1 / 19

EE212 Passive AC Circuits

EE212 Passive AC Circuits. Lecture Notes 5 Three Phase Systems. Balanced 3-Phase Systems. Example: A balanced 3-phase, line-to-line voltage of 220 V is applied to a balanced 3-phase load. The 3-phase load consists of 3 identical loads (each with an impedance of 6+j8  ) (a) connected in Y

primo
Download Presentation

EE212 Passive AC Circuits

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. EE212 Passive AC Circuits Lecture Notes 5 Three Phase Systems

  2. Balanced 3-Phase Systems Example: A balanced 3-phase, line-to-line voltage of 220 V is applied to a balanced 3-phase load. The 3-phase load consists of 3 identical loads (each with an impedance of 6+j8 ) (a) connected in Y (b) connected in D Calculate the line current and the total power consumed for both cases. Draw the complete phasor diagrams for each case.

  3. Balanced 3-Phase Systems A 3-phase load in D-connection consumes 3 times more power than in Y- connection. A 3-phase load in D-connection draws 3 times more current than in Y- connection. Y-D motor starting method to reduce starting current

  4. Zab A B Za B A Zb Zca Zbc Zc C C Delta-Wye (D-Y) Transformation (product of adjacent ZD) ZY = sum of all 3 ZD Za = (Zab. Zca) / (Zab + Zbc + Zca) Zb = (Zab. Zbc) / (Zab + Zbc + Zca) Zc = (Zca. Zbc) / (Zab + Zbc + Zca) For balanced load, Zab = Zbc = Zca = ZD Therefore, ZY = ZD / 3

  5. A B Za B A Zb Zc C C (product of ZY taken in pairs) ZD = the opposite ZY Wye-Delta (Y- D) Transformation Zab Zbc Zca Zab = (Za.Zb + Zb.Zc + Zc. Za) / Zc Zbc = (Za.Zb + Zb.Zc + Zc. Za) / Za Zca = (Za.Zb + Zb.Zc + Zc. Za) / Zb For balanced load, Za = Zb = Zc = ZY Therefore, ZD = 3.ZY

  6. ZL B b a A ZB ZL ~ ZA n N ZC ~ ZL c C Balanced Y load Balanced Y source Line impedance ~ ZL Ip = IL A a Vp ZA ~a n N Balanced 3-f Source and Load Y-Y System: Per phase equivalent circuit:

  7. ZL Ia IAB b a A B ZL Z ~a n Z Z ~a ZL c C ~a Balanced 3-f Source and Load Y-D System:

  8. ZL Ia IAB b a A B ZL Z ~a n Z Z ~a ZL c C ~a ~a ZL Ia A b a Z/3 ZL IAN B ~a Z/3 n N Z/3 ~a ZL c C Y-D System: Convert D load to Y load, Per phase equivalent circuit:

  9. 10+j5  Ia IAB b a A B ~ ~ n Vp = 110 V 75+j225  ~a c C Example: In a balanced Y-D 3-f circuit, the Y-connected source has a Vp = 110 V. Line impedance between the source and the load is ZL = (10 + j5) per phase. Per phase impedance of the D-connected load is ZD = (75 + j225) . Determine the phase currents in the D-connected load.

  10. 10+j5  Ia IAB b a A B ~ ~ n Vp = 110 V 75+j225  ~a c C 10+j5  Ia b A a IAN B ~ ~ n N Vp = 110 V (75+j225)/3  ~a c C Convert D load to Y load, Per phase equivalent circuit:

  11. a b A2 A1 B2 B1 Z1 Z2 Z1 N Z2 Z2 Z1 C2 c C1 Multiple Balanced Loads in 3-f Systems A number of balanced 3-f loads are connected in parallel. Such systems can be evaluated using different methods: • Convert all loads to Y, and parallel the impedances • Convert all loads to D, and parallel the Z’s • Combine the per phase powers

  12. Multiple Balanced Loads in 3-f Systems Example: A 3-f, Y-connected motor takes 10 kVA at 0.6 p.f. lagging from a source of 220 volts line-to-line. The motor is in parallel with a balanced D load having 16- resistance and 12- capacitive reactance in series in each phase. Find the total P, line current and p.f. of the combined load.

  13. Example: Unbalanced 3-f Load A 3-phase unbalanced load shown below is energized by a balanced 3-phase voltage with 208 volts line-to-line, and phase sequence a-b-c. Determine the total real power delivered to the load. a + 10  208 V 10  -j10  _ b + 208 V _ c

  14. Example: Unbalanced 3-f Load Loop Analysis: I1 Vbc = 208/-1200 V a + I2 10  Vab = 208/00 V 10  -j10  _ b + _ c

  15. Example: Unbalanced 3-f Load Ia → Nodal Analysis at node n: n Ib → Vbc = 208/-1200 V The voltage at node n is taken with respect to the neutral node at the source. That is, VnN Ic → a + 10  Vab = 208/00 V 10  -j10  _ b + _ c

  16. Watt-meter cc cc I I + + vc + vc Single phase load Power factor cos + V V Watt-meter Connection in Single Phase System Most watt-meters have CC and VC tap settings such that they can be operated close to the rated values (or at high loads) CC: 0 impedance VC:∞ impedance Power measured by a watt-meter is

  17. + Ia Vcb + A Ic P1 Vca Vcn Vab a b q2 Zb q1 Za 300 B Van q n Ia Ib Zc Vbn + P2 Ic Vbc c C + Watt-meter Connection in 3-f (3-wire) System • Q3f = 3 (P2 – P1) • P3f = P1+ P2 P1 = |Vab|.|Ia|.cos 1where 1= angle between Vab and Ia= 300-  P2 = |Vcb|.|Ic|.cos 2where 2= angle between Vcb and Ic= -300-  2-Wattmeter Method (connected line – line) p.f. angle,  = angle between Vph and Iph = angle between Van and Ia (or Vcn and Ic) P1 + P2 = VL.IL [cos (300- ) + cos (-300- )] =VL.IL [2 cos 300 cos ] = 3.|VL|.|IL|.cos 

  18. + + Pa Ia a A B Ib b N n Ic C c Watt-meter Connection in 3-f Balanced System When neutral point is accessible (3-f, 3-wire system) • Three phase power = 3 xPa

  19. + + Ia A P1 a b Z VL = 220 V B Z = 10/450 n Z + P2 Ic c C + Example A balanced Y load having per phase impedance of 10 /450, is supplied by a 3-f source with a line-to-line voltage of 220 V. Two-wattmeter method is used to measure the power delivered to the load. Determine the reading on each wattmeter, and find the real & reactive power from the wattmeter readings.

More Related