400 likes | 560 Views
10/15/2013 | Westborough, MA. Load Power Factor Audit - 2012/2013 and Area Load Power Factor Standards revised for 2014. Osman Bileya. Lead Engineer, Real Time SUPPORT. Presentation to the Reliability Committee - 2013. Review of the Annual Load Power Factor (LPF) Correction process
E N D
10/15/2013 | Westborough, MA Load Power Factor Audit - 2012/2013and Area Load Power Factor Standards revised for 2014 Osman Bileya Lead Engineer, Real Time SUPPORT
Presentation to the Reliability Committee - 2013 • Review of the Annual Load Power Factor (LPF) Correction process • Review the LPF Survey Results for the 2012/2013 Audit period • Present Updated 2014 LPF Standards for six Areas • Forecast Compliance into the 2014 LPF Audit period
Review of the Annual LPF Correction Program • Eleven LPF Areas are defined in NEPOOL OP17 – Load Power Factor Correction • OP17 and annual LPF audit is managed by the Voltage Task Force (VTF). • Each Area is assessed individually to determine its own reactive needs. • Voltage/Reactive Performance criterion • Net Zero MVAR Interchange criterion
Reasons for Updating LPF Standards • Changes in area voltage/reactive performance due to transmission changes: • New transmission lines • New bulk transformers • Generation Retirement • Changes in generator reactive capability • Additional static or dynamic reactive compensation • Changes in transfer conditions • Load growth since last Area LPF study • Change of Area definition • Revision of “Testing Criteria” assumptions
Annual Load Power Factor Survey • ISO-NE and VTF are responsible for: • Administering the annual LPF survey • Evaluating and reporting results • Requesting remedial action plans from Market Participants • Every year specific historical hours are selected from the previous year • Each load serving Participant ( as defined in OP17) is tasked with submitting LPF data for the selected historical hours • Participant’s surveyed LPFs are compared to the corresponding Area’s LPF Standard for the specified hours • The degree of noncompliance for each Participant is identified in terms of surplus or shortfall of reactive capability • Changes in the underlying networks (i.e. adding caps) can impact compliance with survey requirements
Annual Load Power Factor Survey • The annual LPF Survey Program accomplishes two goals: • Audit Market Participants’ compliance with the current LPF standards • Forecast Market Participants’ compliance with the new standards if the current standards are revised/updated for any of the reasons specified in the previous slide • OP17 program cited by NERC as an Example of Excellence.
2012/2013 Load Power Factor Survey Results • Eighty one participants submitted LPF audit data for six loads points identified by ISO New England: • Spring Light load (9,128 MW) • Summer Intermediate load (21,938 MW) • Summer Peak load (25,880 MW) • Fall Light load (9,246 MW) • Winter Intermediate load (18,753 MW) • Winter Peak load (20,775 MW)
Fully Compliant Participants in the 2012/2013 Audit Period • In the 2012/2013 audit period 33 participants were fully compliant: Boston: NSTAR Central Mass/Harriman : Fitchburg Gas & El, Green Mountain Power, Hudson Connecticut area: Groton Utilities, NU, The United Illuminating Co , Mohegan Tribal Utilities Authority Maine: Bangor Hydro New Hampshire: Littleton, PSNH, Unitil Energy Systems Northeast Mass: Ipswich, Littleton, Mass Electric, Middleton, Peabody, Rowley , RMLD Rhode Island: Narragansett, Pascoag Southeast: Mansfield, Middleboro, Norwood, NSTAR SWCT: NU, South NRWLK Electric & Water, Third Taxing Dist-NRWLK Vermont: CVPS, Granite State Electric (GS WEST), NH Electric Coop, VELCO, Green Mountain Power
Revised Load Power Factor for 2014 • 6 out of the 11 eleven Areas revised LPF Standards for 2014 • Maine • New Hampshire • Northeast Massachusetts • Central Massachusetts / Harriman • Western Massachusetts • Southwest Connecticut
Revised Maine LPF Standard for 2014 The following Maine Power Reliability Program (MPRP) topology upgrades are the reason for the LPF revision for 2014: • 240 MVAR of new reactors, • four new 345/115 kV autotransformers (one replacing the soon to be retired Maxcys T3), • 184 mile long parallel 345 kV aerial transmission path from Orrington to Eliot substation in New Hampshire, • retirement of five special protection systems (SPS), • 100 miles of new 115 kV aerial transmission and various 115 kV transmission improvements
Revised Maine LPF Standard for 2014 Cont’d • The minimum LPF Standards were based on the Net 0-MVAR interchange criterion • Starting with an all lines-in system • Respecting the worst limiting contingency • The maximum LPF Standards were based on high-voltage violation criteria • Starting with a facility out from a light load/high voltage perspective • Respecting the worst limiting contingency
