230 likes | 428 Views
Zio ™ TR70 LCD Wall Module. Customer Training. Zio ™ TR70 LCD Wall Module Feature Brief. Used with the enhanced Spyder ™ Controller with Sylk ™ Two-wire polarity-insensitive bus interface Very large backlit display Pull down and view almost any point in the Spyder controller
E N D
Zio™ TR70LCD Wall Module Customer Training
Zio™ TR70LCD Wall Module Feature Brief • Used with the enhanced Spyder ™ Controller with Sylk™ • Two-wire polarity-insensitive bus interface • Very large backlit display • Pull down and view almost any point in the Spyder controller • Customizable home screens • Balance systems from the wall module • Use Spyder tool to customize your configurations and home screen • Multiple override options • Easy to use, borrows from Honeywell homes thermostat design • Only two models do it all (one offers humidity)
Zio™ TR70 Customizable Home Screens • Customizable Home screen: • Home screen choices are created in the S-Bus Wall Module function block in the newest Spyder tool and downloaded to the TR70. Multiple home screens can be downloaded with one set as default. • From the Home screen, the Tenant can change the setpoint, fan speed and/or initiate override, if configured. They can also view or view/change other parameters using the View More key if desired. View More parameters are configurable. • Some sample home screens shown below: Mix and match options for the home screen as desired
Zio™ TR70 Contractor Mode • A contractor mode can be accessed. • In the contractor mode, you can choose the home screen, select parameter access to tenant (Yes or No as desired), and view/change parameters. • Parameters may include virtually any point in the controller. Scheduling is not accessible. • Some sample parameter screens below. Use the tool to set up how you want the parameter displayed
Wiring and Address Dial of Zio Sylk™Bus Address Dial Leave setting at 1 (Currently the bus can accept only 1 device at a time) Four Terminals 1 and 2 for network jack (optional) 3 and 4 for Sylk Bus (to controller S-bus terminals)
Configuration of Zio • All configuration of the Zio Wall Modules is done through the S-bus Wall Module Configuration tool • This tool is embedded in the Sylk Enhanced Spyder Tool, Version 2.0.0 as of the date of product release in Oct 2008. • Download the latest version at the Honeywell Buildings Forum. Download here