时间继电器自动控制 Y-△ 降压启动线路故障检修

课题:. 时间继电器自动控制 Y-△ 降压启动线路故障检修. QS. FU 2. L 1. 1. L 2. L 3. 0. FR. 2. FU 1. SB 2. KM. 3. SB 1. FR. KM. 4. KM Y. KM △. U 1. V 1. W 1. 5. 7. KT. KM Y. 6. 8. M. KM △. KM Y. KT. KM. KM △. 3 ~. PE. W 2. V 2. U 2. KM Y. 复习: 时间继电器自动控制 Y -△ 降压启动线路的工作原理:. 开始计时.

Download Presentation

时间继电器自动控制 Y-△ 降压启动线路故障检修

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 课题: 时间继电器自动控制Y-△降压启动线路故障检修

  2. QS FU2 L1 1 L2 L3 0 FR 2 FU1 SB2 KM 3 SB1 FR KM 4 KMY KM△ U1 V1 W1 5 7 KT KMY 6 8 M KM△ KMY KT KM KM△ 3~ PE W2 V2 U2 KMY 复习:时间继电器自动控制Y-△降压启动线路的工作原理: 开始计时 延时断开 “Y”接法降压启动 “△”接法全压运行

  3. QS FU2 L1 1 L2 L3 0 FR 2 FU1 SB2 KM 3 SB1 FR KM 4 KMY KM△ U1 V1 W1 5 7 KT KMY 6 8 M KM△ KMY KT KM KM△ 3~ PE W2 V2 U2 KMY 复习:时间继电器自动控制Y-△降压启动线路的工作原理: “Y”接法降压启动 “△”接法全压运行 4 1 5 3 2 0

  4. FU L1 L2 1 Ω FR 0 2 Ω SB2 3 Ω KM SB1 4 Ω KM 电阻分段测量法(a) (a)

  5. FU ① ② ③ ④ L1 L2 1 Ω FR 0 2 Ω SB2 3 Ω KM SB1 4 Ω KM 电阻分段测量法(b)

  6. FU2 L1 1 L2 0 FR 2 3 SB2 SB1 KM 4 KMY KM△ 5 7 KT KMY 6 8 KMY KT KM KM△ 一、故障检修步骤: 1、用通电试验法观察故障现象; 2、断电后用逻辑分析法确定故障范围; 3、用电阻测量法正确找出故障点; 4、排故后通电试车。 二、通电检修注意事项: 1、通电前检查电路是否存在安全隐患; 2、规范操作:严格按照通、断电次序操作; 3、通电检查时,发现不正常情况应立即停车检查; 4、不要随意触动带电电器; 5、养成单手操作的习惯。

  7. 课后思考: 一旦主电路出现故障(开路或短路)对整个电路的运行和电机有什么影响,会出现什么后果?