UDC3500 How to switch from Remote to Local SP

Switching between a Remote & Local Setpoint with a Digital Input.<br><br>Solution: Specify a UDC 3500 with a Digital Input Option.<br><br>When a digital input is configured for To LSP, the UDC will switch from Remote SP to a Local SP with a contact or switch closure.<br><br><br>Configuration:<br><br>1.Setup – Control – RSP SRC is set to Input 1, 2, 3, 4, 5, IN ALG 1 or IN ALG 2.<br><br>2.Setup – Option – DIG INP 1 2, 3 or 4 is set to LSP<br><br><br>Operation:<br><br>1.Make sure that the Digital Input Switch is open and Remote SP is selected<br><br>2.Set the desired setpoint for Local SP using the Lower Display & arrow keys.<br><br>3.With the Digital Input Switch closed, SP will be displayed on the Lower display.<br><br>4.When the Digital Input Switch is re-opened the bar next to the left of the RSP will light, and the Remote SP will be the controlling setpoint.<br><br><br>Notes:<br><br>1.If the Setpoint Select is enabled, then someone can override the Digital Input by pressing the SP Select key.<br><br>A suggested correction is, prior to doing step 3 in the operation section, go to Tuning Group and set the Lockout to None. Keep pressing the Function key until SP SEL appears in the lower display. Set the Upper Display to DISABLE.<br><br>With the Setpoint Select set to disable, the unit can not be switched to Local SP by the keyboard.<br><br>2.A different set of Tuning constants can be selected when Local SP is selected. If Two sets of Tuning constants are selected under the Control section, then by using the DIG 1 CMB or DIG 2 COMB set to PID 2 then PID set 2 tuning values will be used when SP is selected.<br><br><br>For more Industrial HVAC Equipment and Controls visit http://DtiCorp.com/

noblex
Download Presentation

UDC3500 How to switch from Remote to Local SP

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. DtiCorp.com - Industrial HVAC Equipment and Controls U U UD D DC C C 3 3 35 5 50 0 00 0 0 A A Ap p pp p pl l li i ic c ca a at t ti i io o on n n N N No o ot t te e e Switching between a Remote & Local Setpoint with a Digital Input Solution:Specify a UDC 3500 with a Digital Input Option. When a digital input is configured for To LSP, the UDC will switch from Remote SP to a Local SP with a contact or switch closure. Configuration: Setup – Control – RSP SRC is set to Input 1, 2, 3, 4, 5, IN ALG 1 or IN ALG 2. Setup – Option – DIG INP 1 2, 3 or 4 is set to LSP Wiring : DIGITAL SWITCH 1 19 DIGITAL SWITCH 2 20 21 DIGITAL SWITCH 3 22 DIGITAL SWITCH 4 Connect shield to ground at one end only. 23 Operation: 1. Make sure that the Digital Input Switch is open and Remote SP is selected 2. Set the desired setpoint for Local SP using the Lower Display & arrow keys. 3. With the Digital Input Switch closed, SP will be displayed on the Lower display. 4. When the Digital Input Switch is re-opened the bar next to the left of the RSP will light, and the Remote SP will be the controlling setpoint. Notes: 1. If the Setpoint Select is enabled, then someone can override the Digital Input by pressing the SP Select key. A suggested correction is, prior to doing step 3 in the operation section, go to Tuning Group and set the Lockout to None. Keep pressing the Function key until SP SEL appears in the lower display. Set the Upper Display to DISABLE. With the Setpoint Select set to disable, the unit can not be switched to Local SP by the keyboard. 2. A different set of Tuning constants can be selected when Local SP is selected. If Two sets of Tuning constants are selected under the Control section, then by using the DIG 1 CMB or DIG 2 COMB set to +PID 2 then PID set 2 tuning values will be used when SP is selected. Page 1 of 1 Revision 1

More Related