Refrigerant Line Sizing Knowledge makes the professional DESIGN AIR UNIVERSITY
What’s the big deal with line sets? DESIGN AIR UNIVERSITY
What’s the big deal with line sets? • Improperly-sized line sets can cause compressor failures. DESIGN AIR UNIVERSITY
3 Physical Factors • Size of refrigerant charge • Pressure drop • Velocity DESIGN AIR UNIVERSITY
Each manufacturer’s piping design rules must be followed. • Where to look? • In the installation instructions. • Do not just install line sets that match the fitting size on the outdoor unit or indoor coil. DESIGN AIR UNIVERSITY
Don’t just match the connection size! DESIGN AIR UNIVERSITY
Don’t just match the connection size! DESIGN AIR UNIVERSITY
Connection size on unit May be correct liquid line size DESIGN AIR UNIVERSITY
Suction line sizing • Must be large enough to minimize pressure drop which minimizes capacity loss. . . • But small enough to keep the velocity of the refrigerant high enough to pick up and carry the oil back to the compressor. DESIGN AIR UNIVERSITY
Inside the Suction Line: Refrigerant Vapor Molecule Refrigerant Oil Droplets DESIGN AIR UNIVERSITY
Velocity is important! • Approximately 1,200 feet per minute. DESIGN AIR UNIVERSITY
Why? • Picks up refrigerant oil and returns it to the compressor. • If velocity is too low, oil is not returned. DESIGN AIR UNIVERSITY
If suction line is too small . . . • The increased resistance to flow will: • Reduce the capacity and . . . • Reduce the efficiency. DESIGN AIR UNIVERSITY
Why? • Because the lower the suction pressure is when the refrigerant gases return to the compressor, the less dense they are. • The compressor will pump less volume per cycle resulting in lower capacity & efficiency. DESIGN AIR UNIVERSITY
What’s the right size suction line? • Large enough to minimize pressure drop. • Pressure loss reduces cooling capacity. DESIGN AIR UNIVERSITY
What’s the right size suction line? • Small enough to keep velocities up. • A must for oil return to the compressor. • Extra important on 2-stage equipment! DESIGN AIR UNIVERSITY
What about traps in vertical risers? • Not needed. • Undesirable, in fact. • They just add to the pressure drop. • Proper line sizing will result in proper velocity and good oil return. DESIGN AIR UNIVERSITY
Liquid Line Sizing • Must be large enough to minimize pressure drop. . . • But small enough to minimize excess refrigerant which can damage the compressor. DESIGN AIR UNIVERSITY
What’s the right size liquid line? • Large enough to minimize pressure drop. • Keep liquid refrigerant from flashing to a vapor. DESIGN AIR UNIVERSITY
If the liquid line is too small? • Loss of capacity • Damages expansion valve • Noisy evaporator • High superheat can damage compressor DESIGN AIR UNIVERSITY
What’s the right size liquid line? • Small enough to minimize refrigerant charge. • Excessive refrigerant can damage the compressor. DESIGN AIR UNIVERSITY
For example . . . • A 3/8” liquid line holds well over twice as much refrigerant as a ¼” liquid line. DESIGN AIR UNIVERSITY
What happens if . . ? • . . . the manufacturer recommends a ¼ inch liquid line for lengths up to 50 feet, but you install a 3/8 inch liquid line? • The condensing unit is factory charged for 15 feet of “properly-sized liquid line.” DESIGN AIR UNIVERSITY
You must add refrigerant! • 0.6 ounces per foot for every foot over 15 feet. • For example: 50 feet minus 15 feet = 35 feet. • 35 x 0.6 = 21 ounces of refrigerant. DESIGN AIR UNIVERSITY
At what cost? • 21 ounces of R-410A refrigerant @ $10.00 per pound = $13.13 + labor. • And the system performance is worse! DESIGN AIR UNIVERSITY
What about compressor life? • Liquid refrigerant migrates to the coldest spot in the system. • Why put extra liquid into the crankcase? • Washes out the lubrication • Noise on start-up DESIGN AIR UNIVERSITY
Repeat after me . . . • The equipment manufacturer is always right! • Bigger is not better! • Refrigerant line sizing is important! • Incorrect line sizing can cause compressor failure. DESIGN AIR UNIVERSITY