An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Good Manufacturing Practices: HVAC Heating, Ventilation and Air- Conditioning (HVAC) Part 2: Air flows, Pressure concepts WHO Technical Report Series, No. 961, 2011. Annex 5

  2. HVAC Objectives To continue from previous section of Part 1, now focus on: • Air filtration and air flow patterns • The role of HVAC in dust control • HVAC system design and its components (part 3) • Commissioning, qualification and maintenance (part 4)

  3. HVAC Air Filtration • Degree of filtration of air is important to prevent contamination • Type of filters to be used is dependent on: • Quality of ambient air, • Return air / re-circulation • Air change rates • National requirements • Products and required class of clean room etc. • Manufacturer to determine, select and install appropriate filters for use 4.2.1, 4.3.3

  4. HVAC Levels of protection and recommended filtration 4.2.1 - 2

  5. HVAC Contamination can be prevented by considering: • Appropriate materials of construction of HVAC components • Placement of components (e.g. upstream of final filters) • Design and appropriate access (from outside) to dampers, filters and other components • Personnel operations and protection • Airflow direction • Air distribution component design, installation and location • Diffusers (type, design, location) • Air supply and air exhaust location 4.2.4 – 4.2.10

  6. HVAC Induction diffuser

  7. HVAC Perforated plate

  8. HVAC Swirl type diffuser

  9. HVAC Airflow patterns • Filtered air entering a production room or covering a process can be • turbulent, or • unidirectional (laminar) • GMP aspect • economical aspect • Other technologies: barrier technology/isolatortechnology.

  10. Unidirectional/laminar displacement of dirty air Turbulent dilution of dirty air HVAC Airflow patterns

  11. HVAC

  12. Airflow patterns Prefilter AHU Main filter 2 3 1 Unidirectional Turbulent Turbulent HVAC

  13. HVAC Unidirectional airflow (UDAF) Often used in weighing and sampling areas (Airflow Protection Booths) and provides: • Dust containment and product and operator protection Note: For Airflow Protection Booths (APB): • Airflow velocity should not affect balance (may be lower than for Class A areas) • Position of material, balance, operator determined and validated – no obstruction of airflow or risk 4.3

  14. HVAC Airflow patterns Workbench (vertical) Cabin/booth Ceiling

  15. HVAC Unidirectional airflow (UDAF): • Sampling and weighing area classification – same as other processing areas following sampling and dispensing • Dust containment shown through smoke tests as part of validation / qualification • Location and type of return and exhaust grilles • Cleaning and maintenance • Will discuss examples in the following figures 4.3.

  16. HVAC

  17. HVAC

  18. HVAC

  19. HVAC

  20. HVAC

  21. HVAC

  22. HVAC

  23. HVAC Infiltration • Prevent infiltration of unfiltered, contaminated air from outside • Facilities normally under positive pressure to the outside • Building structure well sealed • Some cases - negative pressure (e.g. penicillin manufacture). Special precautions to be taken. See separate guidelines 4.4.1 – 4.4.4

  24. HVAC Cross-contamination • Multiproduct facility – even if in different areas - risk for cross contamination (dust from area to area) • Correct direction of air movement and pressure cascade • Normally, corridors positive to cubicles and cubicles positive to atmosphere • Consider building structure, ceilings, walls, doors etc • Different concepts discussed in following slides 4.5

  25. HVAC Displacement concept • Not a preferred method (Found in older facilities) • Based on low pressure differentials and high airflows • Air supplied to the corridor – then through the doors (grilles) to the cubicles • Air extracted at the back of the cubicle • Velocity high enough to prevent turbulence in doorway 4.6

  26. HVAC Pressure differential concept • Used where there is low dust in areas. Alone or in combination with other control techniques • High pressure differential, low airflow, and airlocks • Airlock types include: Cascade, sink and bubble type (See next slides) • Sufficient pressure differential required to ensure containment and prevent flow reversal – but not so high as to create turbulence • Consider effect of other items such as equipment and extraction systems in cubicles 4.7

