SCAQMD REQUIREMENTS FOR LARGE WATER HEATERS AND SMALL BOILERS. The Gas Company’s Energy Resource Center March 22, 2006. Rule 1146.2 – Emissions of Oxides of Nitrogen From Large Water Heaters and Small Boilers. The Rule Applies to: 75,000 – 2,000,000 Btu/hr Type 1 75,000 – 400,000 Btu/hr

Download Presentation

SCAQMD REQUIREMENTS FOR LARGE WATER HEATERS AND SMALL BOILERS

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. SCAQMD REQUIREMENTS FOR LARGE WATER HEATERS AND SMALL BOILERS The Gas Company’s Energy Resource Center March 22, 2006

  2. Rule 1146.2 – Emissions of Oxides of Nitrogen From Large Water Heaters and Small Boilers • The Rule Applies to: 75,000 – 2,000,000 Btu/hr • Type 1 75,000 – 400,000 Btu/hr • Type 2 >400,000 – 2,000,000 Btu/hr

  3. Requirements for Manufacturers • January 1, 2000 – No manufacture or sales of new Type 2 units (400,000 – 2,000,000 Btu/hr unless: • Certified by AQMD to meet: NOx – 30 ppm or less at 3% O2, dry CO – 400 ppm or less at 3% O2, dry

  4. Requirements for Manufacturers – con’t. • January 1, 2002 – No manufacture of new Type 1 units (75,000 – 400,000 Btu) unless: • Certified by AQMD to meet: NOx = 55 ppm or less

  5. Requirements for Existing Equipment • July 1, 2002 - Units manufactured before January 1, 1992 (>1MM- 2MM Btu/hr) • Modified (retrofitted) or demonstrate to meet: • NOx – 30 ppm or less at 3% O2, dry • CO = 400 ppm or less at 3% O2, dry

  6. Requirements for Existing Equipment – con’t • January 1, 2005 - Units manufactured after January 1, 1992 (>1MM – 2MM Btu/hr) • Modified (retrofitted) or demonstrate to meet: • NOx – 30 ppm or less at 3% O2, dry • CO = 400 ppm or less at 3% O2, dry

  7. Requirements for Existing Equipment – con’t • January 1, 2006 - Units >400,000 - 1,000,000 Btu/hr • Modified (retrofitted) or demonstrate to meet: • NOx – 30 ppm or less at 3% O2, dry • CO = 400 ppm or less at 3% O2, dry • Units 400,000 Btu/hr or less can operate until replaced by a compliant unit

  8. Certification - Manufacturers • Use independent testing lab using District protocol • Mail test report to: • Moustafa Elsherif 21865 Copley Drive Diamond Bar, CA 91765-4182 • Upon approval of the source test, a certification letter will be issued to the manufacturer • Manufacturer required to display certification on the boiler • All manufacturers and their certified models will be posted on AQMD website www.aqmd.gov/rules/doc/r1146/r1146table.html

  9. Retrofitting Existing Boilers • Use independent testing lab using District protocol • Mail test report to: • Moustafa Elsherif 21865 Copley Drive Diamond Bar, CA 91765-4182 • Upon approval of the source test, a certification letter will be issued to the owner

  10. Retrofitting Existing Boilers – con’t • Other requirement for a pre-certified burner • The owner can use Method 100.1 to determine NOx and CO emissions • Using pre-certified burner to same model boiler • The owner can use analyzer to determine the NOx and CO emissions

  11. Derating • Applicant must obtain a derating certificate from the manufacturer or contractor to show how they achieved the derating and the new derating rate

  12. Exemptions • From Rule 1146.2 • Heaters/Boilers used in recreational vehicles • Heaters/Boilers used in mobile homes • Heaters/Boilers at RECLAIM facilities • Tankless water heaters • From the Requirements • Any residential unit (4 units or less) • Heaters/Boilers using 9,000 therms per calendar year (The Gas Company record or the use of a non-resettable hourly meter)

  13. Rule 222 – Filing Requirements For Specific Emission Sources Not Requiring A Written Permit Pursuant to Regulation II • Water Heaters/Boilers 1MM to 2MM Btu/hr • The Rule requires a one time filing of Form 222-B for each new certified boiler and a fee of $123.00 per boiler • Retrofitted boiler are required to submit a annual renewal fee

  14. MOUSTAFA ELSHERIFProgram Supervisor909-396-3113melsherif@aqmd.gov