190 likes | 510 Views
2009 International Fuel Gas Code With Wisconsin Amendments. Training As Developed by Randy Dahmen, WI PE John Spalding, WI Architect WI Dept. of Commerce, Safety & Buildings Division, Madison, WI & LaCrosse, WI Web Site: COMMERCE.WI.GOV/SB.
E N D
2009 International Fuel Gas Code With Wisconsin Amendments Training As Developed by Randy Dahmen, WI PE John Spalding, WI Architect WI Dept. of Commerce, Safety & Buildings Division, Madison, WI & LaCrosse, WI Web Site: COMMERCE.WI.GOV/SB ICC Codes w/WI Amendments
International Fuel Gas Code (IFGC) Table of Contents • Ch. 1 Administration • Ch. 2 Definitions • Ch. 3 General Regulations • Ch. 4 Gas Piping Installations (IFGC Chapter 4 “Gas Piping” is Replaced with the National Fuel Gas Code NFPA 54-2002) • Ch. 5 Chimneys and Vents • Ch. 6 Specific Appliances • Ch. 7 Gaseous Hydrogen Systems • Ch. 8 Referenced Standards ICC Codes w/WI Amendments
Elevation of Ignition Sources IFGC 305.3 • Equipment & appliances w/ ignition sources shall be elevated > 18” above the floor. Exception if appliance is listed as “flammable vapor ignition resistant” (Note: DVSC appliances do NOT necessarily meet this criteria) • Locations include hazardous areas, public/private garages, repair garages automotive service stations & parking garages. ICC Codes w/WI Amendments
Electrical Bonding IFGC 310.1/Comm 16/NEC 250.104(B) • Above ground portion of a gas piping system (other than CSST) is to be bonded to an effective ground-fault current path. Gas piping, other than CSST, to be considered to be bonded where it is connected to appliances that are connected to the equipment grouping conductor of the circuit supplying that appliance. ICC Codes w/WI Amendments
Electrical Bonding (CSST) IFGC 310.1.1/Comm 16/NEC 250.104(B) • The figure shown on the next slide has been tested for use on a pipe. • The Dept. requires that the clamp be used on a hard pipe, and NOT on the CSST itself. • An Licensed electrician is not required unless the bonding is occurring within the electrical box, or local rules are stricter ICC Codes w/WI Amendments
Electrical Bonding (CSST) IFGC 310.1.1/Comm 16/NEC 250.104(B) • Corrugated Stainless Steel Tubing (CSST) gas piping systems shall be bonded to the electrical service grounding electrode system at the point where the gas service enters the building. The bonding jumper shall not be smaller than 6 AWG copper wire or equivalent ICC Codes w/WI Amendments
IFGC Ch. 4/NFPA 54 • All gas piping and gas piping installations shall comply with NFPA 54-2009 ICC Codes w/WI Amendments
Plastic Piping Used for VentingIFGC 503.4.1.1 • Plastic pipe & fittings used to vent appliances to be installed in accordance with appliance manufacturer’s installation instructions. • Where a primer is required, the primer shall be of a contrasting color. ICC Codes w/WI Amendments
Chimney Termination -Low Heat GasIFGC 503.5.4 • DO NOT • INSTALL • Below parapets • Under eaves • Next to walls INSTALL > 2 ft > 3 ft > 10 ft < 10 ft (unless the product is listed for such use) ICC Codes w/WI Amendments
Per the Vent Product Listing? ICC Codes w/WI Amendments
Chimney Termination - Medium Heat GasIFGC 503.5.4 • DO NOT INSTALL • Below parapets • Under eaves • Next to walls INSTALL > 10 ft > 10 ft > 25 ft < 25 ft (unless the product is listed for such use) ICC Codes w/WI Amendments
Venting 2 or more Gas AppliancesIFGC 503.10.4 • Where 2 or more vent connectors enter a common gas vent, chimney flue or single-wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible material. ICC Codes w/WI Amendments
Venting 2 or more Gas AppliancesIFGC 503.10.4 .1 • Where two or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of < 45o or less from vertical ICC Codes w/WI Amendments
No dips or sags, fasten to flue collars and hood outlets with screws or other acceptable means Must slope upward to vent or chimney at least 1/4” per 1 ft Max horizontal length for single wall is 75% of height Max horizontal length for “B” double wall or chimney vent, is 100% of height Vent Connector RequirementsIFGC 503.10.7, 8 & 9 ICC Codes w/WI Amendments
Harry Homeowner installed this CPVC pipe touching the flue pipe. • The fix? Slip some cardboard between the warm flue pipe and meltable plastic! • The good news? The gas was turned off and repairs were done by a licensed plumber before re-inspection. ICC Codes w/WI Amendments
This section of water heater flue pipe is made entirely out of aluminum foil! Vent ConnectorIFGC 503.10.2.3.3 (Aluminum?) ICC Codes w/WI Amendments
Gas Cooking Appliances IFGC 623 • Open-top broiler units hoods to have a min. clearance of 24” to be maintained between the cooking top and combustible material above the hood, such as cabinets. • A minimum clearance of 30” is required above household cooking appliances. Req’t reduced to 24” where 1 of 3 listed exceptions are met. ICC Codes w/WI Amendments