400 likes | 729 Views
SFT 2841 IN CONNECTED MODE. Prepare setting files. Click on the icon. Select the working language Choose the operating mode: connected point to point via the front panel via the network. Starting the application. Same access for SFT disconnected. Connection via the network.
E N D
SFT 2841 IN CONNECTED MODE Prepare setting files
Click on the icon Select the working language Choose the operating mode: connected point to point via the front panel via the network Starting the application Same access for SFT disconnected
Connection via the network • Choice of the network • If required: creation or modification of the network • Connection to Sepam units via the network • Starting of SFT 2841 software on the chosen station
SFT 2841 expert UMI • The protection and parameter setting data may be saved. • Reports may be edited.
PARAMETER SETTING Parameter setting
Current operation • Metering and operating data • alarm messages • tripping current • number of operations • logic status of inputs, outputs and LEDs • Parameter setting • of each protection function • of control logic • of general installation and Sepam data
Logipam • Selection • Choice in the list • Apply • Activate • Delete • Download onto the PC • Automatic updating
Logipam internal resources • LOGIPAM: • internal bits • counters • clocks • delays
General information on connected mode • Connection • Sepam type • Sepam name • Code operating mode • Remote control • Internal clock
Series 20 General diagnosis • General characteristics • Software versions • Sepam status • Clock with time-setting • Presence of modules • Monitoring of communication exchanges
Series 40 General diagnosis • General characteristics • Software versions • Sepam status • Clock with time-setting • Presence of modules • Monitoring of communication exchanges
Series 80 General diagnosis • General characteristics • Software versions • Sepam status • Clock with time-setting • Presence of modules • Monitoring of communication exchanges
Series 40 & 80 Diagnosis: LED, input and output status • Display of LEDs • Display of validated inputs • Display of outputs • Testing of 3s pulse outputs
Series 40 & 80 Diagnosis: remote indication (TS) status • Status transmitted via the communication link
Series 80 Measurements Network measurements: • Current measurements • rms • demand • maximum • residual • additional • Voltage measurements • phase-to-neutral • phase-to-phase • positive-sequence • negative-sequence • Frequency measurement
Series 80 Measurements: vector diagram • Display • voltage • current • Select • scale • référence
Series 80 Power and energy measurements • Power measurements • active • reactive • apparent • power factor • Energy measurements • active • reactive
Series 80 Temperature measurements • MET 148 modules
Series 80 Network diagnosis • Unbalance ratio • Phase displacement • Number of trips • Phase • Earth • Total Harmonic Distortion
Series 80 Network diagnosis • Machine diagnosis • Differential measurements • Phase angles • Impedance measurements • Thermal overload • Running hours counter
Series 80 Network diagnosis • Tripping contexts • Selection by date
Series 80 Switchgear diagnosis • Cumulative breaking current • …
Series 80 Alarm management • Current alarms • Not acknowledged • Clear • Reset • Alarm history • 200 alarms
Series 80 Disturbance recording • Selection by date • Voluntary trigger • Recovery ofrecording
Series 80 On-line help • On-line help
MAIN POINTS TO REMEMBER Main points to remember
Network diagnosis functionsTripping current • This function gives the RMS values of the phase currents and residual currents at time of the last trip. • The measurement is defined as the maximum RMS value measured during a 30 ms interval after the activation of the O1 output. Acquisition of tripping current TRIPI1. RETURN
I I’1 Machine operating assistance functions Current phase displacement • Current phase displacement between the main phase currents (I) and additional phase currents (I') (1, 2, 3) is calculated for each phase. • The angle is measured in the clockwise direction. • The information is used to check Sepam wiring when 87T protection functions are implemented. RETURN
Q V -CAP +IND I P -IND +CAP Metering functionsPower factor (Cos) • This function gives the phase displacement between the phase currents and the phase-to-neutral voltages. • The + and - signs and the IND (inductive) and CAP (capacitive) indications give the direction of power flow and the type of load. RETURN
