1 / 11

项目三:电力负荷及短路计算

项目三:电力负荷及短路计算. 三门峡职业技术学院 供用电技术教研室. 情景 4 :高低压断路器的选择校验. 【 能力目标 】 熟悉低压断路器过流脱扣器和热脱扣器的选择与整定; 掌握高、低压断路器的选择与校验条件。. 课堂导入: 复习高低压断路器的结构功能: 短路保护 — 过流脱扣器; 过负荷保护 — 热脱扣器; ……. 一、低压断路器的选择、校验 1 、过流脱扣器的选择

katy
Download Presentation

项目三:电力负荷及短路计算

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 项目三:电力负荷及短路计算 三门峡职业技术学院 供用电技术教研室

  2. 情景4:高低压断路器的选择校验 【能力目标】 • 熟悉低压断路器过流脱扣器和热脱扣器的选择与整定; • 掌握高、低压断路器的选择与校验条件。

  3. 课堂导入: 复习高低压断路器的结构功能: 短路保护—过流脱扣器; 过负荷保护—热脱扣器; ……

  4. 一、低压断路器的选择、校验 1、过流脱扣器的选择 过流脱扣器额定电流 IN.OR ≥ I30 2、瞬时过流脱扣器动作电流的整定应躲过尖峰电流 • IOP(O) ≥ K rel IPK 万能式QF:K rel = 1.35 塑壳式QF:K rel = 2.5 • 思考?? 如果是短延时、长延时过流脱扣器呢?

  5. 3、过流脱扣器与被保护线路的配合要求 • IOP ≤ K OL×I aL KOL— 导体允许短时过负荷系数(取4.5) I aL— 导线允许载流量(附表17、18) 4、热脱扣器的选择与整定 (1)选择 IN.HR ≥ I30 (2)整定 IOP.HR ≥ K rel I30 (K rel取1.1)

  6. 5、低压QF规格的选择与校验 (1)选择条件 • UN.QF ≥ UN • IN.QF ≥ IN.OR • IN.QF ≥ IN.HR

  7. (2)校验 A、断流能力校验: • 万能式QF: IOC ≥ IK(3) • 塑壳式QF: IOC ≥ Ish(3) B、灵敏度校验: • SP = I K .min/IN.FE ≥K(K取1.3)

  8. 6、前后级低压QF的选择性配合 (1)时间(规格型号) • 前一级采用带短延时的过流脱扣器,后一级采用瞬时脱扣器。 (2)动作电流 • IOP前≥ 1.2 IOP后

  9. 二、高压QF的选择与校验 1、额定电压:UN.QF ≥ UN 2、额定电流:IN.QF ≥ I30 3、开断电流:IOC ≥ IK(3) 4、断流容量:SOC ≥ SK(3)

  10. 5、极限通过电流(动稳定校验) • I max ≥ ish(3) 6、短路时的发热温度(热稳定校验) It2×t ≥ I∞2×t ima • 例题:略

  11. 谢谢!