1 / 12

Stratos ECO Training

Stratos ECO Training. ECM “Smart” Circulators for Heating, DHW Recirculation Systems. ECO 16 FX. ECO 16 F. ECO 16 BFX. Presentation Date – New Jan 2008. Stratos ECO Circulators. WILO Small Wet Rotor Circulators ECM “Smart” Automatically Controlled Circulators.

neci
Download Presentation

Stratos ECO Training

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Stratos ECO Training ECM “Smart” Circulators for Heating, DHW Recirculation Systems ECO 16 FX ECO 16 F ECO 16 BFX Presentation Date – New Jan 2008 Stratos ECO Circulators

  2. WILO Small Wet Rotor CirculatorsECM “Smart” Automatically Controlled Circulators • Stratos ECO Cast Iron & Bronze • ECM (Electronically Communicated) technology • Smart pump adjusts flow to system changes • Auto setback • Anti-seizing feature • Easy wiring quick connectors • Easy set-up (∆p-v in feet of head via red button) • Interchangeable with all competitors • Replaces 12 competitor’s types • 115 and 230 volt, models, cast iron & bronze • Max temp 230 deg F, min temp 60 deg F • Maximum pressure 145 PSI • Minimum pressure – see sheet • Maximum wattage 59, minimum wattage 5.8 • Class “A” energy rating Eco 16 FX & BFX Model Eco 16 F Model

  3. Model Number Designation ECO 16 ( ) FX • 16 = Maximum Head in Feet (adjustable from 4’) • B = Pump Housing (Volute) Material • (B for Bronze, no Letter for Cast Iron) • FX = Pipe Connection • F = Flanged • FX = Flanged Rotated

  4. Benefits - External Fits all Competitors’ Models (2 Bolt Residential Flanges) 2 Allan Screw Connection Automatic Air Venting (Inspection and Service Screw) Red Button Sets Head (∆pv in feet) Also Activates/deactivates Setback

  5. Benefits – Electrical 115/1/60 & 230/1/60 Volt 2 Electrical Openings Wilo-quick connections

  6. Sizing Examples • Sizing Examples – Simplified Heating • Determine BTU’s and Temperature Differential (mostly given) • Calc Flow (USGPM) = BTU per hr/500 (constant)/temperature diff deg F • EG: 10 USGPM will pump 100,000 BTU/hour @ 20 deg F differential • Once flow known size pipe based on max velocity of 4 ft/sec • Higher velocities cause noise, erosion and air problems • Once pipe sized estimate friction loss • Manifold systems heads are not additive – use the highest loss loop • Once friction loss and flow are determined match point to curve • Remember to use the correct companion flanges • Rotate Inventory!

  7. Installation Instructions • Install with shaft horizontal • Pump in any direction (vertical, horizontal etc.) • If pumping vertical try to pump up (with air) • Locate in system where suction pressure as high as possible • Pump away from the thermal expansion tank! • Fluid should be relatively free of abrasive particles • Damages sleeve bearings in wet runners and mechanical seals in dry runners • Do not use any stop leak products (see label) • Install with terminal box @ 9:00, 12:00 or 3:00 positions • Installing @ 6:00 can allow fluid into terminal box during air bleeding • Do not install at the highest point (air) • Do not install at the lowest point (dirt) • Be careful with the suction side (laminar flow)

  8. Application Examples • Applications • Cast Iron (Ferrous) Models • Primary and Secondary Hot and Chilled Water Systems • Up to 50 % Maximum Glycol – DO NOT USE STOP LEAK PRODUCTS! • Closed loop (airless) hot and cold circulation systems (60 to 230 deg F) • Bronze (non-Ferrous) Models • Open loop systems (ie Domestic HW Recirculation) – Max Temp 150 deg F (66 deg C) • Higher temps can cause precipitation of Calcium in hard water applications • Maximum working pressure 145 PSI • Minimum inlet pressure • 0.7 PSI @ 122 deg F (50 deg C) • 4.4 PSI @ 203 deg F (95 deg C) • 14.5 PSI @ 230 deg F (110 deg C) • For indoor use only

  9. ECO DocumentationClick Data Sheet to Access PDF file

  10. Cross Reference: Cast Iron Pumps New body launched in 2007 Also available in 3 speed version

  11. Cross Reference: Stainless Steel and Bronze Body Pump Also available in 3 speed version New body launched in 2007

  12. Questions / Comments?

More Related