An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. VRF Equipment & Applications Ruben Willmarth West Region Sales Manager Toshiba Carrier Ductless & VRF November 07, 2014 Billings, MT Joint Engineering Conference

  2. CONTENTS What is VRF Global Application Examples Benefits of VRF systems System Components Controls Basic Design Practices ASHRAE Std 15 & 34

  3. WHAT IS VRF “VRF” system is a short for Variable Refrigerant Flow system. Refrigerant flow is varied based on demand - System where multiple (up to 50 indoor units) can be connected to outdoor units. - Fan coils are controlled individually or by group controls. - Refrigerant flows to the unit that is calling for heating or cooling.

  4. VRF Technology Overview Two VRF System Types • Heat Pump • Heat Recovery • Simultaneous Cooling & Heating • Single Mode: Cooling or Heating Only

  5. VRF Technology Overview Primary Components of a Heat Pump System

  6. Typical VRF Heat Pump System Outdoor unit Compressor Liquid line (fully liquid) Indoor unit Refrigeration Pipe (Liquid, Gas) Each indoor unit can be controlled individually. On/Off setting , Set point, Air volume, louver position can be set individually. (Operation mode priority : Cooling or Heating, not simultaneously in heat pump model) Cooling : Expansion=Indoor unit Liquid line=Condensed liquid Heating : Expansion=Outdoor unit Liquid line =Condensed liquid

  7. VRF Technology Overview How does VRF work? • Indoor Unit • Transfers heating and cooling directly to the space • Measures Return Air Temperature • Pulse Motor Valve (PMV) adjusts to meet setpoint • Filters and distributes the air • Unit operates to match exact building load • Outdoor Unit • Houses multiple inverter driven compressors • Compressors change speed based on demand of indoor units, which varies the refrigerant flow • Segmented ODU Coil for efficient heat transfer • Unit operates to match exact building load • Flow Selector • Receives superheated gas and subcooled liquid, adjusts flow direction to heat and cool • Allows for indoor unit to be in either cooling or heating mode • Unit operates to match exact building load • Controller • Allows for indoor unit control at zone level • Takes user desired space setpoint, fan speed, mode • Unit operates to match exact building load

  8. Typical VRF Heat Recovery System 3 - Pipe Simultaneous heating and cooling, uses cooling mode waste heat for heating Heat Recovery Box

  9. Typical VRF Heat Recovery System 2 - Pipe

  10. Varying Refrigerant Flow How does the outdoor unit respond to the varyingdemands and vary the flow of refrigerant? The compressor(s) in the outdoor units are inverter driven which means that their speed can be varied by changing the frequency of the power supply to the compressor. As the compressor speed changes, so does the amount of refrigerant delivered by the compressor.

  11. SYSTEM ADVANTAGES High Reliability

  12. Use Wherever Part Load Exists Application: In case of: Not all units are on. Example: office area is on, meeting room is off. OFF In case of: Orientation of building Example: East/West exposure Apartment, In case of: Decreased load. Example: office closed Office building

  13. ZONING OPERATION OF VRF (In case of cooling) OFF OFF OFF OFF : Piping : 4-way cassette type : Hi-wall type : Outdoor units

  14. ADVANTAGES OF VRF -Comfort - Design flexibility -Energy savings (part load, heating) - Cost effective installation

  15. ADVANTAGES OF VRF

  16. COMPRESSOR COMPARISONS Rotary compressor Scroll compressor

  17. COMPRESSOR COMPARISON Scroll compressor Twin rotary compressor Out Out In In In

  18. ADVANTAGES OF VRF EASE OF DESIGN Multiple types of Fan Coils and Sizes provides design flexibility for many different applications

  19. ADVANTAGES OF VRF Modularity of equipment allows for Staging of installation, Redundancy in operation

  20. ADVANTAGES OF VRF HX, and

  21. ADVANTAGES OF VRF

  22. TECHNICAL TRAINING

  23. 1200 apartments in 7 buildings Recognized by China’s Ministry of Construction as being among the most cost-effective air conditioning systems available. ShengshiQiantang Garden 3,840Tons

  24. Jae Neung Education Building 2,400Tons

  25. Portal Commercial Development 280Tons

  26. Approx. 10,000 sq. ft 7 floor multi-tenant office building Burt Hill Architects Office 26

  27. Installed in subway passages and administration offices Contracts extending to other lines China Subway 19,200Tons 27

  28. DESIGNING WITH VRF High Reliability

  29. Designing for Energy efficiency Perimeter/Core Office 107 3.0kBTU Office 108 3.0kBTU Office 110 4.5kBTU Office 109 3.0kBTU Pres. Office 12 kBTU 13.5 kBTU 6 1 Corr 2.0kBTU 12 kBTU Men’s 2.0kBTU Women’s 2.0kBTU 7 Coffee/Brk 2.0kBTU Rejected Heat 5 2 Foyer 2.5kBTU 28 kBTU 12 kBTU 2.5 kBTU Office 106 3.0kBTU Office 105 3.0kBTU Office 104 3.0kBTU Conf. 28.0kBTU Corr 2.0kBTU Office 110 7.5kBTU 3 4 20 kBTU 14 kBTU VP Office 14 kBTU Office 101 6.0kBTU Office 102 6.0kBTU Office 103 6.0kBTU Example: 40oF Ambient

  30. Ventilation Design Ventilation Strategies with VRF Room graphic w/Air into Corner Delivering OSA directly to the space: • Best when it is Neutral temperature & Humidity (DOAS) • An ERV-only is OK in the West & South, if low fraction and high ceilings (mixing time) • Mild Climates can bring in small fraction untreated • Benefits are less ducting, more flexible application

