330 likes | 852 Views
Modular Inverter. Modular Inverter Series UNV. [HF Technology 1st Generation]. UNV-F1.2 - UNV-F1.8 – UNV-F2.5 – UNV-F3.3 – UNV-F5.0. Available input voltages of:. 48V DC. 1200VA(960W) 1800VA(1440W) 2500VA(2000W) 3300VA(2640W) 5000VA(4000W).
E N D
ModularInverter Series UNV [HF Technology 1st Generation] UNV-F1.2 - UNV-F1.8 – UNV-F2.5 – UNV-F3.3 – UNV-F5.0 Available input voltages of: 48V DC 1200VA(960W) 1800VA(1440W) 2500VA(2000W) 3300VA(2640W) 5000VA(4000W) 60V DC 110V DC Available output voltages of: 230V AC / 50Hz | --------------------------------------------------------- 19“ x 3U ------------------------------------------------------------ |
Modular Inverter Series UNV UNV-F Technical information Input: Output:230V, 50 or 60Hz (programmable), single phase It is possible to build three phase system, each phase with numbers inverter in parallel. Max. number of inverter working in parallel: 16 pieces
Modular Inverter Series UNV UNV-F Special features >> Electrical isolation between input and output >> Input over/under voltage shutdown >> Hot-plug-in able >> Ready for paralleling (no fixed master) >>Current sharing based on decrease line of max. 1% for the output voltage >> Load balance max +/- 5% INom >> n+x redundancy >>Ability to build three phase systems with a number of inverters per phase >> Output overload and short circuit proof >> Temperature controlled fan cooling (font-to-rear airflow) >>Digital display for output voltage / current and adjustment of internal default settings >> Crest factor < 3 >> Can bus interface for communication with static bypass switch and/or monitoring unit >>Working temperature: -20°C up to +45°C >>Power factor range: 0,5 ind. - 1 – 0,5 cap. >>Ability for stand-alone operation >> Designed to operate together with static bypass switches >>overload capability 130% for 30sec
Modular Inverter Series UNV UNV-F Signalling Relay signalling: Dry contact for common alarm. Contact rating: 8A@250VAC, 8A@30VDC High input voltage Output voltage O.K. Operation Display for output voltage (top line, 3 signs) and output current (second line, 3 signs) flashing: ventilator fault Constant : high internal temperature Common alarm Overload Low input voltage
ModularInverter Series UNV UNV-F Mounting (mounting kit): View into a system (left side) Plugs for inverter UNV-F Slide rails
ModularInverter Series UNV UNV-F Needed / available accessories - mounting kit >> article number: 880-MEC-MKT.01 (except UNV48-5,0F) >> article number: 880-MEC-MKT.02 (only UNV48-5,0F) - socket (standard: part of delivery scope) >> article number: 880-MEC-MKT.21 (except UNV48-5,0F) >> article number: 880-MEC-MKT.22 (only UNV48-5,0F)
ModularInverter Series INV [HF Technology 2nd Generation] Available input voltages of: INV211 - INV216 - INV245x (x=still in development) 24V DC 48V DC 60V DC 1100W(1375VA) 1600W(2000VA) 4500W(5600VA) (24V only) 110V DC 220V DC Available output voltages of: 230V AC / 50Hz |-------------------- 1/4-19“ x 2U ------------------- | ---------------------- 19“ x 2U ------------------------- |
Modular Inverter Series INV INV 222 (INV215@24VDC) Technical information Input: Output:230V, 50Hz, single phase Max. number of inverter working in parallel: 8 pieces
Modular Inverter Series INV INV INV 222 (INV215@24VDC) Technical information Signalling: Operation: input voltage within nominal value Output voltage within nominal value Common alarm Remote signalling: Dry contact for common alarm. Contact rating 60V/0,1A
Modular Inverter Series INV INV 222 (INV215@24VDC) Special features >> Electrical isolation between input and output >> Input over/under voltage shutdown >> Hot-plug-in able >> Ready for paralleling (no fixed master) >>Current sharing based on decrease line of max. 1% for the output voltage >> Load balance max +/- 10% INom >> n+x redundancy >> Output overload and short circuit proof >> Temperature controlled fan cooling (font-to-rear airflow) >> Crest factor < 3 >> Can bus interface for communication with static bypass switch and/or monitoring unit >>Working temperature: -20°C up to +55°C >>Power factor range: 0,5 ind. - 1 – 0,5 cap. >> Designed to operate together with static bypass switches >> Overload capability 130% for 5sec; 110% for 1min
