Anti-Tamper Paint. Travel Sensor Is Factory Adjusted. The placement of the feedback arm on the travel sensor is factory adjusted and sealed with anti-tamper paint. This setting has been tested for functionality successfully several times before the DVC6000 ships from the factory.

rpitman
Download Presentation

Travel Sensor Is Factory Adjusted

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Anti-Tamper Paint Travel Sensor Is Factory Adjusted • The placement of the feedback arm on the travel sensor is factory adjusted and sealed with anti-tamper paint. • This setting has been tested for functionality successfully several times before the DVC6000 ships from the factory. • Do not assume this setting is wrong. • Check everything else first before disturbing the anti-tamper paint.

  2. DVC6000 – Potentiometer Issues • Potentiometer Components

  3. Vibration Induced Potentiometer Wear • Some control systems are not grounded • Valve Travels in Higher Resistance Area (80 – 90% travel) • Amplification of travel noise by velocity gain in the DVC tuning ( Reduce affect by changing to velocity gain of 0)

  4. No Potentiometer Wear

  5. ValveLink Graph with Potentiometer Wear-Thru

  6. Profile Test • Requires PD Tier

  7. PD Profile No problems

  8. PD Profile Test Showing Early Wear

  9. Best to remove potential wear points all together Unique linkage-less non-contact design Feedback components never touch the instrument DVC2000 Released in 2004 DVC6200 HART DVC6200f FOUNDATION Fieldbus Increase Reliability with Linkage-less feedback Feedback Arrays No Linkages

  10. DVC6200 - Product Details • Differences between the DVC6200 & the DVC6000 • Hall sensor in place of the feedback potentiometer • Terminal box moves to the left side of the housing • New mounting kits (same design as DVC2000 kits) • HART: Firmware 10 required • FOUNDATION fieldbus: new PWB and terminal box required

  11. Curved array Rotary Magnet 1”, 2” & 4” array DVC6200 - Mounting Kits • Bolt patterns for DVC2000 and DVC6200 are identical • Existing DVC2000 mounting kits are being updated • 1 standard kit for both DVC6200 and DVC2000 • Stronger brackets will replace the existing brackets to accommodate additional weight • New curved array • For use with the existing long stroke cams • For Fisher rotary actuator window

  12. Long Stroke Mounting Anti-rotation

  13. Dual Mounting Bracket

  14. DVC6205/6215 Remote Mount

  15. Terminal Boxes • Power 4V to 30V • Feedback 0-.5 V normal • DVC6215 Ground • Status Line

  16. Design Engineering Used for Temperature Calibration -52 to 125 Deg C

  17. Remote Mount Components

  18. ValveLink Mobile

  19. ValveLink Mobile • Bluetooth Communications to a HART modem • Developed for Windows Mobile platform • Very compact, portable platform for local configuration, calibration, and diagnostics. • Integration into Emerson 375 / 475 platform

  20. ValveLink Mobile 2.0 • Icon Driven User Interface • Common Tasks Located on Home Screen. • High Contrast for Outdoor Viewing. • Thumb Driven Interface - No Stylus Required. • Preprogrammed diagnostics. Tests can be run, saved, and uploaded later to ValveLink or AMS.

  21. ValveLink Mobile on 375 / 475 • Same interface as on PDA and Smartphone platforms. • FAST configuration, calibration, and diagnostics.

  22. Diagnostics on the 375 / 475 Total Scan Step Response PD Diagnostics Valve Signature Step Study 1 Button Sweep Dynamic Error Band Stroking Speed PD Traces

  23. Valve Diagnostic Changes

  24. PD Diagnostics

  25. Import Field Data into ValveLink(Upload to the mother ship)

  26. ValveLink Support

  27. ValveLink 12 License Changes • Planning on free Version with 12.0 targeted for Oct. • Install on Multiple PC’s • No additional license key required • Connect to 1 device at a time • Database is limited to one tag • Supports HART & Ff

  28. ValveLink Support • $405 per year • Includes License Support, New Software CD, and Web Based FTP Access • ftp://ftp2.emersonprocess.com/