An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. PX15 Thermosyphon tests results #02 Jose Botelho Direito EN/CV/PJ

  2. Chiller Power • Lauda RP 3090 CWVs. Julabo WP91-SL The Julabo Chiller was providing less than half of the announced power! (sent to repair) jbotelho@cern.ch

  3. Start-up time • Minimum required flow is 25g/s; • Required chiller power to run at -20°C: • P=m.dh=0.025*(309-192)=2.93 kW • dP=143W left to sub-cool the C3F8 in the tank plus the C6F14 in the chiller bath! ( 380kg of C3F8 + 25 kg of C6F14). • It means 47 minutes to cool the liquid C3F8 by one K! • With one extra kW on the chiller (like the Julabo in good conditions) it would take 6 minutes... Lowest evaporation temperature achieved with the Lauda Chiller: -5 °C jbotelho@cern.ch

  4. Expansion valve Flow instabilities Before Dead band settings on the valve actuator changed from 0.8 to 0.1%. Thanks to S. Berry & F. Corbaz After 4 hours jbotelho@cern.ch

  5. Leak on a pressure manometer (bottom) Valve closed to stop the leak ~40 kg Weight trend since first fill until the leak was repaired jbotelho@cern.ch

  6. New Monitored Conditions and Parameters By L. Zwalinski jbotelho@cern.ch

  7. TS Stop origins: Liquid line boiling Stop! Stop! dP = -0.92 bar dP = -0.92 bar jbotelho@cern.ch

  8. TS Stop causes: Liquid boiling inside the Condenser Stop! dT < 0 °C dP = -0.8 bar Stop! dT < 0 °C dP = -1.32 bar jbotelho@cern.ch

  9. Water hammer – pressure peak of 24 bar Pressure Tliq = 0 °C Weight Pressure decrease at the top! Dead bands to be reviewed! jbotelho@cern.ch

  10. Conclusions for the FSTS • Expected “water hammer” pressure peak to be estimated case it happens on the FSTS; • FSTS “water hammer” protection: • Mechanically (ideal) – Shock absorber every x meters on the liquid line? • Control system: valve at the top of the liquid line closure when expected liquid column is bellow a certain value. • Case the liquid column is too low this valve needs to open slowly. • Start-up time and other time constants to be estimated. jbotelho@cern.ch