ModularInverter Series INV INV INV 222 (INV215@24VDC) Mounting: Front view of 19” rack Mounting angles Static bypass switch STS207 Three slots for inverter INV222
ModularInverter Series INV216 INV INV 222 Needed / available accessories >> 19” rack, 2 HU, including backplane for 3x inverter + 1x STS >> article number: 502-222-315.LV (for DC input 24-60V) >> article number: 502-222-315.HV (for DC input 108-216V) >> 19” rack, 2HU, with backplane for 4x inverter (without STS) >> article number: 502-222-405.LV (for nominal DC voltages 24-60V) >> article number: 502-222-405.HV (for nominal DC voltages 108-216V) >> Cover plates to cover not used inverter slot, 2HU, RAL7035 >> article number: 881-MEC-BPL.02.21.B
ModularInverter Series PWS PWS-1.0 - PWS-2.5 - PWS-5.0 Available input voltages of: 24V DC 1000VA(800W) 1800VA(1440W) 2500VA(2000W) 3300VA(2640W) 5000VA(4000W) 110V DC 220V DC Available output voltages of: 230V AC / 50Hz Other voltages / frequencies on request Available mechanical design: 19” 4/5U or wall cabinet
Modular Inverter Series PWS PWS Technical information Input: Output:230V, 50 single phase It is possible to get special output voltages / frequencies Max. number of inverter working in parallel: 12 pieces
Modular Inverter Series PWS PWS Special features >> Electrical isolation between input and output >> Input over/under voltage shutdown >>Available as 19” rack or as wall cabinet >> Ready for paralleling (no fixed master) >>Current sharing based on decrease line of max. 1% for the output voltage >> Load balance max +/- 10% INom >> n+x redundancy >> Crest factor < 2,5 >> Output overload and short circuit proof >> Temperature controlled fan cooling (font-to-rear airflow) >>Overload capability 160% for 1min; 130% for 10min >> Special output voltages / frequencies on request >>Working temperature: -20°C up to +45°C >>Power factor range: 0 ind. - 1 – 0 cap. >>Analogue measurement instruments for output voltage / current >>Ability for stand-alone operation >> Designed to operate together with static bypass switches
Modular Inverter Series PWS PWS Signalling Relay signalling: Dry contact for common alarm. Contact rating: 5A@250VAC, 5A@30VDC High input voltage Output voltage O.K. Operation High internal temperature Common alarm Failure Low input voltage
ModularInverter Series PWS PWS Needed / available accessories - mounting kit >> article number: 880-MEC-MKT.03
Modular Static Switches Series STS STS207 - STS114 - STS230 - STS350 still in development still in development still in development 7kVA@230V AC 14.5kVA@230V AC 30kVA@230V AC 50kVA(1/3phase) |---- 1/4-19“ x 2U ---- | ------------------ 19“ x 1U ------------------ | ---------------------------------------------- 19“ x 3U -------------------------------------------- |
Modular Static Switches Series STS STS Technical information Input: - Special versions for nominal input voltage of 24-60VDC and 108-216VDC. - 1x 230VAC bypass mains - 1x 230VAC inverter output Output: - 1x 230VAC, in phase with bypass input
Modular Static Switches Series STS STS Signalling Remote signalling: Optocoupler for common alarm, Relay on backplane: Max. contact rating: 30W / 50VA; 60VDC / 125VAC; 1ADC / 1AAC Load on Inverter Bypass input Load on Mains Inverter input Operation Display of 4 lines Synchron bus in phase with bypass mains input Common alarm Ethernet Interface CAN-bus Interface
