2011 INSURV Damage Control Surface Trends as of July 2011. DC Over all Grades. DC Over all Grades. CG (Mobile Bay) in San Diego, DDG (Forest Sherman) in Norfolk and FFG (Dewert) in Mayport were degraded. Japan DC Overall. Japan DC Grade by Areas. Mayport DC Overall.
E N D
DC Over all Grades • CG (Mobile Bay) in San Diego, DDG (Forest Sherman) in Norfolk and FFG (Dewert) in Mayport were degraded.
Mayport DC Grade by Areas • Dewert Halon was unsat.
San Diego DC Grade by Areas • Drainage for all ships were unsat.
Norfolk DC Grade by Areas • Halon for all ships were unsat except Nicolas (Redo).
Ballast Hits Contributing to Grade • 2 of 87 tanks valve inoperative from Ballast Control.
AFFF Hits Contributing to Grade • 34 leaks • 25 kinked or collapsed hoses • 8 inoperative or seized nozzles or valves. • 5 expired or missing hydro dates. • 3 inoperative push buttons.
Halon Hits Contributing to Grade • 30 inoperative indicators and/or alarms. • 18 leaks. • 6 faulty time delays. • 6 inoperative vent dampers. • 1 CO2 lever failed to Latch.
Drainage Hits Contributing to Grade • 34 seized valves. • 17 valves leaked by. • 10 gages inoperative. • 3 eductors failed to create a vacuum. • 1 eductor was tagged out.
DCPO Hits Contributing to Grade • 108 of 658 WTC failed (not watertight). • 79 of 658 WTC were degraded (missing hardware or out of adjustment). • 84 of 137 Firezone/ Ellison doors failed. • 31 walk thru discrepancies (CO2. PKP, Fire Station). • 21 of 176 Overboard Fittings failed. • 18 of 176 Overboard Fittings degraded.
Breathing Air Hits Contributing to Grade • 81 missing items. • 20 pieces of equipment failed to operate properly. • 12 leaks. • 3 low pressure
CBR Hits Contributing to Grade • 16 missing Items. • 13 CMWD Zones with no or low flow nozzles. • 6 incorrect HHA Refrigerators.
Misc Hits Contributing to Grade • 65 faulty alarms. • 35 of 159 inoperative remotely operated firemain valves. • 100 of 278 explosion proof lights failed. • 10 P-100’s failed.