Agenda

Network Modeling Group Modeling Off Nominal Transformers in NMMS By Nitika Mago, Model Administration. Agenda. Off-Nominal Transformer – Modeling challenges faced with prevailing software Expectations from any proposed resolution

nola
Download Presentation

Agenda

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Network Modeling Group Modeling Off Nominal Transformers in NMMSBy Nitika Mago, Model Administration

  2. Agenda • Off-Nominal Transformer – Modeling challenges faced with prevailing software • Expectations from any proposed resolution • A Nominal Equivalent for two winding & three winding tranformers • Nominal Equivalent – Report Card • Questions ERCOT Limited

  3. The Challenge – Scenario 1 Planning System Operations & Market Systems NMMS XFMR Impedance XFMR Impedance Transformer Test Data (converted to appr. SI units using rated kV & 100MVA as base) @100 MVA & Vnominal XFMR Tap info. XFMR Tap info. Vrated = Windingrating Vnominal = Bus kV Vneutral = Windingrating @100 MVA & Vrated ERCOT Limited

  4. The Challenge – Scenario 2 Operations & Market Systems Planning System NMMS XFMR Impedance XFMR Impedance Normalized Transformer Test Data (converted to appr. SI units using nominal kV & 100MVA as base) @100 MVA & Vnominal XFMR Tap info. XFMR Tap info. Vrated = Windingrating Vnominal = Bus kV Vneutral = Windingrating @100 MVA & Vrated ERCOT Limited

  5. Any resolution must….. • Provide a clean & simple method for appropriately representing an off-nominal transformer. • Standardize the submission & consumption of off-nominal transformer information from the model. • Allow direct correspondence with field telemetery. • Minimize software changes necessary to implement the resolution. • Maintain system reliability & operations. ERCOT Public

  6. A Nominal Equivalent for an Off-Nominal 2 Winding Transformer • A combination of a nominal transformer with its impedance scaled to compensate for the off-nominal-turns-ratio. • The scaled impedance of this resulting transformer (ztotal) can be derived using the off-nominal transformer’s impedance (z) as, ERCOT Public

  7. A Nominal Equivalent for an Off-Nominal 2 Winding Transformer • Any associated TapChangers must be modeled using prevalent modeling practices, taking care to ensure • Step Voltage Increment is provided in percentage per unit of the nominal voltage. • Neutral Step represents the step at which rated voltage is produced • Neutral Voltage reflects the winding’s rated voltage. ERCOT Public

  8. A Nominal Equivalent for an Off-Nominal 3 Winding Transformer • Three winding transformers are modeled in the NMMS as a set of 3 two-winding transformers connected at a common 1kV node. • Model consuming applications such as the Topology Processor are designed to read this T-equivalent and convert it to true three-winding Transformer model. • When any of the windings in such a transformer is off-nominally rated, its nominal equivalent follow all principal’s defined for a two-winding transformer. ERCOT Limited

  9. A Nominal Equivalent – What works and what doesn’t Operations & Market Systems Planning System NMMS XFMR Impedance XFMR Impedance A Nominal Equivalent for an Off-Nominal Tranformer @100 MVA & Vnominal XFMR Tap info. XFMR Tap info. Vrated = Bus kV Vnominal = Bus kV Vneutral = Windingrating @100 MVA & Vrated ERCOT Limited

  10. A Nominal Equivalent – What works and what doesn’t • Topology Processor is currently tuned to extract the following TapChanger information by relying on the TransformerWinding.ratedkV attribute in CIM. • Winding Turns Ratio (WINDV1) • Voltage or phase angle @ High Step (RMA1) • Voltage or phase angle @ Low Step (RMI1) • With nominal equivalent for an off nominal transformer the computations for these is affected negatively. • Winding Turns Ratio (WINDV1) • Current • Updates needed ERCOT Limited

  11. A Nominal Equivalent – What works and what doesn’t • Voltage or phase angle @ High Step (RMA1) • Current • Updates Needed • Voltage or phase angle @ Low Step (RMI1) • Current • Updates Needed ERCOT Limited

  12. A Nominal Equivalent – What works and what doesn’t • Resolution options (in order of preference, ease of implementation) • Update the computations in Topology Processor to extract all TapChanger related information from the TapChanger instance in CIM. • Use MOD to submit corrective PMCRs. • Post Process the RAW output from existing Topology Processor to correct the associated fields with information from NMMS. ERCOT Limited

  13. Modeling Off Nominal Transformers in NMMS Questions? ERCOT Public