Modular Static Switches Series STS STS Special features >> Hot-plug-in able >>Display for all main operating parameters, settings and measuring values >> Ethernet interface for remote connection via SNMP protocol or WEB-Browser >> Minimized synchronisation time (because of digital PLL) >> It is possible to use diesel gensets as bypass mains >> Transfer time < 4ms >> Monitoring of both incoming sources according to voltage level, frequency and synchronisation >> Temperature controlled fan cooling (font-to-rear airflow) >>Free programmable operation mode (inverter priority or bypass priority) >> Overload capability 1000% for 10ms >> CAN bus interface
Modular Static Switches Series STS STS Needed / available accessories >> 19” rack, 2 HU, including backplane for 3x inverter + 1x STS >> article number: 502-216-315.LV (for DC input 24-60V) >> article number: 502-216-315.HV (for DC input 110-220V) >> Manual bypass switches (recommended by ELTEK VALERE INDUSTRIAL, please have a look on separate description) >> article number: 881-880-HBS-7.0 (max. 7,0kVA) >> article number: 881-880-HBS-14.5 (max. 14,5kVA) >> article number: 881-880-HBS-30.0 (max. 50kVA)
Modular Static Switches Series STS [1st Generation] UNB-5.0 - UNB-12.5 – UNB-23.0 – UNB-30.0 – UNB-40.0 Available DC input voltages of: 24 DC 5000VA 12500VA 23000VA 30000VA 40000VA 48/60V DC 110V DC 220V DC | --------------------------------------------------------- 19“ x 3U ------------------------------------------------------------ |
Static Switches Series UNB UNB Technical information Input: DC input: Special version for 24VDC, 48/60VDC, 110VDC or 220VDC AC bypass input: 230VAC, 50/60 Hz, single phase also available 3x 230/400VAC, 50Hz, three phase with loadable neutral AC inverter input: 230VAC, 50/60Hz, single phase also available 3x 230/400VAC, 50Hz, three phase with loadable neutral Output:230V, 50/60Hz, single phase, in phase with bypass input also available 3x 230/400VAC, 50/60 Hz, three phase with loadable neutral, in phase with bypass input Free programmable operation mode (inverter to load / bypass to load as standard)
Static Switches Series UNB UNB Signalling Relay signalling: Dry contact for common alarm. Contact rating: 8A@230VAC, 8A@24VDC Second source (substitute source) Priority source Operation Display of 4 lines Common alarm Synchron bus in phase with bypass mains input Load on Mains Load on Inverter
Static Switches Series UNB UNB Special features >> Hot-plug-in able >>Display for all main operating parameters, settings and measuring values >> Optional three phase versions >> Designed for AC systems consisting of UNV- or PWS inverters >> Transfer time < 4ms >> Monitoring of both incoming sources according to voltage level, frequency and synchronisation >> Temperature controlled fan cooling (font-to-rear airflow) >>Free programmable operation mode (inverter priority or bypass priority) >> Overload capability 1000% for 10ms >> CAN bus interface
Static Switches Series UNB UNB Needed / available accessories >> mounting kit >> article number: 880-MEC-MKT.01 (5.0 to 12.5kVA) >> article number: 880-MEC-MKT.03 (> 23.0kVA) >> Manual bypass switches (recommended by ELTEK VALERE INDUSTRIAL, please have a look on separate description) >> article number: 881-880-HBS-7.0 (max. 7,0kVA) >> article number: 881-880-HBS-14.5 (max. 14,5kVA) >> article number: 881-880-HBS-30.0 (max. 50kVA) Needed / available accessories >> socket (standard: part of delivery scope) >> article number: 880-MEC-MKT.21
Other applicable products? • Inverter with built-in static switch • UNV-UE series • Input: 48/60VDC • Output: 230V/50Hz/1000VA out • Mechanical design: 19” x 3U
Other applicable products? • Monoblock inverter • MBI series • Input: 110VDC or 220VDC • Output:115VAC or 230VAC • 30-50kAV • (up to 100kVA at 220VDC) • Mechanical design: • stand cabinet in RAL7035
Other applicable products? • Monoblock UPS systems • MBS series • Input: 3x 230/400VAC • Output:1ph. 230VAC or 115VAC • 50 or 60 Hz • 60 up to 100kVA • Mechanical design: • stand cabinet in RAL7035