An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Examples of bad installation

  2. CONTENT • Installation related examples • Application related examples

  3. Installation related : Refrigerant pipe work • Mistake : • Saw used instead of cutter • Problem : • Burrs can enter pipe and cause blockage inside the equipment • Improper cutting causes flares to leak • Advise : • Use copper tube cutter

  4. Installation related : Refrigerant pipe work • Refrigerant pipe work • Close tubes during storage.Problem : • Moisture, dust, sand ect.. Can enter tube. • Mistake : • Pipes stored on the ground without seal plugs • Problem : • Moisture, dust, sand ect… can enter the pipe • Pipes can be crushed by stepping onto them • Advise : • Seal the pipes • Store pipes on a stand

  5. Installation related : Refrigerant pipe work • Mistake : • Dirt entered the unit during installation of field piping • Problem : • Filters gets blocked • Advise : • Take special care to avoid dirt entry • Follow vacuum procedure prescribed in installation manual

  6. Installation related : Refrigerant pipe work • Mistake : • Incorrectly positioned refnet • Problem : • Refrigerant noise • Unequal refrigerant distribution causes lack of capacity at some indoors • Advise : • Install refnet according to specification installation manual. OK OK

  7. Installation related : Refrigerant pipe work • Mistake : • Pipe not connected correctly to refnet • Problem : • Refrigerant noise • Unequal refrigerant distribution causes lack of capacity at some indoors • Advise : • Install refnet according to specification installation manual.

  8. Installation related : Drain pipe work • Mistake : • Too small drain pipe • Problem : • Water can not evacuate and drain switch activates • Water leakage can occur • Advise : • Use drain pipe size advised in installation manual

  9. Installation related : Drain pipe work • Mistake : • Drain trap installedwithout cleaning possibility • Problem : • Dust and rubbish accumulates in trap and blocks the pipe • Advise : • Don’t use drain trap • If inevitable, make it as indicated in picture

  10. Installation related : Drain pipe work • Mistake : • Too long distance between suspension points of drain pipe • Problem : • Pipe bends trough and water can not flow out • Advise : • Suspension distance should be 0,8 ~ 1 m • Slope should be 1/100

  11. Installation related : Drain pipe work • Mistake : • Too small pipe size in collective pipe • Problem : • Drain switch activated by water flow obstruction in too small pipe size. • Advise : • Use drain pipe with ID 30 mm or more for collective piping

  12. Installation related : Electrical wiring • Mistake : • Wire tightened over the insulation part • Problem : • Wire overheated • Over current safety activates • Advise : • Fix wires according to drawing on the left

  13. Installation related : Fixation

  14. Installation related : Wrong position of indoor unit FXLQ Floor mounted type It is not just a problem for condensate evacuation. The fan it is not made to work in this position. Risk of damage on medium term

  15. Installation related : Wrong position of indoor unit • Mistake : No free air suction • Problem : Refrigerant can not be evaporated causing capacity Shortage & compressor break-down • Advise : Provide enough room for free air suction

  16. No internal heat load, NORTH side = heating demand Application related : Installation lay-out NORTH • Mistake : • Indoor unit with different demand on one H/P system • Problem : • Too cold in meeting room • Advise : • Use heat-recovery or connect indoor meeting room to system with same operation mode request Meeting room Landscape office High internal heat load = cooling demand SOUTH HEATPUMP OUTDOOR

  17. Application related : Air distribution location grilles Air discharge grille Air suction grille • Mistake : • Wrong location suction/discharge grill • Problem : • Air short - circuit • Advise : • Install grills in the room in such a way to obtain a good air circulation Largest area no direct air circulation

  18. Application related : Air circulation OFFICE • Mistake : • Air suction side does not come from air-conditioned room • Problem : • Can not heat or cool the office enough • Advise : • Air suction should be done from room to be air-conditioned. Air outlet BASEMENT Air suction from basement at 16°C

  19. Application related : Air distribution Air outlet behind couch • Mistake : • Air short circuit • Problem : • Can not heat or cool the room properly • Advise : • Avoid obstruction at air outlet • Separate air outlet from air suction (e.g. suction at floor level, outlet at ceiling level) Air suction

  20. Application related : Air distribution • Mistake : • Ceiling not closed • Problem : • Heating capacity shortage because warm air goes via the gap into the false ceiling • Advise : • Use closed ceiling so that warm air can not escape to ceiling void Gap (open ceiling) Unit installed in panel

  21. Application related : Fresh air connection Branch duct connection • Mistake : • Fresh air connection to branch ductconnection of FXYF • Problem : • Discharge air unit can escape via fresh air ducting • Advise : • Use fresh air kit chamber , “KDDJ55G80-1” and duct-connection, “KDDJ55G80-2”

  22. Application related : Service space • Mistake : • Installation location outdoor create air - recirculation • Problem : • Outdoor temp is 27°C, but at inlet condensor VRV it is 40°C. • Efficiency & life time go down, unit can trip on HP safety • Advise : • Respect installation service space advised by Daikin

  23. Application related : Temperature control • Mistake : • Bad location remote sensor • Problem : • Unit stops although set temperature is not reached • Advise : • Never install remote sensor where discharge air can influence the sensor Remote air sensor influenced by discharge air unit COLD AIR

  24. Application related : Temperature control • Mistake : • No use of remote sensorfor unit with free suction • Problem : • Warm air (cooling) or cold air (heating) from the ceiling void influences the unit sensor • Bad temperature control • Advise : • Install remote sensor when using free suction DUCT UNIT : e.g. FXSQ80M7V1B Air false ceiling enters the unit 28°C Unit sensor Room air 18°C Setpoint 21°C cooling

  25. Application related : Temperature control Problem: Overheating of a small room where temperature control seems to not work. Why? • Indoor units are running in heating mode • 2. Same system airconditions rooms with different load or application. • Example: a perimetral landscape office requires heating while small interior meeting rooms require cooling or at least no heating. 3. The expansion valve is set to a bleeding openning between 150 and 240 pulses, in order to avoid accumulation of refrigerant and oil in the coil

  26. Application related : Temperature control Problem: Overheating of a small room where temperature control seems to not work. Countermeasure: • Install Remote sensor • Disable the Remote controller sensor • Enable the Heating optimization function of the Intelligent Touch Controller: the indoor unit fan is forced off at the thermostat off.