E N D
1. SITOP selectElectronic Diagnosis Module Fault diagnosis – rapid and reliable
2. Blow the whistle on plant downtimes Keep the overview of your 24V load feeders.
Show the red card to downtimes caused by faults
3. The situation today
4. Reasons for selective triggering failure when fault occurs
Long load lines
Creeping short circuits
Line circuit breakers dimensioned too large
? Consequences
Plant standstill due to drop in 24 V power
Trouble-shooting much more difficult
Long standstill times
Reason for undesired triggering during operation
Excessive current peaks during startup
? Consequence
Malfunction, machine/plant switches off The situation today
5. The solution Fault paths are powered down reliably even under very poor operational conditions.
Retension of the 24 V power for all other paths
Plant down time is reduced or even avoided.
Fast trouble-shooting and fault localization
Loads with high startup current peaks power up with current limitation.
Malfunction-free device startup
6. The solution Selectivity and fast error diagnosis of 24 V feeder circuits
Four feeder circuits (outputs) per module
Each output can be set between 2 and 10 A using potentiometer.
Multi-color LED for each output for rapid fault localization
Potential-free common signal contact for fault diagnosis
Several modules can be connected to a single power supply.
Simple and rapid installation using standard mounting rail
Additional line protection and gradual equipment commissioning with exchangeable FK2 blade-type fuse
7. Circuit diagram
8. Switching characteristic Irated can be adjusted from 2 to 10 A per output circuit. Characteristics per current
requirements depend on the output circuit.
From 0 A to the set value ( I/ Irated=100%) ? without switching off
From set value up to 130% ? switch off after approx. 5 sec
Above 130% of set value ? current limiting to 130% for 50 to 100 msec, next switch off
Over the set value with simultaneous collapse of the supply voltage below 20V ? immediate switch off
9. Device features
10. Ordering data, technical specifications