1 / 8

EPICS support for ControlLogix via EtherNet/IP

EPICS support for ControlLogix via EtherNet/IP. Kay-Uwe Kasemir, LANL May 2001. PS. CNet. PLC. Allen-Bradley ControlLogix. SNS: HPRF, Vac., RCCS, Facility, … Up to 7MB, multithreaded, … Symbolic ‘tag’ names, no ‘I10:12’ Accepts DeviceNet, ControlNet, EtherNet/IP, … like any I/O module.

lionel
Download Presentation

EPICS support for ControlLogix via EtherNet/IP

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. EPICS support for ControlLogix via EtherNet/IP Kay-Uwe Kasemir, LANL May 2001

  2. PS CNet PLC Allen-Bradley ControlLogix • SNS: HPRF, Vac., RCCS, Facility, … • Up to 7MB, multithreaded, … • Symbolic ‘tag’ names, no ‘I10:12’ • Accepts DeviceNet, ControlNet, EtherNet/IP, … like any I/O module

  3. IP = Industrial Protocol • Evolved from “ControlNet over EtherNet” SIG • Encapsulates CIP in TCP & UDP • (Ctrl. & Info. Protocol, shared by DeviceNet and ControlNet) • Specs. used to be part of ControlNet,now available as separate “EtherNet/IP”: • Open DeviceNet Vendor Assoc.,http://www.odva.org

  4. EtherNet/IP Spec. Details • Open portion of CIP (object & service codes): • How to route messages • How to read serial number and vendor code • Vendor specific: • Get data of real interest, e.g. PLC values • This driver:CIP Read/WriteData as used byAllen Bradley ControlLogix PLCs • Round-trip request/response mechanism • Subscription (ForwardOpen) with triggered updates via UDP not implemented/documented by AllenBradley

  5. EPICS Driver/Device • No special hardware, neither for setup nor runtime • IOCs (pc486, PPC), command-line (Win32, Unix) • Can read & write any tag on PLC • Records: ai, ao, bi, bo, mbbi, mbbo, mbbiDirect, mbboDirect • DTYP=“EtherIP”, INP=“@plc1 PS1RB2” • also: INP=“@plc2 arraytag[21]”, “@plc2 struct.elem” • REAL, INT, DINT, BOOL,scalars, struct. elements, arrays • no need to “publish” tag in PLC’s LadderLogicor program ControlNet connection to allocate bandwidth • INP/OUT can be changed at runtime to use different tag on different PLC! • Handles disconnects/reconnects (e.g. PLC reboot)

  6. Driver/Device Details • One communication thread per PLC • Combines requests to minimize transfers • (up to ~500 byte PLC buffer limit) • Arrays are transferred as a whole (default) • Output records: • Monitors PLC, updates rec. on change • Supports SCAN=I/O Event (also for e.g. 30Hz scans) • Provides statistics:min/max/last scan times, #errors, ... • Performance: (default “System Overhead Time Slice”) • Single REAL tag: 11ms (7ms with 50% SOTS) • BOOL[352] + 3xREAL[30]: 15ms + 25ms (combined requests)

  7. 352 BI @ 10Hz, 3 x REAL[40] @ 2 Hz Transfer Time Histogram

  8. Conclusion • Setup: • No additional hardware (neither for PC, IOC, nor communication setup) • Use: • No special LadderLogic required, though arrays might be preferred (performance) • Good IOC support (I/O Event, runtime change) • Performance: • 11ms/transfer, susceptible to network delays • good enough for most applications?

More Related