200 likes | 346 Views
Outdoor unit. Branch joint. Outdoor unit. 室外机. Controller. Connection by the branch joint completely. 分支接头. 室外机. 控制器. 纯粹由分支接头的连接. Branch Joint Selection. Connection type of branch joint/ branch header:. After the branch header no more branching is permitted. Model. Branch joint
E N D
Outdoor unit Branch joint Outdoor unit 室外机 Controller Connection by the branch joint completely 分支接头 室外机 控制器 纯粹由分支接头的连接 Branch Joint Selection Connection type of branch joint/ branch header:
Model Branch joint (2 branch) MDS-Y1 MDS-Y2 MDS-Y3 MDS-Y4 MDS-Y5 Branch header (4 branch) MDS-C1 MDS-C2 MDS-C3 Selection of branch joint / header for MDS
Diameter & thickness requirement for refrigerant copper pipe A-series
Diameter & thickness requirement for refrigerant copper pipe B-series
Piping selection & unit selection Cooling cap. factor
Piping selection & unit selection Heating cap. factor
Example Selection step: 1. Selection of diameter for piping 2. Selection of branch A B C MDS100AR MCC020 MCK020 MCK020 D E MCC015 MCK020 MCC010
Selection step: 1. Piping dia selection 2. Branchselection 1) Main pipe & terminal pipe dia. (Equivalent length<90m) Main pipe:φ15.88 / φ28.6 Terminal pipe : (Same as indoor units) 2) Calculate the downsteam cap. Of point A 4) Same as item 3 B-C Dia: Φ9.52 / φ19.05 A-B-C: 17.4 KW D-E Dia: Φ9.52 / φ15.88 A-D-E: 11.8 KW 3) Select the dia. from the table A-B Dia: Φ12.7 / φ25.4 A-D Dia : Φ9.52 / φ19.05
Selection step: 1. Selection of diameter for piping 2. Selection of branch 1) Select the branch of point A A(Liquid):MDS-Y2 A(Gas): MDS-Y1 2)Same as item 1 B (Liquid):MDS-Y2 C (Liquid):MDS-Y2 B (Gas): MDS-Y1 C (Gas):MDS-Y4 E (Liquid):MDS-Y2 D (Liquid):MDS-Y2 E (Gas):MDS-Y2 D (Gas):MDS-Y4
Additional Charge of Refrigerant Using liquid tube length to calculate required refrigerant → Add in refrigerant Formula: G=∑ Li* Gi G Refrigerant charge amount Li The each section of liquid tube lengthin all(m) Gi Charge amount per length(g/m)
A B C MDS100AR MCK020 MCC020 MCK020 D E MCC015 MCK020 MCC010 Additional Charge of Refrigerant Complete selection of pipe & branch 60m(5/8) 6m(1/2) 8m 8m 8m 8m 8m 8m 7m(1/4) 7m 7m(1/4)
Additional Charge of Refrigerant Additional charge amount G: G=180*60+120*6+80*55+50*14 =6900 (g)
MDS unit selection software McQuay MDS unit selection software