260 likes | 434 Views
The new 3-ph and 1-ph UPS family From 10 kVA to 30 kVA. Alcor & Mizar. Alcor – Mizar: power ratings. Mizar. 10kVA, 15kVA.
E N D
The new 3-ph and 1-ph UPS familyFrom 10 kVA to 30 kVA Alcor & Mizar
Alcor – Mizar: power ratings Mizar 10kVA, 15kVA “Mizar and Alcor are the most famous double stars in the sky. At good conditions the double can be seen without problems. However it is not sure if Mizar and Alcor really orbit each others or they are only neighbours.” Alcor 20 kVA, 25kVA, 30kVA
Alcor – Mizar: general diagram (1) By-pass Input Inverter LOAD Static Switch Output Inverter Batteries
Alcor – Mizar: general diagram (1) NEW No DC voltage booster No battery charger Sinus-shape current (cosj=1, THD < 5%) Power Factor Control (PFC)
Alcor – Mizar: configurations (1) • Alcor – Mizar have big configuration capability. Each unit can be configured by LCD (password protected): 3 phase IN – 3 phase OUT 3 phase IN – 1 phase OUT 1 phase IN – 1 phase OUT Also: 1 phase IN – 3 phase OUT if required
Alcor – Mizar: configurations (2) Mizar and Alcor are available in the following configurations: • Stand alone • Hot stand-by (eco-mode) • Redundant Parallel or full power parallel * It is possible to have maximum n°8 units in parallel. ** The communication between the units of the parallel system is ring type by optical fibres.
Alcor (20/30 kVA): power components (1) 120ARMS three phase inverter AC terminals DC terminals IGBT terminals
Alcor (20/30 kVA): power components (2) Static switch (SCR 85 ARMS) • Load on Inverter • Load on Bypass • Precharge from AC mains AC Terminals AC
Mizar (10/15 kVA): power components (1) 60ARMS IGBT In 1 UPS: 6 x (3 on input, 3 on output)
Mizar (5/15 kVA): power components (2) 25 A relay • Load on Inverter • Load on Bypass • Precharge from AC mains
Alcor – Mizar: LCD display Standard Powertronix (as in SNova) Start/Stop Load switching Rated values configuration Check alarms / status 8 languages available
Alcor – Mizar: design details The same mechanical design for different UPS sizes All power components on 1 board Same control logic for all UPS EASY to MAINTAIN
Alcor – Mizar: operating principle (1) load L DC ~ = ~ = IGBT IGBT Pulse width modulation Measure & regulation
Alcor – Mizar: operating principle (2) Input inverter control details DC voltage regulation (2 x 405 V) Battery charge and control Input current limitation • (it operates as rectifier + DC voltage booster + battery charger)
~ AC = Alcor – Mizar: operating principle (3) PFC: Power Factor Control DC voltage regulated at reference value DC The current has “the same shape” of AC voltage i UPS R v
Alcor – Mizar: operating principle (4) PFC: Power Factor Control High sampling speed (64 µsec) Switching frequency up to 16kHz High speed A/D conversion (32 measurements: voltage, current and temperature) Low harmonic distortion without transformers or magnetic components (12-pulse)
Alcor – Mizar: operating principle (5) OFF +VDC/2 Firing input inverter IGBT the DC voltage value can be regulated -VDC/2 Vmains N ON Current path (T/2)
Alcor – Mizar: input side measurements voltage current
Alcor – Mizar: operating principle (6) Output inverter regulation Output voltage regulation (sinus wave voltage 192 points/period) Current limit (short circuit protection) Output current limitation (overload)
Alcor – Mizar: output side measurement voltage current
Alcor – Mizar: batteries • The unit is equipped with 60 INTERNAL batteries (2 x 360 V) • An additional cabinet with120 batteries is availablefor extended autonomy