  27. HVAC • Essential / critical parameter here is pressure differentials • Risk assessment may be done • High enough to achieve containment; low permissible when airlocks are used • No flow reversal should take place – therefore appropriate limits e.g. 5Pa to 20 Pa • No turbulence • No overlap (two adjacent rooms) 4.7

  28. HVAC • Adequate room pressure differential indication provided • Each critical room pressure must be traced back to ambient pressure (by summation of the room pressure differentials) – provides actual absolute pressure • Gauges with appropriate range and graduation scale to enable accurate reading; analogue or digital; as pressure differentials or absolute pressures • Normal operating range, alert and action limits defined and displayed • OOS condition should be easily identifiable 4.7

  29. HVAC

  30. HVAC • Calibrated and qualified monitoring devices, verified at intervals • Linked to alarm system • Monitoring and recording of results • Doors open to higher pressure, self closers • Doors interlocked where possible 4.7

  31. HVAC • Dust extraction system design is important as it may impact on pressure cascade • Central systems interlocked with AHUs • No airflow between rooms through common system • What happens in the case of component failure? 4.7

  32. HVAC Airlocks and Material Pass-though-hatches (PTH) • Can be used to separate two zones • Dynamic and passive PTH • Also designed as bubble, sink or cascade • See next slides for design principles 4.7

  33. HVAC

  34. HVAC What type of airlock is this? How does it work? Any examples of where It can be used?

  35. HVAC Physical barrier concept • In some cases, impervious barriers are used to prevent cross-contamination • Closed systems • Pump or vacuum transfer 4.8

  36. HVAC Temperature and relative humidity (RH) • Consider materials and product requirements as well as operator comfort in the design of the HVAC • Where conditions are required, provide for control, monitoring and recording • Alert and action limits; minimum and maximum limits • Premises appropriately designed • HVAC design to achieve and maintain conditions in different seasons 4.9

  37. HVAC Relative humidity (RH) • Low RH areas need well sealed walls and ceilings, and preferably air locks • Remove or add moisture as necessary • Dehumidification • Refrigerated dehumidifiers - cooling media • Chemical dehumidifiers • Humidifiers should not be sources of contamination • Use of pure steam or clean steam • No chemicals that can have a detrimental effect 4.9

  38. HVAC Relative humidity (RH) • Humidifiers should be well drained - no accumulation of condensate • Avoid evaporative systems, atomizers, water-mist sprays • Suitable duct material • Insulation of cold surfaces • Air filters not immediately downstream of humidifiers • Chemical driers – used if not sources of contamination 4.9

  39. Dust Control Where possible - dust and vapour removed at source Point of use extraction – fixed points or movable hood – plus general directional airflow in room Ensure sufficient transfer velocity in extraction system to prevent dust settling in ducting Calculations and measurements Periodic checks for build up Risk analysis – airflow direction HVAC 5.1. – 5.6

  40. HVAC Dust Control (2) • Normally air supplied through ceiling diffusers, near the door • Air extracted from low level (rear) • Extraction of vapours – consider density of vapour • Handling harmful products – additional steps needed • e.g. barrier technology, glove boxes • totally enclosed garments with air-breathing systems • Fresh air rate supply • comfort, odour and fume removal, leakage, pressure control, etc. 5.7. – 5.8.

  41. HVAC

  42. HVAC

  43. HVAC

  44. HVAC

  45. HVAC Exhaust air dust • Exhaust air from equipment and some areas of production can carry heavy loads of dust, vapours and fumes (e.g. FBD, coating, weighing) • Filtration may be needed to protect environment (see National legislation) • Location of the inlet and exhaust points relative to one other important to prevent contaminants taken into inlet air Dust collection system 6.1.1 – 6.1.2

  46. HVAC Exhaust air dust • Wet scrubbers can also be used • Contaminated air is collected • Dust is treated with a mist/spray / water • Clean air is exhausted