An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Market TrialsReal-Time Market / LFC Weekly Update August 20, 2010 http://nodal.ercot.com 1

  2. Antitrust Admonition ANTITRUST ADMONITION ERCOT strictly prohibits Market Participants and their employees who are participating in ERCOT activities from using their participation in ERCOT activities as a forum for engaging in practices or communications that violate the antitrust laws. The ERCOT Board has approved guidelines for members of ERCOT Committees, Subcommittees and Working Groups to be reviewed and followed by each Market Participant attending ERCOT meetings. If you have not received a copy of these Guidelines, copies are available at the Client Relations desk. Please remember your ongoing obligation to comply with all applicable laws, including the antitrust laws. DISCLAIMER All presentations and materials submitted by Market Participants or any other Entity to ERCOT staff for this meeting are received and posted with the acknowledgement that the information will be considered public in accordance with the ERCOT Websites Content Management Operating Procedure. http://nodal.ercot.com 2

  3. Agenda • Antitrust Admonition • Environment Report • Planned / unplanned outages • Known Issues • Standing Reports and Updates • General reminders / updates • Real Time Market / LFC Update • State Estimator Convergence Statistics • 24 Hour Full System Market and Reliability Test Update • General Full System Market and Reliability Test Update • Question and Answers / General Discussion ERCOT asks that Market Participants log into the WebEx session using their company name and then their name. This will allow ERCOT to take roll-call offline http://nodal.ercot.com 3

  4. Day-to-day operations summary: Planned / Unplanned Outages of Market Trials • Planned Outages • 08/20/2010 12:00 P.M. – 08/20/2010 6:00 P.M. • Application patch deployments are planned in the Nodal production environment and will intermittently affect services rendered by the following systems: • EWS ( Web services) • Unplanned Outages • 08/13/2010 09:00 A.M. – 08/13/2010 11:00 A.M. • A Hardware outage on one of our AIX frames in the Austin datacenter forced an emergency site failover of the Nodal production systems over to the Taylor center. ERCOT’s infrastructure team, along with IBM, is investigating the cause of the failure. The following application services were affected as a result of this outage. • MMS • EWS • MM-UI • 08/16/2010 8:00 A.M. – 08/16/2010 09:30 A.M. • Users experienced issues with downloading reports via URLs provided by the EWS Get Reports service. An incorrect application configuration was identified as the root cause of the issue. . http://nodal.ercot.com 4

  5. Known Issues Recently Open • None to report Recently Closed • NP6-584-Security Violations and Binding Transmission Constraints (MIS Secure) • Report name in MIR was incorrect • Actual Name: Security Violations SummaryExpected Name: Security Violations and Binding Transmission Constraints • Affected EDW • NP5-649: Temporarily Removed Contingencies (MIS Secure) • Added column "Reason_for_Removal" to track operator-entered text justification for temporary removal of contingencies. • Affected CDR • Shift Factor Issue #1– • During the August 4th – 5th 24-Hour Test, there were three intervals (1815, 1835 and 1850) wherein shift factors were observed to not be passing to SCED • The fix for this issue was implemented prior to the August 19th – 20th full-system test http://nodal.ercot.com 5

  6. Standing Reports and Updates: General Reminders / Updates Reminders/Updates • Updates to Tracking Artifacts • The Known Issues tracking sheet will refresh overnight to the Readiness center at http://nodal.ercot.com/readiness/markettrials/rtm/index.html • Network Model Update • The network model database was updated on Wednesday 8/18/2010 • The next network model database load will occur Wednesday 9/1/2010 • Update: Outage Scheduler with Zonal Outage Transfer • Purging of test data and Zonal to Nodal Transfer completed the morning of 8/16/2010 as planned at 10:30 AM • TSPs / QSEs should now be working on validating outages effective for September, 2010 and December 1, 2010 and later. • Reminders: • Resource Outages were not transferred by design • Request list of Outages not transferred from MarketTrials@ERCOT.com • Send email to Market MarketTrials@ERCOT.comconfirming outages have been validated by 9/17 for all Outages December and beyond • First production pull of OS data is scheduled for 10/2 for the first CRR Auction http://nodal.ercot.com 6

