Daikin Altherma™ Troubling Shooting

Daikin Altherma™ Troubling Shooting. R3T. Outlet thermistor failure. Code: 81 Part: Outlet water thermistor Location: Activation failure: Possible action to resolve the problem: Check connector Check resitance value Replace thermistor. R3T. Freeze up problem. Code: 89

Download Presentation

Daikin Altherma™ Troubling Shooting

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Daikin Altherma™ Troubling Shooting

  2. R3T Outlet thermistor failure • Code: 81 • Part: Outlet water thermistor • Location: • Activation failure: • Possible action to resolve the problem: • Check connector • Check resitance value • Replace thermistor

  3. R3T Freeze up problem • Code: 89 • Part: Heat exchanger freez-up • Activation failure: Outlet water temp. too low • Location: • Possible action to resolve the problem: • Check water flow in the system. Minimum water flow system 9liter / min.

  4. R3T Flow failure • Code: 7H • Part: Flow failure • Location: • Activation failure: Flow switch open during operation (no signal) • Possible action to resolve the problem: • Check water flow in the system. (Minimum water flow system 20liter / min.) • Check water pressure in the installation. (Minimum 0.3 bar) • Check shutt OFF valves • Is water system purged • Check pressure drop and speed of the waterpump • Check pump operation

  5. R3T Outlet water temperture too high • Code: 8H • Part: Outlet water thermistor • Location: Outlet back up heater • Activation failure: If outlet water > 65°C • Possible action to resolve the problem: • Check if contactor(s) back up heater is not welded • Check if thermistor is not damaged • Check if correct resistor value of thermistor • Procedure :Refer to service manual

  6. Indoor PCB failure • Code: A1 • Part: Indoor PCB • Location: Switchbox • Activation failure: • Possible action to resolve the problem: • Replace PCB

  7. R3T Insufficient cooling or heating • Code: A5 • Part: Liquid sensor hydrobox • Location: • Possible action to resolve the problem: • Check water flow in the system. (Minimum water flow system 9liter / min.) • Check water pressure in the installation. (Minimum 0.3 bar) • Check shutt OFF valves • Is water system purged • Check pressure drop and speed of the waterpump • Check refrigerant charge • Check thermistor • Procedure: refer to service manual

  8. Booster heater thermal protector • Code: AA • Part: Thermal protector booster heater or back up heater * • Location: • Possible action to resolve the problem: • Check if thermal protection is not damaged. • Check contactor of the electric BUH / BSH

  9. R3T Stucked flow switch • Code: CO • Part: Flow switch failure • Activation failure: Flow swith remains closed when pump is not operating • Location: • Possible action to resolve the problem: • Check for dirt in flow switch • Replace part is required

  10. R3T Heat exchanger thermistor failure • Code: C4 • Part: Liquid sensor • Activation failure: Sensor broken or out of range • Location: • Possible action to resolve the problem: • Check connector • Check resistance of the sensor • Procedure: refer to servicemanual for procedure • If damaged replace part

  11. Outdoor PCB failure • Code: E1 • Part: Outdoor PCB failure • Activation failure: • Location: • Possible action to resolve the problem: • Out of control of CPU • Voltage drop • Power loss • Noise on power supply • Defect outdoor PCB

  12. Overload activation of compressor • Code: E5 • Part: Overload protector compressor • Activation failure: Failure If overload protector ( >130°C) is activated twice in one hour • Location: Outdoor unit • Possible action to resolve the problem: • Refrigerant shortage. • Malfunction four way valve. • Outdoor PCB failure. • Electronic expansion valve defective.

  13. Compressor start up failure • Code: E6 • Part: Compressor locked • Activation failure: : Failure, if error occurs 16 times, counter reset if compressor runs normal for 5 minutes • Location: Outdoor unit • Possible action to resolve the problem: • Replace outdoor PCB • Replace compressor

  14. Fan motor failure • Code: E7 • Part: Outdoor fan motor • Activation failure: Failure, if error occurs 16 times, counter reset if compressor runs normal for 5 minutes • Location: Outdoor unit • Possible action to resolve the problem: • Fan motor breakdown • Bad contact between PCB and fan motor • Blockage of the fan blades

  15. Sanitary water too high • Code: EC • Part: Sanitary tank temperature • Activation failure: If temperature sanitary water > 89°C • Location: Sensor inside sanitary tank • Possible action to resolve the problem: • Check position of sensor in socket • Check if contactor(s) booster heater is not welded • Check if thermistor is not damaged • Check if correct resistor value of thermistor

  16. Discharge temperature too high • Code: F3 • Part: Discharge sensor • Activation failure: Failure if discharge temperature > 120°C for 6 times • Location: Sensor located on the discharge pipe of compressor • Possible action to resolve the problem: • Refrigerant shortage. • Malfunction four way valve. • Defective discharge sensor. • Defective EEV driver.

  17. Voltage and current sensor failure • Code: H0 • Part: Voltage / Current sensor • Activation failure: No measurement of current during compressor operation. • Possible action to resolve the problem: • Reactor disconnected • Compressor disconnection • Outdoor PCB failure • Compressor defective

  18. Outdoor ambient thermistor • Code: H9 • Part: Thermistor • Location • Activation failure: Resistance value out of range • Possible action to resolve the problem: • Check connector • Check resistance value • Replace thermistor. • Outdoor PCB

  19. Discharge pipe thermistor • Code: J3 • Part: Discharge pipe thermistor • Location • Activation failure: Resistance value out of range • Possible action to resolve the problem: • Check connector • Check resistance value • Replace thermistor. • Outdoor PCB

  20. Outdoor heat exchanger • Code: J6 • Part: Thermistor • Location • Activation failure: Resistance value out of range • Possible action to resolve the problem: • Check connector • Check resistance value • Replace thermistor. • Outdoor PCB

  21. Electrical box temperature rise • Code: L3 • Part: Radiation fin thermistor • Location: Outdoor PCB • Activation failure: failure if temperature > 85°C and compressor OFF • Possible action to resolve the problem: • Defective outdoor fan • Defective Fin thermistor • Defective Outdoor PCB • Heat conductive paste

  22. Radiation fin temperature rise • Code: L4 • Part: Radiation fin temperature rise • Location: Outdoor PCB • Activation failure: failure if temperature > 105°C and compressor ON for 4 times • Possible action to resolve the problem: • Defective outdoor fan • Defective Fin thermistor • Defective Outdoor PCB • Heat conductive paste