Arc-Killer SV-25 - DF-2 + Range. Overview. General Overview Drive Mechanism Cubicle Integration. Overview. General Overview Drive Mechanism Cubicle Integration. General Overview. Arc-Killer SV-25 provides additional safety by minimizing the effects of an internal arc.
E N D
Arc-Killer SV-25 - DF-2+Range Arc-Killer SV-25 – DF-2+ Range
Overview • General Overview • Drive Mechanism • Cubicle Integration Arc-Killer SV-25 – DF-2+ Range
Overview • General Overview • Drive Mechanism • Cubicle Integration Arc-Killer SV-25 – DF-2+ Range
General Overview • Arc-Killer SV-25 provides additional safety by minimizing the effects of an internal arc. • Less energy released • Fewer architectural/structural demands • Unit is reusable after an arc Arc-Killer SV-25 – DF-2+ Range
SV-25 Basic Principles Ionisation Ignition Pressure build fault occurrence Metal Short Circuit SV-25 triggered Arc extinguished 0 18 48 ms Arc-Killer SV-25 – DF-2+ Range
Overview • General Overview • Drive Mechanism • Cubicle Integration Arc-Killer SV-25 – DF-2+ Range
Drive Mechanism [1] • Energy required for operation stored in compression spring • Stored energy is blocked until the system receives a trigger signal Arc-Killer SV-25 – DF-2+ Range
Drive Mechanism [2] • Trigger is not activated: • Before arcing occurs in electrical unit • As a result of environmental vibrations • RP 427-04: Test to demonstrate that arc-killers inside both units will not operate during short-time current and peak withstand current test • When an electrical fault occurs: • Trigger signal is forwarded • Stored energy is released • Additional earthing knife action prevented Arc-Killer SV-25 – DF-2+ Range
Drive Mechanism [3] • Front View Rear View Tension springs Tension springs Arc-Killer SV-25 – DF-2+ Range
Overview • General Overview • Drive Mechanism • CubicleIntegration Arc-Killer SV-25 – DF-2+ Range
Integration of Arc-Killer SV-25 Expansion volume Supplementary Earthing knife Earthing knife Drive mechanism SV-25 Trigger signal Arc-Killer SV-25 – DF-2+ Range
Safety at all times • Cable compartment not accessible. Interlock Earthing Paddle Drive Mechanism SV-25 Released Arc-Killer SV-25 – DF-2+ Range
Safety at all times • Cable compartment door freely accessible. (Door removed.) Interlock Earthing Paddle Drive Mechanism SV-25 Locked Arc-Killer SV-25 – DF-2+ Range
Safety at all times Arc-Killer SV-25 – DF-2+ Range
Safety at all times Arc-Killer SV-25 – DF-2+ Range
Test & Certificates • Tests were carried out in accordance with IEC 62271-200 • SV-25 meets the requirements: • IAC AFL 20kA • IAC BFLR 4.8kA • The Arc-Killer is activated quick enough to reduce all harmful effects of an internal arc. • As a result, the consequences are negligible. Arc-Killer SV-25 – DF-2+ Range