1 / 49

Chapter 8

Feedback Controllers. Chapter 8. Chapter 8. Error Signal. Proportional Control. Chapter 8. Reverse or Direct Acting Controller. Direct-Acting (Kc < 0) : “output increases as input increases" Reverse-Acting (Kc > 0) : “output increases as input decreases". Chapter 8.

nodin
Download Presentation

Chapter 8

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Feedback Controllers Chapter 8

  2. Chapter 8

  3. Error Signal

  4. Proportional Control

  5. Chapter 8

  6. Reverse or Direct Acting Controller • Direct-Acting (Kc < 0): “output increases as input increases" • Reverse-Acting(Kc > 0): “output increases as input decreases"

  7. Chapter 8

  8. Proportional Band (PB) PB is the error (% of the range of controlled variable) required to move the output from its lowest to its highest value.

  9. Example 2:Flow Control Loop Chapter 8 • Assume FT is direct-acting. • 1.) Air-to-open (fail close) valve ==> ? • 2.) Air-to-close (fail open) valve ==> ? • Consequences of wrong controller action??

  10. Chapter 9

  11. Example 3:Liquid Level Control • Control valves are air-to-open • Level transmitters are direct acting Chapter 8 Question: Type of controller action?

  12. INTEGRAL CONTROL ACTION Chapter 8

  13. Proportional-Integral (PI) Controller

  14. Reset Time Reset time is the time that the integral mode repeats the action of proportional mode.

  15. Example: Heat Exchanger Control Loop

  16. Reset Windup

  17. Reset Windup

  18. Anticipatory or Derivative Control Action

  19. Proportional-Integral-Derivative (PID) Control Now we consider the combination of the proportional, integral, and derivative control modes as a PID controller. • Many variations of PID control are used in practice (see Table 8.1, page 194) • Next, we consider the three most common forms.

  20. Parallel Form of PID Control

  21. Effects of Anticipatory (Derivative) Control Action

  22. Drawbacks of Anticipatory (Derivative) Control Action

  23. Chapter 8

  24. Parallel-Form PID Controller with Derivative Filter

  25. Derivative and Proportional Kicks One disadvantage of the previous PID controllers is that a sudden change in set point (and hence the error, e) will cause the derivative term momentarily to become very large and thus provide a derivative kick to the final control element.

  26. Elimination of Derivative and Proportional Kicks in Parallel-Form Controllers

  27. Series Form of PID Control

  28. Elimination of Derivative Kick in Series-Form Controllers

  29. Expanded (Non-interacting) Form of PID Control

  30. Chapter 8

  31. Typical Response of Feedback Control Systems • Consider response of a controlled system after a • sustained disturbance occurs (e.g., step change in • disturbance variable) Chapter 8

  32. Chapter 8

  33. Chapter 8

  34. Automatic and Manual Control Modes • Automatic Mode • Controller output, p(t), depends on e(t), controller • constants, and type of controller used. • ( PI vs. PID etc.) • Manual Mode • Controller output, p(t), is adjusted manually. • Manual Mode is very useful when unusual conditions exist: • plant start-up • plant shut-down • emergencies • Percentage of controllers "on manual” ?? • (30% in 2001, Honeywell survey) Chapter 8

  35. Digital PID Controller • where, • = the sampling period (the time between • successive samples of the controlled variable) • = controller output at the nth sampling • instant, n=1,2,… • = error at the nth sampling unit • velocity form - see Equation (8-19) • (pd)- incremental change Chapter 8

  36. Controller Comparison P -Simplest controller to tune (Kc). -Offset with sustained disturbance or set point change. PI -More complicated to tune (Kc, I) . -Better performance than P -No offset -Most popular FB controller Chapter 8 PID -Most complicated to tune (Kc, I, D) . -Better performance than PI -No offset -Derivative action may be affected by noise

  37. Summary of the Characteristics of the Most Commonly Used Controller Modes • 1. Two Position: • Inexpensive. • Extremely simple. • 2. Proportional: • Simple. • Inherently stable when properly tuned. • Easy to tune. • Experiences offset at steady state. • 3. Proportional plus integral: • No offset. • Better dynamic response than reset alone. • Possibilities exist for instability due to lag • introduced. Chapter 8

  38. 4. Proportional plus derivative: • Stable. • Less offset than proportional alone (use of • higher gain possible). • Reduces lags, i.e., more rapid response. • 5. Proportional plus reset plus rate: • Most complex • Rapid response • No offset. • Difficult to tune. • Best control if properly tuned. Chapter 8

  39. On-off Controllers • Simple • Cheap • Used In residential heating and domestic refrigerators • Limited use in process control due to continuous cycling of controlled variable  excessive wear on control valve. • Example 1: Temperature control of jacketed vessel. Chapter 8

  40. On-Off Controllers Synonyms: “two-position” or “bang-bang” controllers. Chapter 8 Controller output has two possible values.

  41. Practical case (dead band) Chapter 8

More Related