290 likes | 634 Views
Multi Functional Digital Fault Recorder. Fully Featured Digital Fault Recorder For Transmission & Distribution Substations. INTRODUCING THE BLACKBOXDFR. Multi-Functional. PMU Class A Power Quality Monitoring Single or Double Ended Impedance-Based Fault Location Energy Metering.
E N D
Fully Featured Digital Fault Recorder For Transmission & Distribution Substations INTRODUCING THE BLACKBOXDFR Multi-Functional • PMU • Class A Power Quality Monitoring • Single or Double Ended Impedance-Based Fault Location • Energy Metering • 0.1% Accuracy on Analog Channels • Class A Power Quality • 0.1% Power & Energy Accuracy … Surpassing: • IEC 62053-22 Class 0.2S • ANSI C12.20 02 Class 10 + 20 for Energy • Highly Accurate PMU Measurements 24 Bit Continuous Acquisition @ 1024 Samples Per Cycle 1 μsecond Time Synchronization
GENERAL OVERVIEW Full Measurement & System Status RMS THD Trends System Information System Status Events BUILT-IN WEB SERVER • INVESTIGATION • 10,000 Parameters over 16 Analog & 96 Digital Channels: • 1 μsecond Zoom • Monitor Network System Condition • Detect Instabilities • Predict Future Failures • Scopes, Trends, Statistics, Summaries, Spectrums … • EVENTS • Digital Input OR PQ Events: • Dips, Swells, Interruptions, Transients, DI …. • Custom Events • Exceed Limitations • Parameters DX/DT • Event Aggregation • Logic Operator AND, OR, XOR
FULLY FEATURED WEB SERVER - HTML5 WEB TECHNOLOGY Utilizing …. Widely Used Web Browsers: Firefox Internet Explorer Safari & more … Common Smart Devices: Android iOS Windows 8 WEB-ENABLED DEVICE
5” COLOR TOUCH LCD 1 Point Access in Real-Time: All System Functions Configurations Measured Values Interactive: Easy to Operate Full Color User-Friendly Interface REAL-TIME MONITORING
SYSTEM ARCHITECTURE • Power Quality • PMU • Metering • Event Detection • Fault Locator LAN (PQZ, IEC 61850, DNP3, MODBUS) GPS/IRIG B 5” Color Touch LCD • 1 Year Waveform Recording • 10,000 PQ Parameters • 20µs – 2 Hrs Resolution • Metering Serial Port 2 x Synch Ports 2 x USB Ports 16 AC/DC Analog Inputs Digital I/O Sensor Inputs IR Port (Metering/Maintenance)
ARCHITECTURE – SINGLE OR DOUBLE SYSTEM ADAPTIBILITY FRONT VIEW LCD Touch Screen 1 Handles 2 IR Data Port 3
ARCHITECTURE – SINGLE OR DOUBLE SYSTEM ADAPTIBILITY REAR VIEW Communication Ports Custom Modular Design PPS / IRIG B Port Spare Slot 1 6 RS485/422 Serial Port Up to 16 Analog Channels 7 2 2 x DSP Sync In & Out Ports Up to 96 Digital Channels 3 8 LAN Port Main Power ON/OFF Switch 4 9 2 x USB Ports Main Power Inlet Socket 5 10
PHYSICAL DIMENSIONS REAR VIEW FRONT VIEW FRONT VIEW SIDE VIEW REAR VIEW
1 µsec Accuracy to the Master Clock GPS/IRIG B TIME SYNCHRONIZATION SNTP DSP SYNCHRONIZATION • 100 µsec Accuracy to the Master Clock • 100 nsec Between Modules
DIGITAL FAULT RECORDING • 1 Year Continuous Waveform Recordings • 1,024 Sample/Cycle per Analog Channel (50/60Hz) • 128 Sample/Cycle per Digital Channel (50/60Hz) • Unlimited Triggers • Digital Input Change • Analog Exceed Limitations • Parameters DX/DT • Fault Locator • One Ended Impedance-Based: Designed for Locating Faults on Single-Circuit Lines • Two Ended Impedance-Based: Designed to Measure Two-Ended Synchronized Recordings of Voltage & Currents, Formulating Frequency Phasors of Symmetrical Components
CLASS A POWER QUALITY • Measure & Record More Than 10,000 Parameters • Unbalance • 511 Harmonics • Inter-Harmonics • THD • RMS & More … • Power Quality Events • Voltage Dips • Voltage Swells • Voltage Interruptions
CLASS A POWER QUALITY • Custom Events • Per any Measured Parameter • DX/DT for any Measured Parameter • Transient Events • Event Capture per Waveform Signal • Compliance Engine • EN50160 • Custom Compliance – Geared to Meet any Grid Code
PHASOR MEASUREMENT UNIT (PMU) • Measurement of Vector Quantities: • Highly Accurate • According to IEEE C37.118 – 2005 • 1µsec Time Synchronization • On-Board Solution: • Continuous Phasor Recording and Transmitting • ½ Cycle Transmission Rate
ENERGY METER Integrated High Precision Energy Meter – Measure & Record: • 0.1% Power & Energy Accuracy … Surpassing: • IEC 62053-22 Class 0.2S • ANSI C12.20 02 Class 10 + 20 for Energy • Flow of Energy within a System: • Reactive Power • Active Power • Apparent Power • Power Factor • Flow of Power To & From the System to the Grid: • Delivered • Received
MULTI CHANNEL – UP TO 16 ANALOG & 96 DIGITAL CHANNELS PER MODULE HIGHLY ACCURATE MEASUREMENTS ULTRA FAST SAMPLING RATE INTEGRATED DB FOR SW FREE INVESTIGATION PQZIP II – FOR REAL TIME COMMUNICATION BLACKBOXDFR - THE PERFECT DFR SOLUTION