Messung's solutions are designed to share information and make sure youru00a0u00a0systems work together maximizing both comfort and energy efficiency while reducing energy expenses. Whether new construction or retrofit applications, Messungu2019s expert can help you to design, install, integrate and maintain your control system with efficient energy management. Messung's solutions have the flexibility and scalability to adapt, and deliver results for your building environment.<br>

Download Presentation

Industrial grade PLC for HVAC solutions in industries

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Industrial grade PLC for HVAC solutions in industries www.messungautomation.co.in

  2. Messung's solutions are designed to share information and make sure your  systems work together maximizing both comfort and energy efficiency while reducing energy expenses. Whether new construction or retrofit applications,Messung’s expert can help you to design, install, integrate and maintain your control system with efficient energy management. Messung's solutions have the flexibility and scalability to adapt, and deliver results for your building environment. www.messungautomation.co.in

  3. About AHU An Air Handling Unit (AHU) regulates and circulates air as part of a heating, ventilating and air-conditioning (HVAC) system. It consists of a blower, heating or cooling elements, filter racks, sound attenuators and dampers. It is usually connected to a ductwork system that distributes the conditioned air through the building and returns it to the AHU. Sometimes, AHUs discharge and admit air directly to and from the space without ductwork. With the growing emphasis on energy performance in buildings, and new standards to study and improve energy efficiency, buildings need automation & control systems to achieve high levels of energy efficiency. HVAC is one area where huge amount of power is consumed, and where plants with energy-optimised design, installation and commissioning are a must. Automation with AHU-specific functions ensures more systems' energy efficiency, operational reliability and availability. Automation also monitors room and outdoor temperatures to reduce cooling energy needs and improve comfort levels. www.messungautomation.co.in

  4. A Case Study “Our Customer is a Bengaluru based company involved into manufacturing of Products like Metal Working Tools, Mining, Foundation Drilling cutting Tools, Tungsten carbide wear components etc. required for Industries like Aerospace, Additive manufacturing, Machine Tool Industry, Energy, Earthworks.” www.messungautomation.co.in

  5. Basic AHU for Coating Room The project required Messung’s solution to ensure that the coating room is maintained under 5 Pa Negative pressure with respect to ambient and within the room temperature zone of 21.1 Deg. C to 24.4 Deg. C and RH Zone of 40% to 60%. Since the system is working round the clock, it is necessary to control the system in such a way that minimum power is consumed by the HVAC system.  In addition, in case of any process gas leakage in the coating room, fresh air supply and exhaust to be operated at the it’s full capacity to exhaust the leaked gases promptly. www.messungautomation.co.in

  6. Messung proposed an AHU System which can maintain acceptable room conditions using 2 stage evaporative cooling or using chilled water cooling coil, depending on the ambient air conditions throughout the day and year. • Variation of ambient conditions in Bengaluru through the day and year is such that the ambient air conditions can be used to maintain the desired room conditions for much of the time, mainly in cooler nights and winter season. • Since the plant is working round the clock, Messung decided to make use of favorable ambient conditions to the best possible extent to minimize the power consumption by AHU system. • Messung divided the variation of ambient air conditions throughout year, into 3 parts: • Mode -I, where in the ambient condition is hot and dry, where either single stage or 2 stage evaporative cooling can be used to maintain room conditions. • Mode – II, Monsoon conditions with high RH and not so cold temperature, wherein conventional chilled water cooling coil will be used to cool and de humidify and maintain the designed room conditions • Mode – III, typically winter conditions, Messung proposed to modulate return air and cold fresh, as well as single stage evaporative cooling to maintain the designed room conditions. Messung’s solution www.messungautomation.co.in

  7. Proposed Control System www.messungautomation.co.in

  8. Versatile CPU with large Input/Output signals handling capacity • Capturing real time data for Temperature, Relative Humidity, Running hours for AHU • Large program memory for implementing complex Relative Humidity formulas • Incorporating of Program Algorithm based on Psychrometric chart readings • Connection of CPU with 15 nos. of VFD’s on MODBUS RTU control network • Prompt monitoring & controlling the entire system using HMI Salient Features www.messungautomation.co.in

  9. Psychrometric Chart www.messungautomation.co.in

  10. Psychrometric Chart www.messungautomation.co.in

  11. MESSUNG is an Automation Partner capable of Supplying Solutions to any Project of Air Handling Units and Environment Control Systems. Messung's NX-ERA Series of PLCs for industrial automation help to monitor, control and optimise AHUs to ensure performance and efficiency of HVAC systems. Messung's AHU control systems feature these latest technology PLCs with user-friendly interface to monitor and control each component of the AHU including fans, heating, cooling, humidification, heat recovery, etc. The systems offer design flexibility with variable size options and a wide range of choices to make your facility more productive and energy-efficient. www.messungautomation.co.in