An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ARSENIC REMOVALCase History Milos Markovic

  2. Arsenic removal 35000 m3/day Plant in Subotica-SERBIA

  3. Arsenic is a common, naturally occurring drinking water contaminant thatoriginates from arsenic-containing rocks and soil and is transported to natural waters through erosion and dissolution • Arsenate exists in four forms in aqueous solution based on pH: H3AsO4,H2AsO4, HAsO42-, and AsO43-. Similarly, arsenite exists in five forms: H4AsO3+, H3AsO3, H2AsO3-, HAsO32-, and AsO33- • As shown in Figure, which contains solubility diagrams for As(III) and As(V), ionic forms of arsenate dominate at pH >3, while arsenite is neutral at pH <9 and ionic at pH >9

  4. Removal efficiency, % Iron removal can be used to remove arsenic from drinking water Conventional coagulation/filtration is a common water treatment methodology used to remove suspended and dissolved solids from source water. Alum and iron (III) salts, such as sulphates, are the most common coagulants used for drinking water treatment. As can be seen on the Figure, removal efficiency is greater in the case of iron salt for larger pH range

  5. This process involves two major steps: (1) oxidation of reduced iron, Fe(II), to the relatively insoluble Fe(III) in order to form precipitates; and (2) filtration of the water to remove the precipitated iron hydroxides. • Two primary removal mechanisms exist: adsorption and coprecipitation. The following major steps occur when using iron removal for arsenic treatment: (1) the soluble iron and any As(III) are oxidized; (2) As(V) attaches to the iron hydroxides through adsorption and/or coprecipitation; and (3) the particle/precipitate subsequently is filtered from the water. • According to the inlet Arsenic and Iron concentrations, it can be used one and two stage filtration process. At lower Arsenic concentration in raw water, preoxidation and one stage filtration is in most cases sufficient; Iron content in raw water is sufficient for arsenic removal. At greater arsenic concentration, two stage filtration and iron salt dosing is necessary.

  6. Water treatment plant in Subotica,Serbia • Plant capacity: 400 l/s • Inlet flow: 315-400 l/s • Key contaminants: • As: 71-115μg/l Fe: 0.62 mg/l • NH4: 0.64 mg/l Turbidity: 3.80 NTU • Oxidant: chlorine in front of first stage • Coagulant: Fe(SO4)2 in front of second stage • Filtration: Culligan industrial filters, four leaf clover system, made of made of steel and protected by anti-corrosion coatings, a heavy layer of epoxy resin in the inside and synthetic paint on the outside. Multilayer filter has a selective mineral within filtering layers, for iron and manganese removal. • Filtration rate: 12 m/h

  7. Influence of arsenic concentration in raw water on removal efficiency On the next diagram, As concentration in the treated water versus inlet As concentration and Fe2SO4 dose is presented: Condition for these doses is that concentration of Fe in raw water has to be not less than 0.6 mg/l.Optimal doses of iron were in the range from 1.4-1.6 mg/l, if arsenic concentration is not higher than 100 μg/l.In case of extreme inlet As concentration, up to 130 μg/l, it become necessary to apply much higher doses of iron, up to 2.8 mg/l.

  8. Influence of the iron content in raw water When the content of iron in raw water was under 0.6 mg/l, the concentration of As at the outlet of the II stage exceeded maximal concentration level. In this case , it is necessary to add some quantity of iron before I stage filter.

  9. Fe2SO4 dosing before both stage filters As iron dose before I stage increased from 0.7-2.0 mg/l, the efficiency of arsenic removal in I phase filters didn’t change much – arsenic concentration decreased from 43 to 39 μg/l. The dose of iron before II phase was constant, 1.4 mg/l. It can be concluded that in case of iron content in raw water of 0.6 mg/l, was not necessary to dose Fe2SO4 before I stage filter.

  10. As, μg/l Optimal Fe2SO4 dose Optimal dose of ferric sulphate was examined for inlet arsenic concentration up to 100 μg/l. The salt doses were in the range of 1.3-2.8 mg/l. By decreasing of iron dose from 2.8 to 1.3 mg/l, there was minimum on the As outlet concentration curve. This implies that the optimum dose of ferry sulphate is 1.5-1.6 mg/l, if content of arsenic in raw water is not higher than 100 μg/l.

  11. Filtration cycle I stage filters During 48 hours, we investigated iron concentration on outlet from I phase filters, under operating capacities of 50 and 70 l/s. Under previous conditions, iron ”break through” not happened. After 48 h, outlet concentration of iron from I phase filters were on the detection limit - 0,01 i 0,02 mg/l.

  12. II stage filters For the II phase filters, we investigated iron concentration on outlet from II phase filters, under operating capacities from 50 and 100 l/s On the previous diagram, it can be seen that the arsenic outlet concentration from II phase “breaks through” MCL level, when iron on outlet increases to 0.10-0.14 mg Fe/l. In this way, it is possible to established criteria for determining of the end of filtration cycle ( II phase).

  13. The following diagram shows filtration cycle duration (for 50 % and 100 % of nominal flow per line) by using previous criteria. Duration of filtration mode is 18.5 hours, if operation flow is 50 l/s per line, and only 13 hours for capacity of 100 l/s. The optimum filtration cycle for II phase filters is 12-13 hours.

  14. Conclusions Removal of arsenic from raw water is achieved below the desired value (and in most cases below limits of detection) if: • Inlet arsenic concentrations are not much higher than 130 μg/l (max. contract value) • Ferry sulphate dose is in front of the second line is 1.40 - 1.60 mg/l, • Dosing in front of the I phase is not necessary if the inlet iron concentration is stable • Backwashing is performed once in 48 hours for I phase filters, and once in 12 hours for II phase filters

  15. New plants – under construction • Kanjiža 5200 m3/d • Horgoš 3500 m3/d • Subotica II 17500 m3/d • Vršac 32000 m3/d • Apatin 10500 m3/d • Indjija 13000 m3/d