ASHRAE SEMINARRetrofit of Commercial Buildings to Reduce Air Leakage Airtightness Testing of Commercial Buildings David Saum Infiltec Falls Church, VA Airtightness Testing of Commercial Buildings
Where are commercial buildings regularly tested? • In 2002 the UK began testing buildings over 1,000 m2 (10,000 ft2) floor area. • In July 2008 Ireland will begin requiring testing for new a retrofit buildings. • The UK air leakage standard requires shell meet 10m3/h/m2 (0.44 cfm/ft2) @ 50 Pa • Shell is defined as walls, ceiling and floors • How tight is this? 30x50x8 ft house meets standard at 9.4 ACH @ 50 Pa • Test standard developed by ATTMA Airtightness Testing of Commercial Buildings
Tools used for commercial air leakage testing Blower door fans can be stacked but building power is limited. Large mobile fans require trailers and external power sources. Airtightness Testing of Commercial Buildings
Example of a Very Large Building Test: • Building Type: food distribution warehouse • Location: Manchester, UK • Volume: 256,000 m3 (9,000,000 ft3) • Surface: 58,000 m2 (624,000 ft2) • Worst Case Test flow: 142 m3/s (300k cfm) @ 50 Pa to meet 10 m3/s/m2 • Test equipment: Five mobile fans with 60,000 cfm @ 0.2”wc (27 m3/s @ 50 Pa) Airtightness Testing of Commercial Buildings
Exterior of 9,000,000 ft3 Warehouse Airtightness Testing of Commercial Buildings
Trailer Mounted 60,000 cfm Mobile Fan Airtightness Testing of Commercial Buildings
Five 60,000 cfm fans required for worst case test Airtightness Testing of Commercial Buildings
Warehouse depressurized to 50 Pa via truck bays Airtightness Testing of Commercial Buildings
Aligning Fans with Bay Openings Airtightness Testing of Commercial Buildings
Unpacking the 60 Inch Diameter Flex Duct Airtightness Testing of Commercial Buildings
Opening the Gasoline Engine Exhaust Port Airtightness Testing of Commercial Buildings
Fan Connected to Temporary Door Seal Airtightness Testing of Commercial Buildings
Five Fans Depressurizing Building Simultaneously Airtightness Testing of Commercial Buildings
Fan Control Panel Analog and Digital Gauges Airtightness Testing of Commercial Buildings
Recording Fan Data During Test Airtightness Testing of Commercial Buildings
Trailer Mounted Mobile Fan Specifications: • Calibrated Flow: 7-27 m3/s (15k-65k cfm) • Power: 25hp gasoline engine, electric start • Weight: 570 kg (1250 lb) without trailer • Dimensions: 1.8m x 1.8 m x 2.0 m • Gauges: digital, plus analog backup • Fan Blade: 1.37 m (54 inch) diameter • Fuel Container: marine type, external • Electric power: car battery, option • Flex Duct: 4.5 m long, 1.5 m diameter • Fuel: standard unleaded gasoline Airtightness Testing of Commercial Buildings
Future of Commercial Building Testing? • Other EU Countries follow UK and Ireland testing • Increased US testing by ESCOs, government, and proactive building owners • Tougher leakage standards • More Publications of results • Calibration Standards • Tester Certification Airtightness Testing of Commercial Buildings