1 / 27

Cooling Strategies for Small IT Rooms

Cooling Strategies for Small IT Rooms. Presented by Jim Magallanes TechniCool Innovations Inc. jim@CRuptime.com. 1811 Upham Street Suite B-1, Broomfield CO 80020 303-908-8043 Phone / 888-883-8353 Fax www.CRuptime.com. Outline. Small IT Rooms Electronic Equipment Trends Cooling Load

pegeen
Download Presentation

Cooling Strategies for Small IT Rooms

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Cooling Strategies for Small IT Rooms Presented by Jim MagallanesTechniCool Innovations Inc. jim@CRuptime.com 1811 Upham Street Suite B-1, Broomfield CO 80020303-908-8043 Phone / 888-883-8353 Faxwww.CRuptime.com

  2. Outline • Small IT Rooms • Electronic Equipment Trends • Cooling Load • Best Cooling Practices • Cooling Solutions • Portable Systems • Mini Split Systems • A/C Computer Cabinet Systems • A/C Ceiling Systems • Precision Ceiling Systems • Conclusion Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  3. Small IT Rooms • Data Centers & Large Computer Rooms • Always include a dedicated cooling system • Small IT Rooms • Many IT devices are located outside computer room • Closets /Branch Offices / Storage Rooms / Open Offices • Never designed for cooling IT equipment • Power density of IT equipment has increased over time • Servers / Telecom / VOIP Routers & Switches / UPS • Floor Space is a Premium: <100 ft2 • Contents: 1 – 3 Equipment Racks • Heat Load per Rack: 1.0 - 2.0 kW Avg. • Typical Cooling: None or Building Cooling During Day • Remote location of building • Security: Medium • Locked Door and/or Locked Cabinet • “The average wiring closet contains $150,000 - $300,000 of equipment and a typical small server room often houses more than three times that amount.” - Mitch Medford, NetBotz CTO Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  4. Small IT Rooms • Approach to cooling small IT Rooms • Ignore cooling requirement • Deploy equipment … deploy more equipment • Call CTM frantically when IT equipment overheats and/or fails • Average small IT room can contain up to several hundred thousand dollars of equipment • Network down results in more than IT replacement cost • Lost sales / productivity / equipment / data • Cooling Strategy • Requires proactive approach ensuring the uptime availability of your IT network • Cooling Strategies for Small IT Rooms • Basic cooling principals for small IT rooms • Available cooling options Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  5. Electronic Equipment Trends • Power = Heat • Servers • Blade Servers • Smaller & More Powerful • IP & VOIP Telecom Equip • High-powered switches and equipment • Low-powered legacy • Requires UPS support • Overheated IT equipment • Reduced Life / Hardware Damage • Reduced Reliability • Slower Network • Costly System Downtime • General Rule • Every 10°C temperature rise in nominal temperatures produces a 50% reduction in the lifetime and long-term reliability of IT hardware- MIL-HDBK 217 / Arrhenius Models Figure: Product Heat Density Chart(The Uptime Institute) Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  6. Electronic Equipment Trends • Power = Heat • Servers • Blade Servers • Smaller & More Powerful • IP & VOIP Telecom Equip • High-powered switches and equipment • Low-powered legacy • Requires UPS support • Overheated IT equipment • Reduced Life / Hardware Damage • Reduced Reliability • Slower Network • Costly System Downtime • General Rule • Every 10°C temperature rise in nominal temperatures produces a 50% reduction in the lifetime and long-term reliability of IT hardware- MIL-HDBK 217 / Arrhenius Models Figure: Product Heat Density Chart(The Uptime Institute) Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  7. Heat Problem for Small IT Rooms • Businesses dependent on computers and telecom equipment for day-to-day operations • Need to keep IT equipment cool • ASHRAE Technical Committee 9.9 • Thermal Guidelines • Inlet Temperatures • Costly to rely on building A/C • Data Centers • Upper range temperatures acceptable • Tight controls/monitoring • Redundancy • Small IT Rooms • Temperatures in the 60Fs to lower 70Fs (18 – 22 C) are practical • Looser controls/monitoring • No redundancy • Extend UPS Battery life by 3 times with lower temperatures: 5 years • Supplement building cooling • After business hours/weekends/holidays • Cold-weather months when central system is in heating mode 18 C 27 C ASHRAE – Thermal Guidelines for Data Processing Environments Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  8. Cooling Load • Determining the cooling load in a wiring closet • Incremental load from equipment • Nameplate rating • Usually overstated • ASHRAE TC 9.9: Load during operating conditions • Not yet adopted by manufacturers • Determine cooling load from UPS load • Load from all equipment connected to the UPS • Dependent on day and time • Monitor over a period time to get worst case scenario • Other sources of heat • Lights/windows/outside wall/etc… • Room