An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. PERANCANGAN COOLING TOWER Suatu pabrik membutuhkan air pendingin sebanyak 2.000 lb/menit untuk keperluan pendinginan pada condensor di unit distilasi. Panas yang harus diambil dari condensor adalah 55.000 Btu/menit. Air pendingin meninggalkan condensor pada temperatur 110 oF. Direncanakan untuk mendinginkan kembali air tersebut di dalam suatu induced draft cooling tower. Make up H2O ditambahkan dari suatu sumber air pada temperatur 50 oF. Kondisi rancangan menara ditentukan sebagai berikut : - Udara masuk temperatur dry bulb = 85 oF dan temp. wet bulb = 75 oF - Temperatur air keluar menara = 85 oF. - Udara yang dipakai adalah 1,5 kali harga minimumnya. Packing yang dipakai mempunyai harga Kya = 200 lb/jam cuft. Y. Laju cairan minimal = 2.000 lb/jam.ft2 Laju udara minimal = 1.500 lb/jam.ft2. Tentukan : • Luas penampang dan tinggi menara yang dibutuhkan • Kondisi udara keluar menara • Perkirakan make up H2O yang diperlukan (lb/jam) • Kapasitas fan (cuft/menit) • Apabila hasil rancangan menara di atas setelah beroperasi diadakan perubahan sbb: Udara masuk mempunyai tG = 85 oF dan tw = 80 oF, sedangkan perbandingan L/GS sama, hitunglah temperatur air keluar menara dengan kondisi yang baru ini.

  2. Udara keluar = 75 oF = 31.0 = 85 oF = 0.0165 = 120.000 lb/jam = 110 oF 2 Air panas Q = 3.300.000 Btu/jam D Condensor Z Make up H2O Air dingin M lb/jam 1 = 85 oF Udara masuk

  3. LAJU ALIR CAIRAN : LAJU ALIR UDARA : LUAS PENAMPANG YANG MEMENUHI SYARAT

  4. 84.7 66.8 A GRS OPERASI MENYINGGUNG KURVE SETIMBANG 31 B 85

  5. 84.7 66.8 A 41.9 31 B 85

  6. NtoG = Driving force (H’*- H’) dihitung pada interval tL (85 oF – 110 oF)

  7. LUASAN : I = 0.700 II = 0.735 III = 0.630 IV = 0.405 V = 0.371 VI = 0.247 I II III IV V VI + 3.08 (= NtoG) =

  8. = 101 oF UDARA KELUAR MENARA INDUCED DRAFT = 66.8 VH = 15.16 cuft/lb ud krg = 83.800 lb ud. krg/jam KAPASITAS FAN = = 1.270.400 cuft/jam = 1500 /200 = 7.5 ft = 7.5 x 3.08 = 23.1 ft

  9. tG2 = 101 oF (jenuh) Y2=Ys = 0.0453 H’2=66.8 Btu/lb ud. kering KONDISI UDARA KELUAR MENARA METODE GRAFIS (Mickley) 66.8 A 31 B tG2 101 85 tG1

  10. Udara keluar = 75 oF = 31.0 = 85 oF = 0.0165 Q4 = 66.8 = 0.0453 Air panas Q = 3.300.000 Btu/jam Q3 Neraca massa & neraca panas CT Condensor Make up H2O Air dingin Mlb/jam Q2 Q1 Udara masuk

  11. NERACA MASSA H2O NERACA PANAS (2) M = 2694 lb/jam (1) & (2) Gs = lb/jam

  12. KONDISI BARU tG1 = 85 oF H1 = 36 tW1 = 80 oF tL2 = 110 oF tL1 = ? A’ L/Gs sama Grs operasi sejajar 66.8 A Garis operasi baru A’B’: - Sejajar grs operasi AB - Titik A’ terletak pada 110 oF - Titik B’ terletak pada H = 36 B’ 36 31 B Grs operasi A’B’ di trial shg harga NtOG = 3.08 tL1 tL2 87.4 85