1 / 20

Branch Joint Selection

Outdoor unit. Branch joint. Outdoor unit. 室外机. Controller. Connection by the branch joint completely. 分支接头. 室外机. 控制器. 纯粹由分支接头的连接. Branch Joint Selection. Connection type of branch joint/ branch header:. After the branch header no more branching is permitted. Model. Branch joint

jericho-nen
Download Presentation

Branch Joint Selection

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Outdoor unit Branch joint Outdoor unit 室外机 Controller Connection by the branch joint completely 分支接头 室外机 控制器 纯粹由分支接头的连接 Branch Joint Selection Connection type of branch joint/ branch header:

  2. After the branch header no more branching is permitted

  3. Model Branch joint (2 branch) MDS-Y1 MDS-Y2 MDS-Y3 MDS-Y4 MDS-Y5 Branch header (4 branch) MDS-C1 MDS-C2 MDS-C3 Selection of branch joint / header for MDS

  4. MDS-Y1~Y4 dimensional drawing

  5. MDS-Y5 dimensional drawing

  6. MDS-C1 dimensional drawing

  7. MDS-C2~C3 dimensional drawing

  8. Diameter & thickness requirement for refrigerant copper pipe A-series

  9. Diameter & thickness requirement for refrigerant copper pipe B-series

  10. Piping selection & unit selection Cooling cap. factor

  11. Piping selection & unit selection Heating cap. factor

  12. Example Selection step: 1. Selection of diameter for piping 2. Selection of branch A B C MDS100AR MCC020 MCK020 MCK020 D E MCC015 MCK020 MCC010

  13. Selection step: 1. Piping dia selection 2. Branchselection 1) Main pipe & terminal pipe dia. (Equivalent length<90m) Main pipe:φ15.88 / φ28.6 Terminal pipe : (Same as indoor units) 2) Calculate the downsteam cap. Of point A 4) Same as item 3 B-C Dia: Φ9.52 / φ19.05 A-B-C: 17.4 KW D-E Dia: Φ9.52 / φ15.88 A-D-E: 11.8 KW 3) Select the dia. from the table A-B Dia: Φ12.7 / φ25.4 A-D Dia : Φ9.52 / φ19.05

  14. Selection step: 1. Selection of diameter for piping 2. Selection of branch 1) Select the branch of point A A(Liquid):MDS-Y2 A(Gas): MDS-Y1 2)Same as item 1 B (Liquid):MDS-Y2 C (Liquid):MDS-Y2 B (Gas): MDS-Y1 C (Gas):MDS-Y4 E (Liquid):MDS-Y2 D (Liquid):MDS-Y2 E (Gas):MDS-Y2 D (Gas):MDS-Y4

  15. Additional Charge of Refrigerant Using liquid tube length to calculate required refrigerant → Add in refrigerant Formula: G=∑ Li* Gi G Refrigerant charge amount Li The each section of liquid tube lengthin all(m) Gi Charge amount per length(g/m)

  16. A B C MDS100AR MCK020 MCC020 MCK020 D E MCC015 MCK020 MCC010 Additional Charge of Refrigerant Complete selection of pipe & branch 60m(5/8) 6m(1/2) 8m 8m 8m 8m 8m 8m 7m(1/4) 7m 7m(1/4)

  17. Additional Charge of Refrigerant Additional charge amount G: G=180*60+120*6+80*55+50*14 =6900 (g)

  18. MDS unit selection software McQuay MDS unit selection software

  19. MDS control & monitoring software