Dimension: Temp Increases as Room Decreases • Ability to dissipate heat • Electrical power to rejected heat conversion • 1 kW = 3,413 Btu/hr. • 12,000 Btu/hr = 1 ton of A/C Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  9. Cooling Solutions & Best Cooling Practices • Cooling Solutions • Primary cooling for IT equipment • Small IT room is not air conditioned • Nights & Weekends when building a/c is off • Shut down building a/c when people are not in the building • Supplemental Cooling • Added denser IT equipment • Seasonal: Summer or Winter • Redundancy / Emergency backup to primary cooling • Planned or unplanned shut downs: Inexpensive insurance plan • Best Practices • Spot Cool vs. Traditional A/C • Managing Air Movement • Direct cold air to front of server: Airflow = Front to Back • Do not cool down the entire room • Back of the rack: Up to 36°F Hotter • Cold Aisle / Hot Aisle • Use blanking panels for unoccupied rack space • Organize cabling • Maximize airflow Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  10. Cooling Solutions – Portable Systems • Portable Systems • A self contained packaged air conditioner that is on wheels and is easily movable to spot cool “hot spots” • Power: 115 VAC, 230 VAC, & 460 VAC • Heat rejection: Ceiling plenum • Air or water cooled • Condensation removal • Tank: Emptying depends on humidity • Pump: Drain/sink/water line • End-user Installation • Connect accessories (15 – 20 minutes) • Non-standard applications may require contractor • Cooling Capacity • 1 – 5 Ton units available Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  11. Cooling Solutions – Portable Systems • Portable system features • Wide cooling capacity range • Voltage: 115V, 230V, or 460V • Approx. 1.5 Tons at 115V • Condensation removal • Tank: Empty periodically • Pump to drain/sink/water line • Operational features • Automatic Restart • Air delivery • Grille or nozzle • Ducting Capabilities • Exhaust • Long ducting runs • Return/Make-up Air Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  12. Cooling Solutions – Portable Systems • Pros • Low cost • Relocate unit from room to room • Moves with tenant • Little installation required • No outdoor equipment • Cons • Floor space required • Small heat load on building’s A/C • Typically not a problem • Condensate removal • Tank or pump • No Humidity Controls Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  13. Cooling Solutions – Mini Split Systems • Mini Split Systems • Consists of 2 units connected by refrigerant lines • Indoor Unit – Inside the wiring closet • Discharges cold air • Refrigerant lines • Transfers heat to the outdoor unit • Outdoor Unit – Outside the building • Discharges hot air to the environment • Designed for comfort cooling • High latent cooling • Removes moisture from air • Contractor Installation • Mounting/electrical/refrigerant lines/condensate line • System comes with pre-charged refrigerant lines • Cooling Capacity • 1 – 3 Ton units available Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  14. Refrigerant Lines Indoor Unit 70 FT 25 FT Outdoor Unit Cooling Solutions – Mini Split Systems Installation Guidelines Wiring Closet Outside Building Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  15. Cooling Solutions – Mini Split Systems • Pros • Low cost • No floor space required • No affect on building’s A/C system • Cons • Location Restrictions • Maximum height difference: 25 Ft • Maximum piping length: 70 Ft • Landlord Approval • Leasehold improvement • No Humidity Controls • Reliability • Possible leaks at quick-connect • Condensate removal • Does not work in extreme low temperatures Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  16. Cooling Solutions – A/C Computer Cabinet • Air Conditioned Computer Cabinet • A standard 19” computer cabinet housing a self contained packaged air conditioner • Power: 115 VAC and 230 VAC • Heat rejection: Ceiling plenum • Condensation removal • Pump: Drain/sink/water line • Evaporative: Exhausts condensationin warm condenser air • Delivers data center infrastructure to LAN room/wiring closet • End-user Installation • Connect accessories (20 – 30 minutes) • Cooling capacity per computer cabinet • ½ - 1 Ton units available Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  17. Cooling Solutions – A/C Computer Cabinet • A/C Computer Cabinet Features • Cooling capacity to match IT load • Voltage: 115V or 230V • Airflow Pattern • Most IT Equipment: Front to Back • Air conditioner Location • Bottom of cabinet to prevent water leak • Condensation Removal • Pump to drain/sink/water line • Evaporate in exhaust: Poor IAQ • Backup Cooling • Backup UPS for cooling • Fresh outside air • Automatic Restart • Environmental Monitoring Airflow Pattern Front to Back Airflow Pattern: Side to Side Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  18. Cooling Solutions – A/C Computer Cabinet • Pros • Low cost • Relocate unit from room to room • Used in open office