330 likes | 502 Views
. Organized Troubleshooting. Have knowledge of how the system should operateKnow the product being refrigeratedMeasure pressures, temperatures, amperages and voltagesInspect the system for obvious problemsDefective components can trigger other problemsIt is rare for more than one component to f
E N D
1.
2. UNIT OBJECTIVES After studying this unit, the reader should be able to
3. Organized Troubleshooting Have knowledge of how the system should operate
Know the product being refrigerated
Measure pressures, temperatures, amperages and voltages
Inspect the system for obvious problems
Defective components can trigger other problems
It is rare for more than one component to fail at any given time
6. Troubleshooting High-Temp Applications Boxes range from 45 to 60 degrees
Coils are 10 to 20 degrees cooler than the box
At the lowest temperature, the coil will be 25F
45F - 20F = 25F
R-134a at 25 degrees is 22 psig
For R-134a, a suction pressure below 22 psig is considered to be low
10. Troubleshooting Medium-Temp Applications Boxes range from 30 to 45 degrees
Coils are 10 to 20 degrees cooler than the box
At the lowest temperature, the coil will be 10F
30F - 20F = 10F, R-134a at 10F is 11.9 psig
During the off cycle, the highest suction pressure will be 40 psig (R-134a, 45F box temperature)
After startup, the pressure will be about 22 psig (45 degrees 20 degrees = 25 degrees)
14. Troubleshooting Low-Temp Applications Low temperature applications start at 5F
Coil temperature is -15F ( 5F - 20F = -15F)
For R-134a, the highest suction is 0 psig at -15F
Lowest suction is 14.7Hg (-20F - 20F = -40F)
With the compressor off at 5F, suction pressure for R-134a is about 9.1 psig
Use the P/T chart to determine pressures for other refrigerants
18. Typical Air-Cooled Condenser Operating Conditions Head pressure controls maintain the desired head pressure, which is about 105F
Most condensers operate with condensing temperatures about 30F higher than ambient
High efficiency condensers can operate with condensing temperatures as low as 10F above ambient temperature
22. Typical Water-Cooled Condenser Operating Conditions Wastewater systems require about 1.5 gpm/ton
Recirculating systems require about 3.0 gpm/ton
Water-regulating valves maintain desired pressure
R-12 system (head pressure of 220 psig, 145F sat. temp)
Leaving water is 95F
Refrigerant is condensing at a temperature 50F higher than the leaving water
Condenser is likely dirty (high temperature differential)
24. Typical Conditions for Recirculating Water Systems Usually do not use water regulating valves
Water enters at 85F and leaves at 95F
Refrigerant normally condenses at a temperature that is 10F higher than the leaving water temp.
Refrigerant normally condenses at about 105F
Cooling tower water can often be cooled to a temperature within 7F of the wet bulb temperature of the ambient air
25. 6 Common System Problems Low refrigerant charge
Excess refrigerant charge
Inefficient evaporator
Inefficient condenser
Restriction in the refrigerant circuit
Inefficient compressor
26. Symptoms of a Low Refrigerant Charge Reduced system capacity
Low head pressure
Low suction pressure (except for AXV systems)
High superheat (Except for TXV systems)
Sight glass will have bubbles in it
Compressor will often run hot
Suction line will be warm
27. Inefficient Evaporator System suction pressure will be low
Evaporator does not absorb heat properly
Caused by dirty or blocked coil, defective evaporator fan motor, defective expansion valve, or recirculating air
Evaporator saturation temperature should be no more than 20F lower than the box temperature
28. Symptoms of a Refrigerant Overcharge High operating pressures (Except AXV systems)
Capillary tube systems may have liquid floodback
Low superheat (Except for TXV systems)
High condenser subcooling
Sweating is a sign that liquid may be entering the compressor
29. Inefficient Condenser High head pressure
Refrigerant cannot desuperheat, condense and subcool refrigerant effectively
Amount of cooling medium (air or water) must be sufficient
Condenser discharge air must not be permitted to recirculate through the coil
30. Refrigerant Flow Restrictions Restrictions can be partial or full
A pressure drop is created at the restriction
Damaged or kinked tubing can cause a restriction
A temperature difference will exist across a liquid line restriction
Freezing moisture in the system can cause a restriction
Improperly set valves or controls can be at fault
31. Inefficient Compressor Electrical problems are relatively easy to diagnose
Evaluating pumping problems are more difficult
Various tests can be performed on the compressor
Compressor Vacuum Test
Closed-Loop Compressor Running Bench Test
Closed-Loop Compressor Running Field Test
Compressor Running Test in the System
32. UNIT SUMMARY When troubleshooting, be organized!
Evaporator coils are typically 10 to 20 degrees cooler than the box temperature
Use the P/T chart to obtain operating temperatures
Head pressure controls maintain desired pressures
Standard efficiency condensers operate at temperatures that are about 30F higher than ambient
Common system problems include overcharge, undercharge, restriction, inefficient compressor, condenser or evaporator