1 / 37

ECE 476 POWER SYSTEM ANALYSIS

ECE 476 POWER SYSTEM ANALYSIS. Lecture 24 Transient Stability Professor Tom Overbye Department of Electrical and Computer Engineering. Announcements. Be reading Chapter 13.

lavernes
Download Presentation

ECE 476 POWER SYSTEM ANALYSIS

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ECE 476POWER SYSTEM ANALYSIS Lecture 24 Transient Stability Professor Tom Overbye Department of Electrical andComputer Engineering

  2. Announcements • Be reading Chapter 13. • HW 11 is not turned in but should be done before final. HW 11 is 13.1, 13.7, 13.8, 13.18, and the special problem (see website for complete assignment) • Final is Tuesday Dec 16 from 7 to 10pm in EL 165 (note this is NOT what the web says). Final is comprehensive. One new note sheet, and your two old note sheets are allowed

  3. Generator Electrical Model • The simplest generator model, known as the classical model, treats the generator as a voltage source behind the direct-axis transient reactance; the voltage magnitude is fixed, but its angle changes according to the mechanical dynamics

  4. Generator Mechanical Model Generator Mechanical Block Diagram

  5. Generator Mechanical Model, cont’d

  6. Generator Mechanical Model, cont’d

  7. Generator Mechanical Model, cont’d

  8. Generator Swing Equation

  9. Single Machine Infinite Bus (SMIB) • To understand the transient stability problem we’ll first consider the case of a single machine (generator) connected to a power system bus with a fixed voltage magnitude and angle (known as an infinite bus) through a transmission line with impedance jXL

  10. SMIB, cont’d

  11. SMIB Equilibrium Points

  12. Transient Stability Analysis • For transient stability analysis we need to consider three systems • Prefault - before the fault occurs the system is assumed to be at an equilibrium point • Faulted - the fault changes the system equations, moving the system away from its equilibrium point • Postfault - after fault is cleared the system hopefully returns to a new operating point

  13. Transient Stability Solution Methods • There are two methods for solving the transient stability problem • Numerical integration • this is by far the most common technique, particularly for large systems; during the fault and after the fault the power system differential equations are solved using numerical methods • Direct or energy methods; for a two bus system this method is known as the equal area criteria • mostly used to provide an intuitive insight into the transient stability problem

  14. SMIB Example • Assume a generator is supplying power to an infinite bus through two parallel transmission lines. Then a balanced three phase fault occurs at the terminal of one of the lines. The fault is cleared by the opening of this line’s circuit breakers.

  15. SMIB Example, cont’d Simplified prefault system

  16. SMIB Example, Faulted System During the fault the system changes The equivalent system during the fault is then During this fault no power can be transferred from the generator to the system

  17. SMIB Example, Post Fault System After the fault the system again changes The equivalent system after the fault is then

  18. SMIB Example, Dynamics

  19. Transient Stability Solution Methods • There are two methods for solving the transient stability problem • Numerical integration • this is by far the most common technique, particularly for large systems; during the fault and after the fault the power system differential equations are solved using numerical methods • Direct or energy methods; for a two bus system this method is known as the equal area criteria • mostly used to provide an intuitive insight into the transient stability problem

  20. Transient Stability Analysis • For transient stability analysis we need to consider three systems • Prefault - before the fault occurs the system is assumed to be at an equilibrium point • Faulted - the fault changes the system equations, moving the system away from its equilibrium point • Postfault - after fault is cleared the system hopefully returns to a new operating point

  21. Transient Stability Solution Methods • There are two methods for solving the transient stability problem • Numerical integration • this is by far the most common technique, particularly for large systems; during the fault and after the fault the power system differential equations are solved using numerical methods • Direct or energy methods; for a two bus system this method is known as the equal area criteria • mostly used to provide an intuitive insight into the transient stability problem

  22. Numerical Integration of DEs

  23. Examples

  24. Euler’s Method

  25. Euler’s Method Algorithm

  26. Euler’s Method Example 1

  27. Euler’s Method Example 1, cont’d

  28. Euler’s Method Example 2

  29. Euler's Method Example 2, cont'd

  30. Euler's Method Example 2, cont'd

  31. Euler's Method Example 2, cont'd Below is a comparison of the solution values for x1(t) at time t = 10 seconds

  32. Transient Stability Example • A 60 Hz generator is supplying 550 MW to an infinite bus (with 1.0 per unit voltage) through two parallel transmission lines. Determine initial angle change for a fault midway down one of the lines.H = 20 seconds, D = 0.1. Use Dt=0.01 second. Ea

  33. Transient Stability Example, cont'd

  34. Transient Stability Example, cont'd

  35. Transient Stability Example, cont'd

  36. Transient Stability Example, cont'd

  37. Equal Area Criteria • The goal of the equal area criteria is to try to determine whether a system is stable or not without having to completely integrate the system response. System will be stable after the fault if the DecelArea is greater than the Accel. Area

More Related