370 likes | 543 Views
X. INCREASING TEMPERATURE - HEATING A. Heating system requirements Optimum inside temperature Uniform temperature Prevent hot air on plants Low cost Fuel available Automated. Energy Loss from Greenhouse. B. Heating terminology refer to physical principles
E N D
X. INCREASING TEMPERATURE - HEATING A. Heating system requirements • Optimum inside temperature • Uniform temperature • Prevent hot air on plants • Low cost • Fuel available • Automated
B. Heating terminology • refer to physical principles C. Factors affecting heating • Q = Qc + Qi • Qc = U x A x (ti-to) • Qi = .018 x V x N x (ti-to) Q - heat loss Qc - conduction & radiation heat loss Qi - infiltration heat loss U - heat transfer coef. A - area of coverings ti-to - inside set pt – coldest temp
1. House surface area vs volume • Surface area • Reducing surface area • lower eaves • ridge and furrow • shape of house perimeter & surface area correlated 2. Temperature differential • (ti -to)
3. Covering: Number of layers • Heat transfer coeffieicnt • 2 layers 40% less energy than 1 • 3 layers 16% less energy than 2 4. Types of coverings • Heat transfer coefficient 5. Air leakage • Tight house vs loose house • Leaks around fans, doors, vents • Thermal radiation
6. Side walls • Heat transfer coefficient 7. Structure - conductional heat loss • 8% more loss through metal than wood • Frame on double layer not exposed to outside 8. Wind • Sweep away boundary layer
D. Sources of heat 1. Fossil fuels • Major: Coal Natural gas Oil Propane • Minor: Wood chips Straw Wheat Sawdust 2. Electricity
3. Other possible sources • Generating plants • Natural gas compression stations • Ethanol plants • Geothermal • hot springs • ground water • underground caverns
E. Types of Heating Systems • hydronic • forced air • Infrared 1. Hydronic - water or steam a. heating process • conduction • convection • radiation
b. Steam vs hot water • boiler • steam higher pressure • steam cools faster
c. boiler • fuel - gas, coal, propane • operation and maintenance • manual or automatic control
d. distribution system • sidewalls, under benches, above benches • 2) circulate air • natural • forced convection • 3) finned pipe • 2/3 along side wall, 1/3 under benches
Forced Air - Unit Heater a. Types • hot water or steam • boiler required • fuel fired unit heaters • Fuel burned in house • Air distribution • forced convection • electricity
b. distributing heat from unit heaters • Polytube • Heater fan and HAF c. problems arising from heat distribution • Hot air on plants • Uneven temperatures • Incomplete combustion CH3-CH2-CH2- + O2 -----> CO2 + H2O + (CH2-Ch2, CO, SO2) • Remedy • 1 sq in/2000BTU/hr for air inlet
3. Infrared Heater a. Principles • Energy not absorbed by air • Leaves, etc., absorb energy • Increase in temp. • Air warmed • conduction - leaves, etc., to air • convection - air rises b. Possible less condensation • Plants warmer than air at night • Air up to 7 deg cooler • Other systems - plants cooler than air at night • Radiation heat loss • Transpiration
c. Energy savings • 30-70% • Fuel combustion 90% • Less temperature differential • Air up to 7 deg cooler • Less energy loss • Do not use circulation fans • Less electricity • Installation cost higher
Bottom heat Can provide 25-50% of heat during winter a. Root system warmer b. Natural air currents c. Water • small rubber tubes on bench or floor • Finned pipe under bench • Plastic pipe in floor d. Electricity • Resistance coil
e. Advantages • Uniform temperature • Crop time reduced • Reduced disease • Root rot- soil dries faster • Foliar - leaves warm less condensation • Crop uniformity • Compact plants • Zone flexibility
Bottom Heating Bottom heating: tube placement
F. Special Heating Needs 1. Propagation • Warm bottom temperatures • Cable, pad, pipe under bench 2. Sterilization/pasteurization • Steam best if available
G. Using Less Energy 1. Conservation • Seal cracks • Burner efficiency • Insulation - side walls, north wall • Double layer • movable curtains • Foam between polyethylene • Styrene beads
2. Management practices • Optimum space utilization • progressive spacing • movable benches • grow under benches • hanging baskets • Reduce container size • Improved varieties • faster production • cooler temp. requirements
2. Management practices (cont) • Supplemental lighting • CO2 increase • Reduce crop losses • Reduce night temperature
Supplemental heating: collect and store solar radiation