An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. btrc.masdar.ac.ae • Optimal Control of Chiller Condenser Sub-cooling, Compressor Speed, Tower Fan and Pump Speeds, and IGV • Omer Qureshi, Hassan Javed & Peter Armstrong, June 2013

  2. Presentation Outline • Introduction • SCADA and Heat Balance Analysis • Component Models • Chiller System Solver • Optimization • Conclusion and Future Work

  3. Introduction • Plant under consideration-(4x2500T). • Collection and analysis SCADA • Development of sub models for Individual chiller components • Validation of model • Development of solver- to execute these sub models and predict chiller performance. • Optimize the model to produce set of conditions for optimum power consumption.

  4. District Cooling Plant • Selected District cool Plant • Capacity (4x2500T) • Shell and tube Evaporator and Condenser • Constant speed single stage centrifugal compressor • Capacity control by Pre-rotation vanes • Surge control Variable geometry diffuser • 2-cell cooling tower each with variable speed fan (Fan diameter: 8m) • Variable speed chilled water pump • Constant speed condenser water pump

  5. Chiller Unit 1. Maintenance manual of York Chiller(Source: Tabreed)

  6. SCADA & Heat Balance Analysis

  7. Components Models—Chiller Unit • Steady-state models based on first principle • Inputs • Component engineering parameters • SCADA Data • Simple models, less computation time • Four Component models for district cooling plant • Evaporator Model----Shell and tube • Condenser Model----Shell and tube • Centrifugal Compressor Model (Isentropic work + loss Mechanism) • Constant speed • Variable speed • Variable speed pump model

  8. Evaporator Model Assumptions: • No pressure drop considered for refrigerant side • Thermal resistance from refrigerant side is neglected.

  9. Evaporator Model • Two regions for refrigerant were modeled: • Evaporation • Superheating • 𝞮 – NTU Method • Single Stream HX for evaporation • Crossflow HX for super heating Evaporator 1st Pass 2nd Pass

  10. Evaporator Model • Equations utilized in Evaporator Model

  11. Evaporator Model • Equations utilized in Evaporator Model Equation for regressed length: Equation for temperatures:

  12. Evaporator Model 1. Maintenance manual of York Chiller(Source: Tabreed)

  13. Evaporator Model

  14. Condenser Model Assumptions: • No pressure drop considered for refrigerant side • Thermal resistance from refrigerant side is neglected.

  15. Condenser Model Condenser 1st Pass 2nd Pass • Three regions for refrigerant were modeled: • Sub-cooling • Condensation • De-Superheating • 𝞮 – NTU Method

  16. Condenser Model • Equations utilized in Condenser Model 1a. Sub-Cooling Section(First Pass):

  17. Condenser Model 1b. Condensation Section (First Pass): Mixing Section:

  18. Condenser Model 2a. Condensation Section (Second Pass): 2b. De-superheating Section (Second Pass):

  19. Condenser Model

  20. Condenser Model

  21. Compressor Model • Integral and mathematically most complex part of chiller • Constant and variable speed compressor model • Non-Dimensional loss model based on Aungier(2000)

  22. Compressor Model-Inputs and Outputs • Constant Speed Model • Variable speed Model

  23. Validation Constant Speed Compressor Model

  24. Validation Constant Speed Compressor Model

  25. Variable Speed Compressor Model Loss Model Calculations

  26. Variable Speed Compressor Model-Benefits/comparison • Variable Speed Compressor (KW) • Measured Compressor Power (KW) • Compressor Power (KW) • Operation Conditions: • mr(kg/s) • Pout/Pin • No. of Observations

  27. Impeller Loss Model

  28. Variable Speed Compressor Model-losses profile

  29. Cooling Tower Model • Effectiveness NTU Method

  30. Cooling Tower Model • Assumptions, Specifications and Input/ Output Variables

  31. Cooling Tower Model

  32. Pump Model Mainly there are two mode of operation for these pumps: • Constant flow pump • Variable flow pump with a variable speed drive To model a variable pump power following relationship is used: Where, PMP = pump motor power at rated condition, kW C1, C2, C3 and C4 are pump performance coefficients Also, PLRi = pump part load ratio defined as follows:

  33. Pump Model • Validation Graph • + 5%Error Line

  34. Solver Description Qt,e Tw,in,e Tw,in,c Ve Vc dTsh,e

  35. Optimization • Optimization performed with two configurations: • Chiller Water Flow Optimization • Chiller Water Flow And Condenser Water Flow Optimization • Objective Function: Minimize total power consumption i.e. compressor power and pump(s) power combined.

  36. Optimization • Chiller Water Flow Optimization:

  37. Optimization • Chiller Water Flow And Condenser Water Flow Optimization: Qe = 10,000 kW Ve,opt = 0.349 m3/s Vc,opt = 0.408 m3/s Total Power (KW) Vc (m3/s) Vc (m3/s) Tw,in,e = 14 C; Tw,in,c = 25 C

  38. Optimization • Chiller Water Flow And Condenser Water Flow Optimization: Qe = 8,000 kW Ve,opt= 0.296 m3/s Vc,opt= 0.355 m3/s Total Power (KW) Vc (m3/s) Vc (m3/s) Tw,in,e = 14 C; Tw,in,c = 25 C

  39. Optimization • Chiller Water Flow And Condenser Water Flow Optimization: Qe = 6,000 kW Ve,opt = 0.249 m3/s Vc,opt = 0.332 m3/s Total Power (KW) Vc (m3/s) Vc (m3/s) Tw,in,e = 14 C; Tw,in,c = 25 C

  40. Optimization • Chiller Water Flow And Condenser Water Flow Optimization: Qe= 4,000 kW Ve,opt = 0.205 m3/s Vc,opt = 0.251 m3/s Total Power (KW) Vc (m3/s) Vc (m3/s) Tw,in,e = 14 C; Tw,in,c = 25 C

  41. Optimization • Chiller Water Flow And Condenser Water Flow Optimization: Tw,in,e = 14 C; Tw,in,c = 25 C

  42. Optimization • Chiller Water Flow And Condenser Water Flow Optimization:

  43. Conclusions • Variable Speed compressor provide savings of 30-40% • Variable speed pump for water circulation play an imperative role in reducing overall power consumption of chiller plant. • Modeling of chiller components can be performed with limited engineering information from manufactures.

  44. Future Work • More rigorous compressor loss model • Transient model for the condenser and evaporator • Cooling tower Model • Variable Speed condenser pump • Investigate the effect of pressure drop and resistance from refrigerant side