230 likes | 405 Views
Electrical Machines. LSEGG216A 9080V. Transformer Operation. Week 4 . Transformer Operation. CIVIL. V+. Voltage. Current. Magnetic Flux. Transformer Operation. Applied Voltage. Induced Voltage. V’ 2. V’ 1. V 1. Induced Voltage in Secondary. I M. Resultant Current.
E N D
Electrical Machines LSEGG216A 9080V
Transformer Operation Week 4
Transformer Operation CIVIL V+ Voltage Current Magnetic Flux
Transformer Operation Applied Voltage Induced Voltage V’2 V’1 V1 Induced Voltage in Secondary IM Resultant Current
Induced Voltage Φmax =Maximum instantaneous flux F = Frequency N = Number of turns Bmax = Maximum permissible flux density in Wb A = CSA of core in m2
Transformer Operation Ie V1 Ie= Iron loss current Io = No load current Io IM
Transformer Operation I’2 V’2 V’1 V1 I’1 Io I1
Transformer Operation V’2 V’1 V1 I’2 I’1 Io I1
Transformation Ratio Magnetic flux is common coils Therefore the voltage can be varied by changing the number of turns
Transformation Ratio V1= N1 = k = Transformation Ratio V2= N2
Transformation Ratio V1x I1 = V2 x I2 N1 I2 = N2 I1
Transformation Ratio V1x I1 kVA VA Power In Power Out V2 x I2
Transformation Ratio V1x I1 K = 2 200V 100V V2 x I2 400 200
Voltage Regulation Coils have both • Resistance • Inductance I E V Voltage Drop Due to R Voltage Drop Due to XL
Voltage Regulation V less than E I V E Lagging PF of 45
Voltage Regulation V More than than E I E V Leading PF of 45
Voltage Regulation 100 x VNo Load – V Full Load R% = VFull Load If PF = Unity 100 x I x (R x cos + XL x sin) R% = VFull Load
Transformer Basic Tests Open Circuit Test Short Circuit Test Oil Tests Electrical Insulation Polarity Continuity
Open Circuit Test Used to determine Iron Losses Supply = Rated Voltage
Open Circuit Test Ie V1 Wattmeter reading Supply Voltage Ammeter reading Io IM
Short Circuit Test Used to determine Copper Losses Supply Adjusted = Rated Secondary Current