PHOS Cooling status (1-6 Oct) Brief

PHOS Cooling status (1-6 Oct) Brief. 28 Sep start cool down to 5°C (by cooling liquid) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical control valve) controller alarm raised due to battery fail (inside controller)

len
Download Presentation

PHOS Cooling status (1-6 Oct) Brief

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. PHOS Cooling status (1-6 Oct)Brief 28 Sep start cool down to 5°C (by cooling liquid) 1 Oct at 5 Am cooling plant failure happened: ECV (electrical control valve) controller alarm raised due to battery fail (inside controller) Problem temporary fixed after 8 hours (switch ECV in manual control mode: work in non-optimal mode). Normal operation mode started after 3 days with battery alarm OFF (after some tests with controller). PHOS cooling now work in normal operation mode. Cooling liquid ~5°C, PWO ~7°C, FEE in 16÷20°C range, humidity in 10÷20% range. Liquid leak ~1 L per 5 days in PHOS-4.

  2. PHOS Cooling status (1-6 Oct) PHOS temperatures FEE2 FEE3 FEE4 PWO3 PWO2 PWO4 ECV failure C6F14 Normal operation Temporary operation (manual mode)

  3. PHOS Cooling status (1-6 Oct)PHOS-2 humidity, 7÷15% % PWO2 FEE2

  4. PHOS Cooling status (1-6 Oct)PHOS-3 humidity, PWO=20%, FEE=15% % PWO3 FEE3

  5. PHOS Cooling status (1-6 Oct)PHOS-4 humidity, PWO=12÷20%, FEE=15% This sensor looks strange, maybe damage? PWO3 FEE3

  6. PHOS Cooling status (1-6 Oct)Liquid level going down, now 59 L We have leak ~1 Liters per 5-6 days (inside PHOS-4, it seems) Liquid filling

  7. PHOS Cooling status (1-6 Oct)Temperature of pump’s cover Cooling plant have 2 pumps. 1st pump looks more “cold” (why?). During 1 Oct incident pump temperature raised up to 45°C. Pumps works in “round-robin” mode to have equal resource (working time) Pump1 Pump2

  8. PHOS Cooling status (1-6 Oct)Temperature of compressor’s cover In normal operation mode cover have temp-re in 35÷58°C range. During 1 Oct incident compressor temp-re up to 70÷80°C. In manual mode temp-re range more wide (20÷60 °C). Compressors works in “round-robin” mode to have equal resource (working time) Interlock on compressor’s cover temperature should be added to control software Incident 1 Oct Compressor-1 Compressor-3 Compressor-2 Compressor-4 Normal mode Manual mode (not optimal) Pump1 Pump2

  9. PHOS Cooling status (1-6 Oct) What is ECV controller

  10. PHOS Cooling status (1-6 Oct) ECV controller failure Alarm: Battery failure

  11. PHOS Cooling status (1-6 Oct) ECV controller problem fixed now Battery Alarm switched OFF as tests with controller show, controller can work without battery if battery alarm is OFF

  12. PHOS Cooling status (1-6 Oct)To Do • ECV controller alarm signal should be connected to cooling control system • Some additional program (software) blocking (interlocks) should be added • Some investigations should be done to find optimal and fault-safe parameters of cooling control software • Documentation should be updated after this changes • PHOS-4: to be or not to be… After this will be done, we are ready to cool down to -25 (?) It will takes about 2-3 weeks (?)