An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. LRFD – Floor beam Unbraced top flange

  2. Lateral Torsion Buckling • We have to check if there is plastic failure (yielding) or lateral-torsion buckling. • This depends on the length between the lateral braces, related to the limiting lengths. • Lp is the limiting length for plastic failure • Lr is the limit length for torsional buckling. • If Lb < Lp it is plastic failure • If Lp < Lb < Lr we have a different failure criteria • If Lb > Lr we use the lateral buckling stress criteria

  3. Plastic Failure • If Lb < Lp • Mn = Mp = syZx • Zx is the plastic section modulus about the x axis

  4. Lp < Lb < Lr

  5. Lb > Lr • Mn = scrSx ≤ Mp

  6. The following definitions apply

  7. c • For a doubly symmetric I-shape • c=1 • For a channel, • Where h0 = distance between flange centroids

  8. Conservative simplifications

  9. A beam of A992 steel with a span of 20 feet supports a stub pipe column with a factored load combination of 55 kips A992 Steel: structural steel, used in US for I-beams. Density = 7.85 g/cm3. Yield strength = 50 ksi.

  10. No flooring – no lateral bracing on top flange Find max moment. Assume beam weighs 50 lbs/ft From distributed load, Mmax = w L2/8 From point load, Mmax = P L / 4 Mmax = 55,000 * (20/4) + 50 * (20^2)/8 = 277.5 kip-ft

  11. Use trial method • Find a beam that has a fMp of at least 277.5 kip-ft • Need to check if it will fail in plastic mode (Mp) or from flange rotation (Mr) • Tables will show limiting unbraced lengths. • Lp is full plastic capacity • Lr is inelastic torsional buckling. • If our length is less than Lp, use Mp. If greater than Lr, use Mr

  12. Selected W Shape Properties – Grade 50

  13. W18 x 40 looks promising 294 > 277.5 But, Lp = 4.49. Our span is 20 feet. And, Lr = 12.0 again, less than 20’ fMr = 205, which is too small. W21x50 has Lr = 12.5, and fMr = 285. That could work!

  14. Nominal flexural design stress • Mn = scrSx • The buckling stress, scr , is given as

  15. Terms in the equation • rts = effective radius of gyration • h0 = distance between flange centroids • J = torsional constant (torsional moment of inertia) • Cw = warping constant • c = 1.0 for doubly symmetric I-shape

  16. Effective radius of gyration

  17. So the critical stress is

  18. Then the nominal moment is • Mn = scrSx • = 18.77 • 94.5 = 1,774 kip-in = 147.9 kip-ft • We need 277.5!! • If we had the AISC design manual, they show unbraced moment capabilities of beams. • We would have selected W21x62, which turns out to handle 315.2 kip-ft unbraced.