Reduced Safety/Reliability: Arc Flash Hazard Example

Reduced Safety/Reliability: Arc Flash Hazard Example. Scenario 1: 200A RK-1 Branch Fuse 400A RK-1 Main Fuse Short circuit protection with low let-through energy Partial selective coordination, through overload range Scenario 2: Changed to 400A RK-5 Main Fuse

lysander
Download Presentation

Reduced Safety/Reliability: Arc Flash Hazard Example

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Reduced Safety/Reliability: Arc Flash Hazard Example Scenario 1: 200A RK-1 Branch Fuse 400A RK-1 Main Fuse • Short circuit protection with low let-through energy • Partial selective coordination, through overload range Scenario 2: Changed to 400A RK-5 Main Fuse • Short circuit protection, but higher let-through energy • Total selective coordination through all current ranges

  2. Reduced Safety/Reliability: Arc Flash Hazard Example (cont’d) Description AvailableFault Current 8200A 8200A 8200A IEEE 1584 CalculatedIncident Energy, Cal/cm2 0.7 8.4 0.4 Category PPERequired 0 3 0 Scenario 1 Scenario 2  NEC Mandated Scenario 3 (For comparison purposes) PARTIAL Selective Coordination 400 Ampere Molded Case Main Circuit Breaker PARTIAL Selective Coordination 400 Ampere Class RK 1 Main Fuse TOTAL Selective Coordination 400 Ampere Class RK 5 Main Fuse

More Related