  31. Ventilation Design Ventilation Strategies with VRF Delivering OSA ducted to the Fan Coil: • Pre-Filtered, tempered air is best. (DOAS) • Allows selecting to meet Envelope load for max comfort • Air inlet point is before the filter on some ductless, so Filter is a must! • An ERV-only is Good in the West & South, but may need additional heat in the North • DOAS system or ERV+FC is best for Cold Climates • Mild Climates can bring in small fraction untreated (<30%) • Benefits are better humidity control, no extra grills

  32. Ventilation Design DOAS using an ERV • DOAS approach allows us to split the ventilation load away from the Mechanical system by tempering the air first. • Can use an ERV only for most applications • Can run OSA through a standard Fan Coil in Series for Neutral Air application, especially if not ducted to Fan Coils • Can apply Supplemental Heat for Cold Climate applications for Neutral Air, or even higher

  33. Heating Design Heating Design Strategies Heating with a VRF System: -VRF is a Heat Pump, but…. • But it is not your Grandpa’s Heat Pump! • Capacity is better than traditional because of inverter compressors that can spin faster to compensate • De-rate due to ambient temperature is less, but must still be accounted for. • Auxiliary Heat to cover the <average

  34. Heating Design Heating Design Strategies- Avg. vs. Design: “Avg. winter low in Billings, MT is 16F” • The Design Heating in Billingsis -20F • But the Average January Low is 16F

  35. Ventilation Design Heating Design Strategies “Avg. winter low in Seattle, WA is 36F” “Avg. winter low in Billings, MT is 16F” “Avg. winter low in Chicago, IL is 17F” “Avg. winter low in Nashville, TN is 29F” When to use Auxiliary Heat? • Rule of Thumb is start considering it at 15F design temp. • Simple Answer is when heating Design Day exceeds capacity • ERV & DOAS can provide significant contributions.

  36. Heating Design Heating Design Strategies-Aux Heat Types of Aux. Heat: • Electric Strip-Heater (Ducted Models only) • Hydronic Coil (can feed from an upsized DHW source) • Both of above can be placed in DOAS ducting for 90+F ventilation air if that meets the needed BTU’s! • Baseboard Heating Panels • Hydronic or Electric-All Fan Coils • Radiant Panels • Hydronic or Electric-All Fan Coils • Wall Heaters • Typically Electric-All Fan Coils • Or….Previously Existing Heating System!!

  37. Heating Design Heating Design Strategies-Aux Heat There are 3 ways to activate the Aux. Heat • Individual Space Response: • Zone temp drops, Aux heat activates at Temp. A, then deactivates at Temp B. Both must be less than heating setpoint • Outdoor Ambient Trigger. Aux heaters engage when FC is in Heating, Aux Heating system activated by separate Outdoor Ambient Thermostat. • BMS Control system activation. Can use custom logic for zone by zone response, minimize setpoint drift.

  38. Heating Strategies Heating Design Strategies-Aux Heat Heating Setback with VRF: • A VRF system is different from a combustion heater because it’s efficiency gets better at part-load. • When system is in recovery, system goes to full-load, which is less efficient than maintaining a constant temperature, but total heat loss is more. • So, optimum use is probably minimal setback during weekdays, and more of a setback over weekends & Holidays, or just a 2F setback period. • No setback during cold snaps to avoid using Aux Heat.

  39. Heating Strategies Heating Design Strategies-Aux Heat Alternate to zone-level Aux. Heat-Put Outdoor Units in a Mechanical Room or “Doghouse”

  40. Heating Design Heating Design Strategies-Aux Heat Alternate to zone-level Aux Heat-Put Outdoor Units in a Mechanical Room or Doghouse: • Simplifies controls of Aux. Heat by having one set of controls and heat source. • Heater is typically a Gas unit heater, or other combustion unit • Backup isolates from Outdoor air at preset ambient temp. • Key Selection Criteria: • Size the Unit heater for 70-80% of Heat Load • Ducting system must be 0.2” esp max. in both modes • Activation temp typically below freezing, but maintain interior temp around 45F to avoid frost buildup. • Don’t forget to include a condensate drain, w/heat tracing

  41. Refrigerant system Design VRF and ASHRAE 15/34 In part, Standard 15, Safety Standard for Refrigeration Systems,strives to ensure a safe system by limiting the maximum quantity of refrigerant below that which is a danger to human occupants if a leak occurs. Because VRF uses the Refrigerant as the transport medium, it is inherently a more refrigerant intensive product than most traditional HVAC. Std. 15 is the application guideline that ensures a safe design every time.

  42. VRF and ASHRAE 15/34 Refrigerant Concentration Limit (RCL) R410A R410A is a commonly used refrigerant for commercial VRF systems. Per Standard 34, Table 2, the safety classification of R-410A is Group A1 (meaning non-flammable and non-toxic). Even though R-410A is Group A1, its ability to displace oxygen could pose a danger to occupants if released in large quantities into smaller-volume spaces. Therefore, Standard 34, Table 2 has established an RCL for R-410A at 26 lbs of refrigerant per 1,000 cuft of room volume. For Institutional Occupancies such as patient care areas of hospitals and senior homes, the RCL is cut in half, changing the RCL for R-410A to 13 lbs/1,000 cuft.

  43. VRF and ASHRAE 15/34 • Smaller Capacity Systems • Design for “Connected Spaces” • Combine multiple smaller zones on a single ducted fan coil unit • One to-One Systems • Diversity • Refrigerant Piping Layout • Y-branching versus manifold • Isolate refrigerant circuit for Smaller Rooms • R410A sensor and alarm, or isolation valves Stephen W. Duda’s article published in ASHRAE Journal, July 2012. Posted at www.ashrae.org. Applying VRF? Don’t Overlook Standard 15

  44. Questions ?