents and voltages • Current and voltage unbalance • Under-voltage, neutral current • Ready-to-use fault reports—fault currents magnitude and duration, coincident volts magnitude, faultwaveforms and RMS • Distance to fault calculation • Multi-feeder (up to 3) fault recorder • Waveforms from 2 separate locations (via PAS)
Power Quality Recorder • Class A IEC 61000-4-30 Power Quality analysis: • Sags/swells (dips/over-voltages), interruptions, frequency variations, Flicker, voltage unbalance, harmonic and inter-harmonic voltages • Programmable thresholds and hysteresis • Built-in EN50160 statistics & reports • Redundant auxiliary power supply for recording major dips & interruptions • Harmonics & inter-harmonics according to IEC 61000-4-7 • Directional power harmonics and power factor phasors • THD, TDD and K-Factors • Symmetrical components • Flicker measurement according to IEC 61000-4-15 • Selectable sampling rate up to 256 samples/cycle • Event recorder for logging internal diagnostic events, control events and I/O operations • Waveform & data recorder
Transient Recorder • Transient pulses as short as 20μs at 50 Hz (17μs at 60 Hz) • Up to 1024 samples per cycle • Amplitude relative to ground as per EN 50160 (4 channels) • Up to 2kV measurement, 6kV withstand
Case StudySubstation Automation System (SAS) • SATEC products (ezPAC, PM175 and PM130) are the heart of the substation automation system (SAS) solution provided by NPT throughout the entire Russian Federation • Two configurations: • Comprehensive for220 and 750kV • Standard for 6, 10,35 and 110 kV
Key Design Concepts • SATEC IEDs provide protection, automation, measurement and control functions • SCADA-system for operational control • Open system concept reduces dependency on vendors • Standard protocols for IED and HMI communication • Wide use of Factory Acceptance Testing (FAT) • Integration of substation protection and automatics into control software
Bay controllers RTU SA300-330 SATEC ezPAC SA330 bay controllers are used on lower level to collect digital, analogue information as well as to control switchgear.
PM175 • Power Quality Analysis (EN50160, IEEE 1159 and GOST 13109-97) • Time Of Use (TOU) • Accuracy Class 0.2S • RTC and 10-year calendar • Full galvanic isolation • Non-volatile memory • Registration of parameters on set-point or time
ezPAC IEC 61850 Protocols • IEC 61850-7-2,3,4 • Basic communication structure for substation and feeder equipment – Abstract communication service interface (ACSI), Common Data classes, Compatible logical node classes and data classes • IEC 61850-8-1 • Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO 9506-1 and ISO 9506-2) and to ISO/IEC 8802-3 • IEC 61850-10 • Conformance testing
Implementation in NPT Expert SAS IEC 61850 configurator and system driver allow: • IED configuration reading • Data receiving via read requests and via event reports referenced by Report Control Blocks • Files downloading (in particular COMTRADE files) • Data Sets configuration • Report Control Blocks and GOOSE Control Blocks configuration