1 / 28

Multi Functional Digital Fault Recorder

Multi Functional Digital Fault Recorder. Fully Featured Digital Fault Recorder For Transmission & Distribution Substations. INTRODUCING THE BLACKBOXDFR. Multi-Functional. PMU Class A Power Quality Monitoring Single or Double Ended Impedance-Based Fault Location Energy Metering.

rune
Download Presentation

Multi Functional Digital Fault Recorder

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Multi Functional Digital Fault Recorder

  2. Fully Featured Digital Fault Recorder For Transmission & Distribution Substations INTRODUCING THE BLACKBOXDFR Multi-Functional • PMU • Class A Power Quality Monitoring • Single or Double Ended Impedance-Based Fault Location • Energy Metering • 0.1% Accuracy on Analog Channels • Class A Power Quality • 0.1% Power & Energy Accuracy … Surpassing: • IEC 62053-22 Class 0.2S • ANSI C12.20 02 Class 10 + 20 for Energy • Highly Accurate PMU Measurements 24 Bit Continuous Acquisition @ 1024 Samples Per Cycle 1 μsecond Time Synchronization

  3. GENERAL OVERVIEW Full Measurement & System Status RMS THD Trends System Information System Status Events BUILT-IN WEB SERVER • INVESTIGATION • 10,000 Parameters over 16 Analog & 96 Digital Channels: • 1 μsecond Zoom • Monitor Network System Condition • Detect Instabilities • Predict Future Failures • Scopes, Trends, Statistics, Summaries, Spectrums … • EVENTS • Digital Input OR PQ Events: • Dips, Swells, Interruptions, Transients, DI …. • Custom Events • Exceed Limitations • Parameters DX/DT • Event Aggregation • Logic Operator AND, OR, XOR

  4. FULLY FEATURED WEB SERVER - HTML5 WEB TECHNOLOGY Utilizing …. Widely Used Web Browsers: Firefox Internet Explorer Safari & more … Common Smart Devices: Android iOS Windows 8 WEB-ENABLED DEVICE

  5. 5” COLOR TOUCH LCD 1 Point Access in Real-Time: All System Functions Configurations Measured Values Interactive: Easy to Operate Full Color User-Friendly Interface REAL-TIME MONITORING

  6. SYSTEM ARCHITECTURE • Power Quality • PMU • Metering • Event Detection • Fault Locator LAN (PQZ, IEC 61850, DNP3, MODBUS) GPS/IRIG B 5” Color Touch LCD • 1 Year Waveform Recording • 10,000 PQ Parameters • 20µs – 2 Hrs Resolution • Metering Serial Port 2 x Synch Ports 2 x USB Ports 16 AC/DC Analog Inputs Digital I/O Sensor Inputs IR Port (Metering/Maintenance)

  7. ARCHITECTURE – SINGLE OR DOUBLE SYSTEM ADAPTIBILITY FRONT VIEW LCD Touch Screen 1 Handles 2 IR Data Port 3

  8. ARCHITECTURE – SINGLE OR DOUBLE SYSTEM ADAPTIBILITY REAR VIEW Communication Ports Custom Modular Design PPS / IRIG B Port Spare Slot 1 6 RS485/422 Serial Port Up to 16 Analog Channels 7 2 2 x DSP Sync In & Out Ports Up to 96 Digital Channels 3 8 LAN Port Main Power ON/OFF Switch 4 9 2 x USB Ports Main Power Inlet Socket 5 10

  9. PORT CONFIGURATIONS

  10. PHYSICAL DIMENSIONS REAR VIEW FRONT VIEW FRONT VIEW SIDE VIEW REAR VIEW

  11. 1 µsec Accuracy to the Master Clock GPS/IRIG B TIME SYNCHRONIZATION SNTP DSP SYNCHRONIZATION • 100 µsec Accuracy to the Master Clock • 100 nsec Between Modules

  12. DIGITAL FAULT RECORDING • 1 Year Continuous Waveform Recordings • 1,024 Sample/Cycle per Analog Channel (50/60Hz) • 128 Sample/Cycle per Digital Channel (50/60Hz) • Unlimited Triggers • Digital Input Change • Analog Exceed Limitations • Parameters DX/DT • Fault Locator • One Ended Impedance-Based: Designed for Locating Faults on Single-Circuit Lines • Two Ended Impedance-Based: Designed to Measure Two-Ended Synchronized Recordings of Voltage & Currents, Formulating Frequency Phasors of Symmetrical Components

  13. CLASS A POWER QUALITY • Measure & Record More Than 10,000 Parameters • Unbalance • 511 Harmonics • Inter-Harmonics • THD • RMS & More … • Power Quality Events • Voltage Dips • Voltage Swells • Voltage Interruptions

  14. CLASS A POWER QUALITY • Custom Events • Per any Measured Parameter • DX/DT for any Measured Parameter • Transient Events • Event Capture per Waveform Signal • Compliance Engine • EN50160 • Custom Compliance – Geared to Meet any Grid Code

  15. PHASOR MEASUREMENT UNIT (PMU) • Measurement of Vector Quantities: • Highly Accurate • According to IEEE C37.118 – 2005 • 1µsec Time Synchronization • On-Board Solution: • Continuous Phasor Recording and Transmitting • ½ Cycle Transmission Rate

  16. ENERGY METER Integrated High Precision Energy Meter – Measure & Record: • 0.1% Power & Energy Accuracy … Surpassing: • IEC 62053-22 Class 0.2S • ANSI C12.20 02 Class 10 + 20 for Energy • Flow of Energy within a System: • Reactive Power • Active Power • Apparent Power • Power Factor • Flow of Power To & From the System to the Grid: • Delivered • Received

  17. BLACKBOX ARCHITECTURE

  18. PQSCADA 5 – OVERVIEW [SINGLE MAP]

  19. PQSCADA 5 – OVERVIEW [MULTIPLE MAPS]

  20. PQSCADA 5 – OVERVIEW [ELECTRICAL MAP]

  21. PQSCADA 5 – OVERVIEW [TOPOLOGY]

  22. PQSCADA 5 – POWER QUALITY

  23. PQSCADA 5 – POWER QUALITY

  24. PQSCADA 5 – POWER QUALITY

  25. PQSCADA 5 – POWER QUALITY

  26. PQSCADA 5 - INVESTIGATOR

  27. MULTI CHANNEL – UP TO 16 ANALOG & 96 DIGITAL CHANNELS PER MODULE HIGHLY ACCURATE MEASUREMENTS ULTRA FAST SAMPLING RATE INTEGRATED DB FOR SW FREE INVESTIGATION PQZIP II – FOR REAL TIME COMMUNICATION BLACKBOXDFR - THE PERFECT DFR SOLUTION

  28. THANK YOU