Mounting of the IZM. Mounting of the IZM. The IZM can be mounted in tilted position up to 30°. 30°. 30°. 30°. 30°. Mounting of the IZM. on horizontal surface (standard). Fixed 4 bolts M8-8.8. Mounting of the IZM. on horizontal surface (standard). Withdrawable unit 4 bolts M8-8.8
E N D
The new line of circuit breaker IZM Mounting of the IZM
The new line of circuit breaker IZM Mounting of the IZM The IZM can be mounted in tilted position up to 30° 30° 30° 30° 30°
The new line of circuit breaker IZM Mounting of the IZM on horizontal surface (standard) Fixed 4 bolts M8-8.8
The new line of circuit breaker IZM Mounting of the IZM on horizontal surface (standard) Withdrawable unit 4 bolts M8-8.8 + Nuts + Strain washers
The new line of circuit breaker IZM Mounting of the IZM on vertical surface: IZM1/2-XTW (available for frame size 1 + 2) NEW
The new line of circuit breaker IZM Mounting of the IZM on vertical surface: IZM1/2-XTW NEW Mounting brackets 1. Fix the brackets at the mounting plate
The new line of circuit breaker IZM Mounting of the IZM on vertical surface: IZM1/2-XTW NEW Mounting brackets 2. Insert the breaker and fix it
The new line of circuit breaker IZM Mounting: Sealing frame IZM-XRT Protection degree: IP40
The new line of circuit breaker IZM Mounting of the IZM Example: IZMN1-V1600 in withdrawable technique, panelboard of 400 mm with sealing frame
The new line of circuit breaker IZM Mounting: Protective cover IZM-XDT Mounted with two hinges: Can be opened to the left or to the right hand side. And can be removed completely. Not designed for combination with sealing frame IZM-XRT. (Combination not neccessary for the high protection degree.) Protection degree: IP55
Horizontal Connection (standard to 5000 A) Vertical Connection IZM.-XATV.. (optional up to 5000 A standard for 6300 A) The new line of circuit breaker IZM Mounting: Connection technology
The new line of circuit breaker IZM Mounting: Connection technology Front Connection (optional up to 4000 A) Double-hole fitting IZM.-XATF.. Meaning: the holes are arranged in two lines Single-hole fitting IZM.-XAT1F.. Meaning: the holes are arranged in one line Free choice between double- and single-hole fitting. Free choice, not depending on the rated current.
The new line of circuit breaker IZM Mounting: Connection technology NEW Flange connections IZM.-XATA..-AV for the withdrawable technique only (optional up to 4000 A)