Antony Ren Delta Electronics, Inc. PSBG IDC. Delta’s Contribution for OCP Solution 2014. Facebook Open Rack V2. Key Features: Fully complied with FB V2 & OCP spec. 1250 Kg loading ability Two power shelves / power zones. Free configuration flexibility. Facebook Open Rack V2.
E N D
Antony Ren Delta Electronics, Inc. PSBG IDC Delta’s Contribution for OCP Solution 2014
Facebook Open Rack V2 • Key Features: • Fully complied with FB V2 & OCP spec. • 1250 Kg loading ability • Two power shelves / power zones. • Free configuration flexibility.
Facebook Open Rack V2 External Size: W: 600 mm H: 2210 mm D: 1067 mm Internal space: 3 OU for switch 4 OU for power 32 OU for devices Total: 39 OU 3 OU for switches 8 OU for devices 2 OU for power shelf 8 OU for devices Support bar 8 OU for devices 2 OU for power shelf 8 OU for devices
Facebook Open Rack V2 DC PDU AC PDU Stingray V2 Power shelf Power shelf V2
Facebook Open Rack V2 Testing! How Delta verify the rack worked? • Caster test • Swivel level feet test • Rack Devices Retrofit Test • Rack moving test
Facebook Open Rack V2 Caster Test To meet rack total 1385 (1250 + 135) kg weight requirement, one single caster can withstand 550 Kg for both static and dynamic conditions (about 40 % of max rack total weight, 4 casters in one rack). a. Static loading test Passed! b. Dynamic moving test Passed!
Facebook Open Rack V2 Static loading test (659 Kg / 16 hours) Loading Caster
Facebook Open Rack V2 Dynamic moving cross obstacle test Loading 550 Kg, 2700 meters moving, speed: 0.9 meter / sec, Obstacle height: 3.6 mm, Change moving direction each 3 mins.
Facebook Open Rack V2 Swivel level feet Test To meet rack total 1385 (1250 + 135) kg weight requirement, Single swivel level feet can withstand 1200 Kg for both vertical and 10∘angle conditions (about 87 % of max rack total weight, 4 feet in one rack). a. Vertical loading test (1200 kg vertical static) Passed! b. Limit angled loading test (1200 kg 10∘) Passed!
Facebook Open Rack V2 Vertical Loading Test (1595 Kg / 16 hours tested)
Facebook Open Rack V2 Angled Loading Test (1595 Kg / 16 hours tested on two directions) Test on the opposite direction
Facebook Open Rack V2 Devices Retrofit Test
Facebook Open Rack V2 • Rack Moving Test • Load up the rack to its maximum loading (1250 Kg) for: • Over 6 mm high obstacle 5 times. • Passed! • Over 1” wide gap 5 times • Passed! • Move rack up and down 10’ / 5° ramp 5 times • Passed! • Moving force test (less than 5% of rack total weight) • Passed! • Rack total weight: 1250 + 135 = 1385 Kg • Tested force on terrazzo floor is 35 kg, 2.52% total weight.
Facebook V2 PDU • Key Features: • Box on rack top design • On-site serviceability • Modularized design support different region power type requirements.
Facebook V2 PDU AC input plugs Output Connector (with molding) Locking Latches AC PDU 16A 277 / 480 VAC, With surge protection, 2 inputs / 2 outputs
Facebook V2 PDU Locking Latches Input connector DC 54V, Connect to power shelf Output connectors Signal Ports Signal Ports
Fidelity Open Bridge Rack • Key Features: • OCP and EIA two-way interchangeable rack • Easier and quicker conversion • Lockable, removable front / rear doors • Two independent power shelves for OCP
Fidelity Open Bridge Rack External Size: W: 28” H: 82.3” D: 50.1” H D W
Fidelity Open Bridge Rack OCP Spacing EIA Spacing Zone 3 16 OU (23~38) for devices Zone 2 6 OU (17~22) for two set power shelves EIA standard 19” / 42U Total 38 OU Zone 1 16 OU (01~16) for devices
Fidelity Open Bridge Rack Front / rear door can be removed / installed tool-less. 90∘
Fidelity Open Bridge Rack OCP EIA 4 3 2 1 Transforming time: 25 minutes / 2 operators 3 4 2 1
Fidelity Open Bridge Rack Step 1: Exchange the location of column 1 & 2. Step 2: Exchange the location of column 3 & 4. Step 3: Rotate column 1 & 4 by 90 degrees counterclockwise. Step 4: Rotate column 2 & 3 by 90 degrees clockwise. Step 5: Fix to Rack EIA OCP 3 3 4 1 1 2 3 4 4 2 2 1
Fidelity Power System Two independent power shelves and copper bus bar sets.
Fidelity Power System Output Bus Bar Connection Upper side vertical Bus Bar Busbar connection between shelf and Rack AC PDU *2 Down side vertical Bus Bar
Fidelity Power System AC PDU Design – Delta 208V/ 230V AC input plug NEMA L22-30P AC output breaker; 2 PCS AC outlet C13; 4 PCS (2 PCS on top, 2 PCS on bottom) AC I/P power cord UL2586 #10 5C AC output cord For shelf
Fidelity Power System AC PDU Design – WYE 400V/415V AC output breaker; 2 PCS AC outlet C13; 4 PCS (2 PCS on top, 2 PCS on bottom) AC input plug ME460P9W -1109A AC I/P power cord SOOW #4 4C AC output cord For shelf
Fidelity Power System Power Shelf Key Specifications RMC 3pcs PSUs + 3pcs PSUs, maximum power 7.5KW
PSU3_B PSU2_B PSU1_B PSU3_A PSU2_A PSU1_A Fidelity Power System Power Shelf’s Block Diagram– Delta Connection 3 phase 208Vac L3 L2 L1 DC+ DC- L3 L2 L1 I2C& Alert Signals
Fidelity Power System Delta Connection Shelf Outward Drawing RMC slot 3 PSUs + 3 PSUs, maximum power 7.5KW Front View Main 12.5V with 3 pair Bus bar Rear View Dual AC 208V inputs
PSU3_B PSU2_B PSU1_B PSU3_A PSU2_A PSU1_A Fidelity Power System Power shelf’s block diagram – WYE Connection 3 phase 400Vac L3 N L2 L1 DC+ DC- L3 N L2 L1 I2C& Alert Signals
Fidelity Power System Delta Connection Shelf Outward Drawing RMC slot 3 PSUs + 3 PSUs, maximum power 7.5KW Front View Main 12.5V with 3 pair Bus bar Rear View Dual AC 400V inputs
Fidelity Power System PSU Photo – AC: DPST-2430AB B
Fidelity Power System PSU Key Specifications H: 40.9mm D: 436mm W: 101.6mm
Fidelity Power System PSU Block Diagram -- DPST-2430AB
Fidelity Power System Tested Efficiency of AC&DC Input PSU PSU Eff. Efficiency Load The efficiency result can meet he platinum level of 80plus requirement. 48
Fidelity Power System Power Shelf – RMC Functions RMC functions – FW/SW management • Both RMC and PSU’s Firmware can be upgrade via serial port or GbE port CPMS PSU FW Browser Network RMC FW/SW management Memory FW RS232 Cable PSU ATS PSU ATS PSU ATS PSU ATS PSU ATS PSU 49
Fidelity Power System RMC Block Diagram and Interface Interface: Gigabit Ethernet (RJ45) USB , support OTG function (Micro-USB) RS-232_COM0 + CAN_0 (RJ45) RS-232_COM1 + CAN_1 (RJ45) Reset Button LED indicator (Red and Green light)