Io Vo 0 I V Network diagnosis functions Phase displacement • This function gives: • phase displacement measured between the residual voltage and residual current in the trigonometric direction • phase displacement between the V1, V2, V3 voltages and I1, I2, I3 currents respectively, in the trigonometric direction • The measurements are used during Sepam commissioning to check that the voltage and current inputs are wired correctly. • The angle is positive when the current is leading compared to the voltage (trigonometric direction). • the angle is modified by 180° by the setting incomer / feeder. RETURN
Idiff = Iadjusted + I’adjusted It = max ( Iadjusted , I’adjusted ) Machine operating assistance Differential / through current • Differential / through current is calculated for the implementation of the differential protection functions 87T and 87M. • It is calculated for each phase by: • When a transformer is used (87T), the Idiff / It calculation takes into account the vector shift and transformation ratio.. • The Idiff / It value is expressed with respect to In, the rated current of the main channels. RETURN
Metering functionsPhysical values measured • Sepam measures the following physical values: • phase current (3I) • residual current (Io) • phase voltage (3V) • residual voltage (Vo) • Each measured signal is processed by Sepam to produce all the values necessary for the metering, diagnosis and protection functions. RETURN
Metering functionsRMS measurement • RMS measurement is only used by the phase current metering function and for the thermal overload protection function (49). The RMS values take into account harmonics up the the 13th. • For all other metering and diagnosis functions, the H1 fundamental 50 Hz or 60 Hz component is used. RETURN
Metering functionsResidual current • This function gives the RMS value of the residual current obtained by: • measurement: Io • calculation of the sum of the phase currents: Io • Accuracy at Ino: ±1%. • Accuracy ± 2% from 0.3 to 1.5 Ino • Accuracy ± 3% from 0.1 to 0.3 Ino • The measurement range extends to 40 Ino when Io measurement is used. In the other cases, the range extends to 20 Ino. RETURN
Demand current A 5mn 5mn 5mn 5mn 5mn 100A t 55A 63A 89A 78A 59A Metering functionsDemand phase current • Resetting to zero: • by the clear key on the display unit if one of the two screens is displayed, • by the clear command in the SFT2841 software, • via the communication link (remote control order TC4). RETURN
Peak demand current A 5mn 5mn 5mn 5mn 5mn 100A t 55A 63A 89A 89A 89A Metering functionsPeak demand current • At the end of each integration period, i.e. once the new demand current values are available, the function determines the greatest demand current value obtained since the last reset. RETURN
Metering functionsPhase-to-phase voltage • This function gives the RMS value of the 50 or 60 Hz component of the phase-to-phase voltages. • U21 voltage between phases 2 and 1 (U21=V1-V2) • U32 voltage between phases 3 and 2 (U32=V2-V3) • U13 voltage between phases 1 and 3 (U13=V3-V1) • by calculation when 3 phase-to-earth VTs are connected, • by measurement (U21 and U32) and by calculation (U13) when 2 phase-to-phase VTs are connected, • by measurement (U21) when only one phase-to-phase VT is connected, in which case the U32 and U13 voltages are not available. RETURN
Metering functionsFrequency • This measurement is based on: • U21 if only one phase-to-phase voltage is available, • positive sequence voltage if the U21 and U32 measurements are available. • The frequency is not displayed (replaced by ****) if: • U21 or Vd is less than 40% of Un. • frequency is out of range. • Accuracy at Unp: ±0.01Hz • 25 to 65 Hz range Sepam series40 and 80 • 45 to 55 Hz if 50Hz Sepam series 20 • 55 to 65 Hz if 60Hz Sepam series 20 RETURN
V I Metering functionsPower factor (Cos) • Capacitive/inductive circuit: • If V is leading compared to I, in the trigonometric (counter-clockwise) direction, then is positive. • A capacitive (CAP) circuit is one in which the current is leading compared to the voltage ( <0). • An inductive (IND) circuit is one in which the current is lagging compared to the voltage ( >0). CAP I IND V RETURN
Metering functionsActive, reactive and apparent power • For an incoming circuit: • Power supplied to the busbars is positive. • Power supplied by the busbars is negative. • For an outgoing circuit: • Power supplied to the busbars is negative. • Power supplied by the busbars is positive. Direction of power flow Direction of power flow P+ P+ RETURN