1 / 24

Node-breaker model

Node-breaker model. January 23 2014 TSS J. Gronquist, S. Kincic. West-wide System Model (WSM) as example of node-breaker model. WECC WSM is a product of the three existing RCO models (RDRC, CMRC, and PNSC) CIM XML formatted Models (RDRC & CMRC) & Areva EMS Netmom (PNSC) were merged

patr
Download Presentation

Node-breaker model

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Node-breaker model January 23 2014 TSS J. Gronquist, S. Kincic

  2. West-wide System Model (WSM) as example of node-breaker model • WECC WSM is a product of the three existing RCO models (RDRC, CMRC, and PNSC) • CIM XML formatted Models (RDRC & CMRC) & Areva EMS Netmom (PNSC) were merged • Merged Model required clean-up: removal of duplicate lines & substations, standardization of basic modeling methodology & naming conventions • Result: West-wide System Model (WSM) Areva EMS Netmom PNRC (Areva) CMRC(ABB) RDRC(GE Harris)

  3. West-wide System Model (WSM) - usage • WECC RC (Peak Reliability) run SE every minute and RTCA every 5 minutes; • Next day operation studies; • Near real time studies as needed; • Used for update for BPA and CAISO SE external model; • Providing access to WECC members to advanced applications; • Post cases in PTI30 and .csv format daily at www.peakrc.com

  4. WSM vs. basecase • Planning Basecase – Cholla 500kV (1-bus:14000)

  5. WSM vs. basecase (bus number) • WSM Model – Cholla 500kV (4-busses)

  6. WSM vs. basecase • WSM Model – Cholla 500kV (4-busses)

  7. WSM vs. basecase • WSM Model – Cholla 500kV (4-busses)

  8. Node-breaker vs. bus-brunch model: • Node-breaker model is more flexible: • It can represent all operating conditions; • Allows more accurate modeling of RASs (SPS) and contingencies; • There is usually no convergence problems; • Can easily be benchmarked against measurements; • Event analysis-SE case is saved automatically; • Corrective switching action; • Needs for more frequent studies-renewable resources ; • Dynamic assessment of SOLs; • Stuck breaker; • Lot of base-cases;

  9. Model Detail • To the right is a redacted detail of what the topology of the 500 kV bus at Grand Coulee • It’s a Breaker and a Half configuration • This would be a single bus in a “planning case”

  10. Planning Case Bus View

  11. Breaker a4 Out for Maintenance • Now what happens when Line A is taken out of service?

  12. Invalid Contingency SimulationsExample 2 Line D isolated from Line B and Line C

  13. PSLF • PSLF to read WSM in node breaker format in V19; • PSLF to match .dyd file to WSM using EMS names;

  14. WSM vs. basecase (WSM in PSLF)

  15. Building node-breaker model • Model Update Process: • WECC RC Modeling Engineers use the Alstom E-terrasource modeling tool to build (RC’s BCCS) • Each modeler works in their own independent workspaces • Allows for parallel modeling - can have different models & projects loaded • Avoids the issue of shared resources • Avoids the risk of “one-corrupts-all” • Avoids the need for close-coordination of work (e.g. when performing validation, model export) • Each modeler begins with the latest Model Authority Set – MAS (most recent model “basecase”) to create their projects • Model Integrator integrates the projects together, validates, and create a new MAS

  16. Modeling in E-terrasource Network ParameterData

  17. Modeling in E-terrasource (GUI) Node ConnectivityData Node 900C Node 900D

  18. Modeling in E-terrasource (GUI) Graphical Modeler

  19. West-wide System Model (WSM) • Model Export Formats: • PTI Raw File Format • Mapping done via Alstom Translation Table Mapping, manually maintained by WECC RC Modeling Staff • Alstom Netmom Savecase • CIM version 12 • Powerworld CSV File Format ** WSM is available to signatories of the WSM License Agreement or the Universal NDA

  20. Continuous Model Validation • Running state estimation once every minute results in continuous model validation; • Comparing measurements (kV, MW, MVARs) to powerflow solution; • Peak Reliability has 24x7 monitoring support of the State Estimator solution quality;

  21. Model Validation-Dynamic • System event: Arlington plant trip and loss of Palo Verde unit on 04/07/2012 • Differences: • Some difference in in initial conditions; • Differences in power flow data; • No plant load in WSM; • Not all units are matched in .dyd file; • Composite load model used with base-case; • WSM in TSAT and base-case in PSLF;

  22. Progress update: dynamic

  23. Progress update: dynamic

  24. Questions?