Revised New Hampshire LPF Standard for 2014 • The main reason for this year’s study is the revised “Testing Criteria” for the maximum LPF standards • Facility out as opposed to all lines-in testing during light and shoulder load levels • Only high voltage violations are respected (net 0-MVAR interchange criterion is not respected) • Similar to last year’s study, the following transmission upgrades are included in this year’s study: • the new 345 kV path from New Hampshire to Maine (Elliot to Maguire Road to South Gorham • New Capacitors at Webster and Weare • Up-rate the 326 line to 1780 MVA summer LTE
Revised New Hampshire LPF Standard for 2014 • The minimum LPF Standards were based on the Net 0-MVAR interchange criterion • Starting with an all lines-in system • Respecting the worst limiting contingency • The maximum LPF Standards were based on high-voltage violation criteria • Starting with a facility out from a light load/high voltage perspective • Respecting the worst limiting contingency
Revised Northeast MA LPF Standard for 2014 • The reason for revising NEMA’s LPF standardsis the retirement of Salem Harbor Units 3 & 4 by end of 2014: • Total real power capability is approximately 585 MW • Total lagging/leading reactive power capability is approximately 265 MVAR
Revised Northeast MA LPF Standard for 2014 Cont’d • The minimum LPF Standards were based on the low voltage violation criterion • Starting with an all lines-in system • Respecting the worst limiting contingency • The maximum LPF Standards were based on the high-voltage violation criterion • Starting with a facility out from a light load/high voltage perspective • Respecting the worst limiting contingency
Revised Central MA/Harriman LPF Standard for 2014 Cont’d The following topology upgrades are the reason for the LPF revision for 2014: • Reclosing of A127 and B128 (major change) • Auburn St substation - 2nd 345/115 kV auto transformer (March 2014) • E Main St, Westborough - 2nd 115/13 kV transformer and new in-line breaker (June 2014) • O-15S conversion to 115 kV (Oct 2014)
Revised Central MA / Harriman LPF Standard for 2014 Cont’d • The minimum LPF Standards were based on the Net 0-MVAR interchange criterion • Starting with an all lines-in system • Respecting the worst limiting contingency • The maximum LPF Standards were based on high-voltage violation criteria • Starting with a facility out from a light load/high voltage perspective • Respecting the worst limiting contingency
Revised Western MA LPF Standard for 2014 • The previous LPF standards were evaluated in 2012 and included the Greater Springfield Reliability Project (GSRP) • In addition to the completion of the GSRP project, this year’s study included: • The closing of A127 and B128 (Harriman to Millbury 115 kV) circuits • Addition of the following 115 kV capacitors to the Pittsfield area • 14.4 MVAR Capacitor at Podick • 14.4 MVAR Capacitor at Amherst • 14.4 MVAR Capacitor at Cumberland • Another reason for this year’s study is the revised “Testing Criteria” for the maximum LPF standards • Facility out as opposed to all lines-in testing during light and shoulder load levels • Only high voltage violations are respected (net 0-MVAR interchange criterion is not respected)
Revised Western MA LPF Standard for 2014 Cont’d • The minimum LPF Standards were based on the Net 0-MVAR interchange criterion • Starting with an all lines-in system • Respecting the worst limiting contingency • The maximum LPF Standards were based on high-voltage violation criteria • Starting with a facility out from a light load/high voltage perspective • Respecting the worst limiting contingency
Revised Southwest CT LPF Standard for 2014 The following topology upgrades are the reason for the LPF revision for 2014: • 8300 Line Reconfiguration • East Shore Capacity Upgrade • Union Substation • Addition of Beseck Shunt Reactor • Addition of Stamford – Glenbrook Cable • Addition of South Norwalk Substation • Addition of 345-kV Series Breaker at E. Devon Another reason for this year’s study is the retirement of Norwalk Harbor Units 1 & 2 • Total real power capability is approximately 335 MW • Total Lagging reactive power capability is approximately 100 MVAR • Total Leading reactive power capability is approximately 55 MVAR
Revised Southwest CT LPF Standard for 2014 • The minimum LPF Standards were based on the low voltage violation criterion • Starting with an all lines-in system • Respecting the worst limiting contingency • The maximum LPF Standards were based on high-voltage violation criteria • Starting with a facility out from a light load/high voltage perspective • Respecting the worst limiting contingency
Forecast Compliance • All 11 Areas are compliant (no reactive deficiency) based on the 2014 LPF standards • Note that some Participants within the individual Areas may still be non-compliant, however each area as a whole is compliant.
Improvement in Spring Light load Compliance based on Forecasted LPF Standards