Advanced PD Monitoring of Power Transformers Supporting Asset Management Gregor Pudlo Doble Lemke Germany Switzerland www.ldic.de
Abstract • Reasons for (PD) monitoring of transformers • Partial Discharge Detection principles • Electrical PD diagnostic techniques • PD measuring circuits according to IEC 60270 • Advanced tools for PD monitoring • Acoustic and electromagnetic PD measuring principle • Cone-shaped drain valve UHF-sensors / Performance Check • Case studies – UHF PD measurements
Reasons: PD Monitoring of Power Transformers • Power transformers are the most important and expensive pieces of equipment in substations. • A new power transformer costs millions of dollars. • Unplanned outage and repair costs, penalties, etc. sum up • Transformers design life is 20-35 years. • With proper maintenance they can remain in service for 60 years. • As transformers age, their internal conditions degrade which increases the risk of failures. • Time-based maintenance changes to condition-based maintenance approaches
Optical Effects(Light) Optical Acoustic HV Pressure Wave(Sound) Mechanical Opto-acoustic Discharge EffectsDielectric LossesHigh Frequency Waves Electrical IEC 60270 HF/VHF/UHF Chemical Effects Chemical Draft IEC 62 478 Heat Partial Discharge Detection Principles Macroscopic-Physical Effects Detection Methods
Electrical PD diagnostic techniques PD measuring circuits according to IEC 60270 often applied in on-site/on-line PD investigations frequently used circuit in test laboratories [König, 1993] a) coupling device in series with the coupling capacitor b) measurement at a bushing tap Components:AC voltage source U, optional blocking impedance Z, coupling capacitor CK, measuring impedance Zm, a measuring instrument M and generalized test object Ca.
Electrical PD diagnostic techniques PD Measuring Impedance for Bushing Tap Installation • Decoupling of PD signals from the bushing tap • in a wide frequency range up to 30 MHz • Lower cut-off frequency < 60 kHz • Additional voltage signal for phase-resolved measurements • Superimposed PD and test voltage signal • Very fast and safe over-voltage protection • TNC-socket for signal output • Dimensions: diameter 125 mm, length 120 mm; Weight: 2 kg • Special feature for continuous PD monitoring (IP 68) 500 kV Transformer Bushing
IEC 62478 - Draft level • "Non-conventional PD-measurements“: • Electromagnetic PD Detection in the (HF/VHF/UHF) - range • Acoustic PD measurements • Mixed acoustic and electromagnetic method -> PD location in Power Transformers and Reactors
Advanced tools for PD monitoring – Electromagn. PD Tests Cone-shaped active drain valve UHF-sensors • for the decoupling of electromagnetic PD signals from the inner of an oil-paper-insulated transformer • PD-signals in the UHF frequency range (mainly 300 MHz – 1 GHz) • sensors support „Performance/Sensitivity Check“ (high-frequency test impulses can be injected with additionally integrated electrode) • sensor head is grounded (for lower frequencies) • sensor application at oil valves, which are available e.g. for oil filling or draining (liquid tightness is tested for 120°C warm oil with 5 bar compression) View from inside the transformer
Performance Check output path input path Cone-shaped active UHF-sensor (DN 50/80 oil gate-valve) UHF PD spectra for grounded and ungrounded sensor head • Functional check of the whole measuring path including sensors and partial discharge (PD) acquisition system through injection of high-frequency test impulses • „single-port“ solutions are possible • the Performance Check „controls“ e.g. the effect of a contact to grounded elements within the oil valve.
Drain valve Output Pre-amplifier UHF PD probe DN80 High-pass filter Input Transformer Performance Check Performance check at 750 MHz Phase-resolved view in UHF PD device LDS-6/UHF
Applicationbenefit: • customer wanted to verify the hydrogen measurements and locate potential PD • full in-service sensor application and measurement • UHF PD signal could be used to enhance acoustic PD measurements Advanced tools for PD monitoring – Electromagn. PD Tests Case study B -on-line UHF PD measur. of a 200 MVA single-phase transformer 380/220kV, 200 MVA single-phase transformer and position of the gate-valve UHF-sensor UHF pulse recorded on-line corresponding UHF PD spectrum up to 1.5 GHz
Applicationbenefit: • gas-in-oil hydrogen indication „useless“ due to active hot spot • customer wanted to test for PD and check a potential load dependency of PD • full in-service sensor application and measurement • Inception and extinction voltage could be identified, load dependency excluded Advanced tools for PD monitoring – Electromagn. PD Tests Case study C -on-line UHF PD measur. of a 3-phase power transformer 600 MVA gate-valve UHF-sensor used at the 3-phase power transformer 600 MVA, 21/380kV UHF pulse recorded on-line corresponding UHF PD spectrum up to 1.0 GHz
UHF PD Measurements and delivered UHF PD Probe DN50/80 Taiwan Taipeh China Shangai Belgium Linkebeek Germany Berlin Heidenau Riesa Ireland & UK Ardnacrusha Cashla Dublin Louth Philippines Manila Saudi Arabia Jeddah Jizan UAE Dubai Egypt Kairo Colombia Bogota
UHF PD measurements in Ireland • Locations: • Louth • Dublin • Ardnacrusha • Cashla • Application benefit: • Tested measurements have been performed using non-conventional decoupling methods taking advantage of electromagnetic field coupling • PD measurements on the power transformers have been functioned on the drain valves of the 3- phase 110/225kV power transformers with the help of the UHF probe DN 50 • Three transformers found with minor PD activity, one transformer with clear PD
UHF PD measurements in Ireland • Measuring Instrument: • PD Measuring System LDS-6/UHF • UHF Probe DN50 (with Adapter DN50/DN80) • UHF Calibrator LDC-6/UHF • Pre Amplifier LDA-5/GIS Measuring System LDS-6/UHF Mounting of the UHF Probe DN50 (with Adapter DN50/DN80)
UHF PD measurement in Louth, Dublin, Ardnacrusha, Cashla (Ireland) Louth The measurements on both valves showed PD activity from inside the transformer. T2xxx Not any critical PD levels above the detection sensitivity have been measured in Dublin, Ardnacrusha and Cashla.
UHF PD measurements in Jizan, Saudi Arabia on 33/13,8 KV Power Transformers “A” and “B” • Measuring Instrument: • UHF Probe DN50 • Calibrator LDC-6/UHF • PD measurement instrument LDS-6/UHF Power Transformer
UHF PD measurements in Jizan, Saudi Arabia “A” “B” Not any critical PD levels above the detection sensitivity have been measured. • Application benefit: • For examination and diagnostics of the insulation quality of high voltage apparatus the measurement of PD is accomplished by sensitive UHF method on-site • UHF probe applied in full operation of transformer, no outage needed
Conclusion • sensitive UHF PD measurement with UHF probes applicable in service provide advantageous robust and easy PD decoupling • PD location - especially in transformers of great importance - is possible in mixed and all-acoustic way • significant diagnostic information are derived from advanced tools for PD monitoring • valuable application benefits e.g. on-line quick start of PD monitoring, enabling time-based maintenance, “diagnostic double checks”, etc. are at hand Doble Lemke GmbH Kesselsdorf/Dresden,Germany Tel.: +49 35204 3900 0 www.ldic.de Doble Lemke AG Rheinfelden, Switzerland Tel.: +41 61 836 8000 www.ldic.ch