ME 401 Suction Line Heat Exchangers. Rankine Refrigerator Enhancement Suction Line Heat Exchanger. Exchange heat between the suction gas line and the liquid line The suction gas (exit from the evaporator) is cool…approximately evaporator temperature
E N D
Rankine Refrigerator EnhancementSuction Line Heat Exchanger • Exchange heat between the suction gas line and the liquid line • The suction gas (exit from the evaporator) is cool…approximately evaporator temperature • The liquid line (exit from condenser) is warm…approximately ambient temperature • Warming (superheating) suction gas increases compressor work • Cooling liquid line refrigerant increases refrigeration capacity • If cooling capacity increases faster than compressor work, then performance is improved • Depends on specific refrigerant characteristics • R134a improves in performance (refrigerators) • R22 decreases in performance (house air conditioners)
Qcond Condenser 2 1 High P Expansion Device Compressor Low P 3 4 Wcomp Evaporator Qevap Rankine Refrigerator Enhancement • Basic System • No enhancement
Qcond Condenser 2 High P 4’ SLH 1 2’ Low P Compressor Expansion Device 3 4 Wcomp Evaporator Qevap Rankine Refrigerator Enhancement • Suction line heat exchanger • Find new points 2’ and 4’
Isentropes change • Increasing superheat increases work Liq x2=0 1 Thot 2’ P 2 Vapor Tcold 3 4’ 4 x4=1 h Suction Line Heat Exchange Note: changes in enthalpy across heat exchanger fluids are equal h2-h2’ = h4’-h4
Expansion Valves Thermostatic expansion valves: See description on: http://www.hvacmechanic.com/txv.htm