environments • Moves with tenant • Little installation required • No outdoor equipment • Efficient cooling • Brings cooling directly to IT heat source: Cold Aisle / Hot Aisle • Delivers data center infrastructure to wiring closet • Cons • Small heat load on building’s A/C • Typically not a problem • Manufacturer specific cabinet • No Humidity controls • Condensation removal Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  19. Cooling Solutions – A/C Ceiling Systems • A/C Ceiling Systems • Packaged air conditioner that fits above the drop ceiling plenum that only has A/C capabilities. • Packaged system • Air Cooled • Water-cooled • Contractor Installation • Minimal labor • Unit comes pre-charged with refrigerant • Cooling Capacity • 1 – 5 Ton units available Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  20. Cooling Solutions – A/C Ceiling Systems • A/C Ceiling System Features • Cooling capacity: 1 – 5 Tons • Voltage: 115V or 230V • Condensation removal • Pump to drain / sink/ water line • Gravity drain • Air delivery • Supply air ducting • Exhaust air ducting • Return air ducting • Optional Features • Automatic restart • BMS compatibility Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  21. Cooling Solutions – A/C Ceiling Systems • Pros • Configurable • Air-cooled or water-cooled • No floor space required • Low profile fits most ceiling plenums • Ducting capabilities • Cold supply air • Exhaust air • Cons • Contractor installed • Landlord Approval • Leasehold improvement • No humidity controls • Small heat load on building’s A/C • Typically not a problem Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  22. Cooling Solutions – Precision Ceiling Systems • Precision Ceiling Systems • A precision ceiling system is an air conditioner that fits above the drop ceiling plenum that has humidity and reheat capabilities. • Engineered system for specific applications • Packaged or split systems • Packaged: (1) component inside building • Split: Components inside and outside building • Air-cooled/water-cooled/chilled water-cooled systems • Contractor Installation • Copper piping/electrical/mounting/condensate line • Charges with refrigerant on-site • Cooling Capacity • 1 – 8 Ton units available Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  23. Cooling Solutions – Precision Ceiling Systems • Precision ceiling features • Wide cooling capacity range • Voltage: 115V, 230V, or 460V • Condensation removal • Pump to drain/sink/water line • Gravity drain • Operational features • Automatic Restart • Air delivery • Grille Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  24. Cooling Solutions – Precision Ceiling Systems • Pros • Highly configurable • Packaged or Split • Air-cooled/Water-cooled/chilled water-cooled • No floor space required • Multiple Options • Humidity controls/alarms/etc… • Cons • Very high cost • May require outdoor heat rejection equipment • Plenum space above ceiling is limited • Air Delivery is fixed location • Landlord Approval • Leasehold improvement • Engineered for application • Contractor installed: Expensive Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  25. Cooling Solutions – Comparison Chart Cost / Adaptable Ideal Wiring Closet Comments • Cost effective solution • Little installation required • Moves with tenant • Air or water cooled • Loads: 1 – 5 Tons • Requires floor space • Works with any building • Ideal for backup cooling PortableSystems Low / Flexible • Comfort cooling design • Cost effective solution • Leasehold improvement Low / Specific Buildings • Loads: 0 – 3 Tons • Close proximity to outside • No floor space Mini SplitSystems • Loads: .5 – 1 Ton/cabinet • No floor space required • Works with any building • Optional alarm/Mini DC • Cost effective solution • Efficient cooling system • Little installation required • Moves with tenant A/C Computer Cabinet Moderate / Flexible A/C CeilingSystems • Air or water cooled • Cost effective solution • Leasehold improvement • Loads: 1 – 5 Tons • Low height in plenum • No floor space Moderate / Flexible Precision Ceiling Systems • Better ROI > 3 Tons • Site monitoring system • Leasehold improvement • Loads: 1 – 8 Tons • No Floor space • Alarms needed High / Flexible Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  26. Cooling Strategies Conclusion • Small IT Room • Dedicated A/C system • Electronic equipment benefits • Increased life/reliability/server speed • Improve security with locked door • Selecting a cooling solution • Building structure • Budget • Closet requirements • Floor space • Location within building • Available power • Own/Leasehold improvement • Insurance Policy – Mission Critical IT Network • Redundant cooling solution for shut-downs (planned/unplanned) Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

  27. Cooling Strategies for Small IT Rooms • Questions www.CRuptime.comjim@CRuptime.com303-908-8043 Phone Cooling Strategies for Small IT Rooms – CTM 2013 Operations Seminar

More Related