  7. Standing Reports and Updates: General Reminders / Updates Reminders/Updates • Submissions window extended to 14 days • As of 8/17, the submission window for COPs, Bids/Offers, and Output Schedules has been extended to 14 days.  • This functional change allows MPs to better manage their submission data • 168-Hour Handbook V2.1 Published • Version approved at NATF and TAC • Reviewed with the Board of Directors • Posted at http://nodal.ercot.com/readiness/markettrials/index.html http://nodal.ercot.com 7

  8. Real Time Market / LFC Update 10/14/2014 http://nodal.ercot.com 8

  9. Real Time Market / LFC Update • SCED Week 29 • System Lambda at $2250 offer cap or higher for 373 intervals (compared to 425 last week) • From 8/12 – 8/16, average of 1200MW dispatched away from units where LDL has been set to HDL due to bad telemetry • From 8/17 – 8/18, average is only 300MW, resulting in reasonable prices • Primary cause is actual generation > HSL http://nodal.ercot.com 9

  10. 24 hour test New Garfield_AT1 constraint violated by 11MW in first interval; $3500 SP http://nodal.ercot.com 10

  11. 24 hour test Odessa constraint violated; $2800 SP 22:30 BMRTN to SMOUR activated 23:30 W-to-N activated (constrained all night) http://nodal.ercot.com 11

  12. 24 hour test Price excursion due to 2000 MW over-generation due to bad HSL telemetry 2:20am & 2:45am: AUSSND constraint unresolved by TCM; no SF passed to SCED (known issue) http://nodal.ercot.com 12

  13. State Estimator Convergence http://nodal.ercot.com 13

  14. State Estimator Convergence Update http://nodal.ercot.com 14

  15. State Estimator Convergence Update http://nodal.ercot.com 15

  16. State Estimator Convergence Update Convergence Dips on the 11th and the 13th • These Dips occurred in the morning hours during Ramp Up • Historically, telemetry quality drops during the evening and is corrected during the morning hours • ERCOT shift engineers will begin monitoring more closely during the evening hours and calling MPs to correct issues • This is another preparation step as we near the 168-Hour test and other September activities http://nodal.ercot.com 16

  17. 24-Hour Full-System Market and Reliability Test UpdateStacy Bridges http://nodal.ercot.com 17

  18. 24-Hour Test Update 24- Hour Full-System Market and Reliability Test • Timeline • This week’s 24-Hour Full System Test will conclude at 12:00PM today • Generation is currently switching back to Zonal which started at 11:00AM • Hot Line Call will be made once all generation is switched back to Zonal control • Preliminary results including CPS1 score will be shared at the end of the test • Results will be shared on 8/30/2010 Monday Call with additional details provided on September 3, 2010 Friday call • Any issues to be resolved will be updated on the Monday call • GREDP results to be sent out the week of 8/30/2010 http://nodal.ercot.com 18

  19. General Full-System Market and Reliability Test UpdateStacy Bridges http://nodal.ercot.com 19

  20. General Full System Market and Reliability Test Update 40 - Hour Full-System Market and Reliability Test • Timeline • 08/26/2010 08:00 AM – 10:00 AM Trouble Shooting Period • 08/26/2010 10:00 AM – 11:00 AM Cutover to Nodal • 08/26/2010 11:00 AM – 08/28/2010 01:00 AM – Nodal Control • 08/28/2010 01:00 AM – 02:00 AM Cutback to Zonal Additional Full System Tests Specified in the 168-Hour Handbook • During the 168-Hour Test: 48-Hour Test • Late September – 36-Hour Test • Late October – 24-Hour Test http://nodal.ercot.com 20

  21. Questions Q&A http://nodal.ercot.com 21

  22. Appendix http://nodal.ercot.com 22