1 / 18

Inspecting Electrical

Inspecting Electrical. Inspection Includes:. Service entrance & masthead Main panel and subpanels (if any) Branch circuit wiring Junction boxes, outlets & fixtures. National Electric Code. Governs all electrical installations for both commercial and residential

reese-morse
Download Presentation

Inspecting Electrical

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Inspecting Electrical

  2. Inspection Includes: • Service entrance & masthead • Main panel and subpanels (if any) • Branch circuit wiring • Junction boxes, outlets & fixtures

  3. National Electric Code • Governs all electrical installations for both commercial and residential • NEC does NOT require updating to older homes with new code revisions • The MOST important aspect of the electrical inspection is to be on alert for SAFETY HAZARDS

  4. Required to Inspect • Service entrance • Main distribution panel • Branch circuit wiring • GFCIs within 6 ft of interior plumbing fixtures • Polarity & grounding of representative number of interior receptacles and ALL carport receptacles

  5. Not Required to Inspect • Low voltage systems • Telephone, security, cable TV, intercoms or other ancillary wiring DO NOT: • Insert tool, probe or testing device inside panel • Test or operate overcurrent devices except GFCIs • Dismantle any electrical device or control other than to remove main panel cover

  6. Inspecting Service Entrance • Service entrance • Overhead or underground • Secure attachment to house • Copper, aluminum, or copper-clad aluminum • Amperage 60A (round meter base), 100A (square meter base), or 200A (rectangular meter base) • By today's standards, 100-amp service is considered minimal service.

  7. Typical Service Entrance Wiring

  8. If service comes in below roof level, it must be at least 3’ from windows If service comes in above roof level, it must be at least 3’ above roof Service wires must: Be 12’ above driveways At least 10’ above ground At least 8’ above a flat roof & 18” above roof ridges Service Drop & Masthead

  9. Voltage Rating • Service drops: • Number of wires going to masthead indicates voltage • Three wires with one tied back & two entering = 120 V • Three wires entering = 240V

  10. Service Panel • Check box for heat. • Don’t open of warm..cause for immediate concern. • If OK remove cover: • Inspect for any “tapping before the main” …SAFETY HAZARD • If no main disconnect, must be able to power down in six hand movements • Inspect for properly sized wires to properly sized breakers or fuses

  11. Wiring to Branch Circuits & Breakers

  12. Service Panel Inspection Overview • Look for signs of corrosion outside and at interior connections • Look for circuit breakers that have more than one conductor attached • (Double or triple tapping is normally prohibited)

  13. Double Tapping Breaker

  14. Service Panel Inspection • Check for loose or unattached conductors • Check wires for signs of arcing, charred metal or burnt wire insulation • Evaluate cables entering box for proper protection and fastening

  15. Main Service Panel Inspection • Report wires smaller than #8 (fire hazard) • Clearance around panel should be: • 6-6” headroom • 30” all around • 36” clear in front

  16. Grounding Conductor • Grounding releases unwanted electricity to “ground” (earth) • Ground wire must come from the neutral to the plumbing system or to a steel rod driven into earth. (Both reqd since 1987) • Check for continuity of plumbing and dielectric connectors!

  17. Common Defects To Report: Recommend an Electrician Be Called • Double tapped circuits • Broken or cracked fixtures or outlets • Melted insulation • Handyman wiring • Loose ceiling fans • Permanently installed extension cords & temporary wiring • Missing or inoperable GFCIs • Oversized breakers & fuses

  18. Safety Hazards: Report & Recommend An Electrician Be Called • Masthead within reach of occupants • Frayed entrance cable • Tapping before main • Oversized fuses or breakers • System not grounded • More than 6 hand movements to power down

More Related